GNB Absolyte GP Battery Module Data Sheet

®
CELL
TYPE
LENGTH WIDTH
DEPTH OR HEIGHT
UNPACKED DOMESTIC PACKED EXPORT PACKED
WEIGHT WEIGHT WEIGHT
NOM AH
CAP
(100 HR)
IN MM IN MM IN MM LB KG LB KG LB KG
Absolyte GP Single Cell Module Weights and Dimensions
50G
50G05 140 3.80 97 6.49 165 16.00 406 32 15 35 16 44 20
50G07 210 3.80 97 6.49 165 16.00 406 39 18 41 19 51 23
50G11 370 4.55 116 6.49 165 16.00 406 50 23 53 24 61 28
50G13 430 5.30 135 6.49 165 16.00 406 58 26 61 28 69 31
50G15 510 6.05 154 6.55 166 16.00 406 66 30 69 31 77 35
50G19 660 7.67 195 6.67 169 16.00 406 91 41 95 43 112 51
50G27 950 10.67 271 6.67 169 16.00 406 124 56 130 59 147 67
CELL SPECIFICATIONS
140-6300 AH @ 100 Hour Rate
Container and Cover Polypropylene.
Flame retardant UL94 V-0/28% L.O.I. is optional.
Separators Spun glass, microporous matrix.
Safety Vent 3-10 psi opening pressure, self-resealing.
Terminals Solid copper insert.
Positive Plate Patented Lead-Calcium-Tin-Silver grid
alloy.
Negative Plate Lead-Calcium grid alloy.
Operating Temperature Temperature excursions
between -40°C (-40°F) to +50°C (122°F) allowed (battery
performance and life will be affected).
Cycle Life 1200 cycles at 80% D.O.D. [at 25˚C (77˚F)]
when operated per the I&O Manual.
Self Discharge 0.5 to 1.0% per week maximum at
25˚C (77˚F).
Charge Controller Upper Voltage Settings—
at 25°C (77°F) with a maximum charge current of 5% of
nominal C/100 Amp-hour rating.
2.28 ± 0.02 V.P.C. @ 0-2% D.O.D.
2.33 ± 0.02 V.P.C. @ 3-5% D.O.D.
2.38 ± 0.02 V.P.C. @ >5% D.O.D.
For other temperatures and charge currents,
contact GNB for recommendations.
NOTE: Design and/or
specifications subject
to change without
notice. If questions
arise, contact your
local GNB sales
representative for
clarification.