13 Specicadjustment
13.1 Heating circuit adjustment
It may be necessary to adjust the by-pass to the design of the
system. The boiler is delivered pre-set open 1/2 turn (1).
1
Key
1 Screwforby-pass
Depending on the design of the system the by-pass may
need further adjustment. It is adjusted clockwise to close and
anti-clockwise to open. This should be balanced to ensure
that it operates if the pump output is adjusted.
Output/pressure curve Ultracom
2
24cxi
60
50
40
30
20
10
0
500 1000 1500
B
1 2 3 4
Key
A Availablepressurebetweenheatingowandreturn(kPa)
B Heatingcircuitowrate(l/h)
1 Speed min, bypass closed
2 Speed max, bypass closed
3 Speed max, bypass middle position
4 Speed max, bypass opened
Output/pressure curve Ultracom
2
30cxi
60
50
40
30
20
10
0
500 1000 1500
B
1 2 3 4
Key
A Availablepressurebetweenheatingowandreturn(kPa)
B Heatingcircuitowrate(l/h)
1 Speed min, bypass closed
2 Speed max, bypass closed
3 Speed max, bypass middle position
4 Speed max, bypass opened
Output/pressure curve Ultracom
2
35cxi
60
50
40
30
20
10
0
500 1000 1500
B
1 2 3 4
Key
A Availablepressurebetweenheatingowandreturn(kPa)
B Heatingcircuitowrate(l/h)
1 Speed min, bypass closed
2 Speed max, bypass closed
3 Speed max, bypass middle position
4 Speed max, bypass opened
13.2 Appliance technical settings and
parameter list
The access to the boilers technical data allows you to adjust the
boiler to the exact system requirements.
Note: the heating power decrease has no effect on the domestic
hot water power.
13.2.1 Installation settings
Press for more than 7 seconds on the button to
access the conguration menu. The screen displays "0".
Press 4 times on the button
under the symbol .
The screen displays "96". This is the installer's password.
Press on
to validate. The screen displays the
parameter "00" and its value "XX”.
Press on button
or under the symbol to access the
parameter to modify.
Press on button
or under the symbol to modify the
value of the parameter.
INSTALLATION