® ® SECTION 62.
Page 1 ® A WORLD LEADER IN VALVE REGULATED LEAD ACID (VRLA) BATTERY POWER FOR PHOTOVOLTAIC AND ALTERNATIVE ENERGY APPLICATIONS • Proven Field Experience Since 1983. • The Absolyte was developed by GNB, in conjunction with Sandia National Laboratories, as the first VRLA, large capacity, deep-cycle battery for photovoltaic applications. • Patented lead-calcium-tin-sliver positive grid alloy provides excellent cycle life for photovoltaic applications.
Page 2 ® Absolyte GP Stackable Module Weights and Dimensions MODULE TYPE NOM VOLTS AH CAP STACKING DIMENSIONS IN MM IN MM IN MM UNPACKED WEIGHT LBS KG LENGTH HEIGHT DEPTH (100 HR) DOMESTIC PACKED WEIGHT EXPORT PACKED WEIGHT LBS KG LBS KG 50G 6-50G05 12 140 17.19 437 8.53 217 16.22 412 157 71 176 80 228 104 6-50G07 12 210 21.69 551 8.53 217 16.22 412 209 95 228 104 280 127 6-50G09 12 290 26.19 665 8.53 217 16.
Page 3 ® Operating Temperature — Temperature excursions between -40°C (-40°F) to +50°C (122°F) allowed (battery performance and life will be affected). CELL SPECIFICATIONS 140-6300 AH @ 100 Hour Rate Container and Cover — Polypropylene. Cycle Life — 1200 cycles at 80% D.O.D. [at 25˚C (77˚F)] when operated per the I&O Manual. Flame retardant UL94 V-0/28% L.O.I. is optional. Separators — Spun glass, microporous matrix. Safety Vent — 3-10 psi opening pressure, self-resealing.
Page 4 ® Absolyte GP Performance Characteristics — Constant Current Amperes to 1.75 Volts Per Cell @ 25°C (77°F) HOURS CELL TYPE 50G 120 100 72 48 36 24 20 12 10 8 50G05 50G07 1.2 1.8 1.4 2.1 1.9 2.9 2.8 4.2 3.6 5.5 5.1 7.7 6 9.1 9.3 14 11 16 13 19 50G09 50G11 50G13 50G15 50G19 50G27 2.4 3.1 3.7 4.3 5.6 8.0 2.9 3.7 4.3 5.1 6.6 9.5 3.9 5.0 5.9 6.9 8.9 13 5.6 7.1 8.5 10 13 19 7.3 9.
Page 5 ® Absolyte GP Performance Characteristics — Constant Current Amperes to 1.80 Volts Per Cell @ 25°C (77°F) HOURS CELL TYPE 50G 120 100 72 48 36 24 20 12 10 8 50G05 50G07 50G09 50G11 50G13 50G15 50G19 1.2 1.8 2.4 3.1 3.6 4.3 5.5 1.4 2.1 2.8 3.6 4.3 5.1 6.5 1.9 2.9 3.9 4.9 5.8 6.8 8.8 2.8 4.2 5.6 7.0 8.4 10 13 3.6 5.4 7.2 9.1 10 13 16 5.1 7.7 10 13 15 18 23 6.0 9.0 12 15 18 21 27 9.2 13 18 23 27 32 42 10 16 21 26 32 37 48 12 19 25 31 38 44 57 50G27 8.0 9.
Page 6 ® Absolyte GP Performance Characteristics — Constant Current Amperes to 1.90 Volts Per Cell @ 25°C (77°F) HOURS CELL TYPE 50G 120 100 72 48 36 24 20 12 10 8 50G05 50G07 50G09 50G11 50G13 50G15 50G19 50G27 1.1 1.6 2.2 2.8 3.3 3.9 5.0 7.3 1.3 1.9 2.6 3.3 3.9 4.6 5.9 8.5 1.7 2.6 3.4 4.4 5.2 6.1 7.8 11 2.4 3.7 4.9 6.2 7.4 9 11 16 3.1 4.8 6.3 8.0 9.6 11 14 21 4.5 6.8 9.1 11 13 16 21 30 5.3 8.0 10 13 16 19 24 35 8.
Page 7 ® Absolyte GP Performance Characteristics Cycle Life vs. Depth of Discharge [at 25°C (77°F)] Life Determined by Age Open Circuit Voltage vs. State of Charge [at 25°C (77°F)] Capacity Retention vs.
Page 8 ® Absolyte GP Performance Curves @ 25°C (77°F) 50G Series 1 to 10 Hours 6 5.5 5 4.5 4 3.5 3 Amp-Hours/Positive 10 9 8 7 Amps/Positive 12 to 100 Hours Amp-Hours/Positive 50G Series Amps/Positive 2.
Page 9 ® Absolyte GP Performance Curves @ 25°C (77°F) 90G Series 1 to 10 Hours 6 5.5 5 4.5 4 3.5 3 Amp-Hours/Positive 10 9 8 7 Amps/Positive 12 to 100 Hours Amp-Hours/Positive 90G Series Amps/Positive 2.
Page 10 ® Absolyte GP Performance Curves @ 25°C (77°F) 100G Series 1 to 10 Hours 6 5.5 5 4.5 4 3.5 3 Amp-Hours/Positive 10 9 8 7 Amps/Positive Amp-Hours/Positive 100G Series 12 to 100 Hours Amps/Positive 2.
® Exide Technologies – The Industry Leader. ® GNB Industrial Power, a division of Exide Technologies is a global leader in stored electrical energy solutions for all major critical reserve power applications and needs. Network power applications include communication/data networks, UPS systems for computers and control systems, electrical power generation and distribution systems, as well as a wide range of other industrial standby power applications.