GNB Absolyte GP Battery Module Data Sheet
®
Absolyte GP Performance Characteristics — Constant Current
Amperes to 1.90 Volts Per Cell @ 25°C (77°F)
For additional ratings, refer to section 26.10B.
CELL
HOURS
TYPE
120 100 72 48 36 24 20 12 10 8
50G05 1.1 1.3 1.7 2.4 3.1 4.5 5.3 8.3 9 11
50G07 1.6 1.9 2.6 3.7 4.8 6.8 8.0 12 14 16
50G09 2.2 2.6 3.4 4.9 6.3 9.1 10 16 18 22
50G11 2.8 3.3 4.4 6.2 8.0 11 13 21 23 28
50G13 3.3 3.9 5.2 7.4 9.6 13 16 25 28 33
50G15 3.9 4.6 6.1 9 11 16 19 29 33 39
50G19 5.0 5.9 7.8 11 14 21 24 38 42 50
50G27 7.3 8.5 11 16 21 30 35 55 61 73
90G07 2.8 3.2 4.3 6.2 8.0 11 13 21 24 28
90G09 3.7 4.3 5.8 8.3 10 15 18 28 32 38
90G11 4.6 5.4 7.3 10 13 19 22 35 40 47
90G13 5.6 6.5 8.7 12 16 23 27 42 48 57
90G15 6.5 7.6 10 14 18 27 31 49 56 67
100G13 5.9 7.0 9.4 13 17 25 30 47 54 63
100G15 6.9 8.1 11 15 20 29 35 55 63 74
100G17 7.9 9.3 12 18 23 33 40 63 72 85
100G19 8.9 10 14 20 26 38 45 71 81 95
100G21 9.9 11 15 22 29 42 50 79 90 106
100G23 10 12 17 24 32 46 55 87 99 117
100G25 11 14 18 27 35 50 60 95 108 127
100G27 12 15 20 29 38 55 65 103 117 138
100G29 13 16 22 31 41 59 70 110 126 149
100G31 14 17 23 34 44 63 75 118 135 159
100G33 15 18 25 36 47 67 80 126 144 170
100G39 17 21 28 39 51 75 90 141 162 189
100G45 20 24 33 45 60 87 105 165 189 222
100G51 23 27 36 54 69 99 120 189 216 255
100G57 26 30 42 60 78 114 135 213 243 285
100G63 29 33 45 66 87 126 150 237 270 318
100G69 30 36 51 72 96 138 165 261 297 351
100G75 33 42 54 81 105 150 180 285 324 381
100G81 36 45 60 87 114 165 195 309 351 414
100G87 39 48 66 93 123 177 210 330 378 447
100G93 42 51 69 102 132 189 225 354 405 477
100G99 45 54 75 108 141 201 240 378 432 510
50G
100G
90G
Page 6