Industrial Batteries / Network Power Marathon L / XL »More More energy for safer storage storage««
Network Power > Product overview Industrial Batteries The powerful range of Network Power Energy storage solutions for critical systems that require uninterrupted power supply. GNB® Industrial Power offers powerful batteries for your individual needs. The below table is only indicative and depends on customers' specific applications. For more information please ask a GNB sales representative.
Network Power > Marathon L / XL > Benefits Marathon L / XL The safe storage system with long design life Designed for durability in telecommunications and electric utility applications, the Marathon L/XL series provides high performance and reliability in medium and long duration discharge applications.
Network Power > Marathon L / XL > Technical data Marathon L / XL Technical data Technical characteristics and data Nom. Nominal Capacity Capacity Length Width (l) (b/w) voltage capacity C20 1.80 C1 1.60 V C10 1.80 Vpc 20°C Vpc 20°C mm mm Vpc 20°C Ah Ah Ah Height Height Weight (h1) incl. con- approx. max. nectors kg mm (h2) max. mm Internal Short Terminal Pole resist- circuit pairs ance current mOhm A Type Part number L2V220 NALL020220HM0FA 2 220 236 150 209 136 265 265 16.0 0.
Network Power > Marathon L / XL > Drawings Marathon L / XL Drawings L2V220 L2V270 L2V320 L2V425 L2V470 L2V575 (h) (h) (h) (l) (l) (l) (b/w) (b/w) L6V110 L12V15 L12V24 L12V32 XL12V70 XL12V85 (h) (l) (b/w) XL6V180 XL12V50 (h1) (h2) (h1) (h2) (h1) (h2) (l) (l) (l) (b/w) (l) (b/w) (b/w) Not to scale!.
Network Power > Marathon L / XL > Constant current discharge Marathon L / XL Constant current discharge 1.95 Vpc – Discharge in A at 20 °C Type Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 5h 8h 10 h 20 h L2V220 NALL020220HM0FA 215 203 176 161 146 122 99.0 85.5 55.6 42.0 28.3 19.5 16.2 8.70 L2V270 NALL020270HM0FA 248 237 210 190 174 148 121 105 68.4 51.5 34.7 23.9 19.9 10.
Network Power > Marathon L / XL > Constant current discharge Marathon L / XL Constant current discharge 1.85 Vpc – Discharge in A at 20 °C Type Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 5h 8h 10 h L2V220 NALL020220HM0FA 435 395 324 276 241 192 148 122 75.5 56.4 37.1 25.2 21.0 20 h 11.3 L2V270 NALL020270HM0FA 515 470 389 331 290 233 182 150 92.5 69.2 45.5 30.9 25.7 13.
Network Power > Marathon L / XL > Constant current discharge Marathon L / XL Constant current discharge 1.75 Vpc – Discharge in A at 20 °C Type Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 5h 8h 10 h 20 h L2V220 NALL020220HM0FA 615 545 432 354 302 232 176 141 83.5 61.2 39.6 26.8 22.3 12.0 L2V270 NALL020270HM0FA 740 660 524 434 370 283 214 173 102 75.0 48.6 32.9 27.4 14.
Network Power > Marathon L / XL > Constant current discharge Marathon L / XL Constant current discharge 1.65 Vpc – Discharge in A at 20 °C Type Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 5h 8h 10 h L2V220 NALL020220HM0FA 775 670 500 400 330 249 185 149 87.0 63.0 40.6 27.2 22.6 20 h 12.1 L2V270 NALL020270HM0FA 935 815 610 486 405 305 227 182 106 77.3 49.8 33.4 27.7 14.
Network Power > Marathon L / XL > Constant current discharge Marathon L / XL Constant power discharge 1.90 Vpc – Discharge in W/block at 20 °C Type Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 5h 8h 10 h L2V220 NALL020220HM0FA 615 570 485 420 370 307 246 207 131 99.0 66.4 45.4 37.8 20 h NA L2V270 NALL020270HM0FA 735 675 575 504 448 370 297 251 160 122 81.5 55.7 46.
Network Power > Marathon L / XL > Constant power discharge Marathon L / XL Constant power discharge 1.80 Vpc – Discharge in W/block at 20 °C Type Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 5h 8h 10 h L2V220 NALL020220HM0FA 915 830 675 575 498 398 303 248 151 114 75.0 51.4 43.2 20 h NA L2V270 NALL020270HM0FA 1085 990 810 690 595 480 370 304 186 139 92.0 63.1 53.
Network Power > Marathon L / XL > Constant power discharge Marathon L / XL Constant power discharge 1.70 Vpc – Discharge in W/block at 20 °C Type Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 5h 8h 10 h 20 h L2V220 NALL020220HM0FA 1150 1025 810 670 570 442 336 271 159 117 77.0 52.7 44.1 NA L2V270 NALL020270HM0FA 1375 1230 975 805 690 537 403 331 195 144 94.5 64.7 54.
Network Power > Marathon L / XL > Constant power discharge Marathon L / XL Constant power discharge 1.60 Vpc – Discharge in W/block at 20 °C Type Part number 3 min 5 min 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 5h 8h 10 h L2V220 NALL020220HM0FA 1300 1145 880 715 600 460 343 278 163 119 78.2 53.2 44.3 20 h NA L2V270 NALL020270HM0FA 1555 1365 1050 855 725 555 417 338 199 146 96.0 65.3 54.
Network Power > Service Battery Service – Energy Solutions Keeping your business on the move GNB® is the Expert Who could do this job better than the professionals of a company with more than 100 years of experience in battery development, production and application? Leave the responsibility for the maintenance of your batteries and chargers to the professionals: a GNB service contract provides you with exceptional economic advantages through time savings, cost savings and safety! Installation of Batterie
Network Power > Marathon L / XL > Notes Marathon L/XL Notes
© GNB Industrial Power GNB® INDUSTRIAL POWER – A division of Exide Technologies – offers an extensive range of storage products and services, including solutions for telecommunication systems, railway applications, mining, photovoltaic (solar energy), uninterrupted power supply (UPS), electrical power generation and distribution, fork lifts and electric vehicles. Exide Technologies takes pride in its commitment to a better environment.