Installation Guide
Copyright © 2015 Nortek Security & Control LLC 17
Feature Description Range
Default
Setting
Heat - Cool
Delta
Sets the minimum separa on between hea ng
and cooling setpoints. NOTE: Attempts to lower
cooling setpoint below the heating setpoint will
PUSH the heating setpoint down to maintain
this separation. The same applies to setting the
heating setpoint above the cooling setpoint, it
will PUSH the cooling setpoint up to maintain the
setpoint delta separation
3 to 15
degrees
3F (1C)
Hea ng Stage
1 on Threshold
Sets the delta from setpoint that stage 1 hea ng starts 1 to 6
degrees
1
Hea ng
Stage 1 Off
Threshold
Sets the delta from setpoint that stage 1 hea ng stops.
Stage 1 turns off at setpoint + Delta Stage 1.
0 to 5
degrees
0
Hea ng
Stage 2 On
Threshold
Sets the delta from setpoint that stage 2 hea ng starts 2 to 7
degrees
2
Hea ng
Stage 2 Off
Threshold
Sets the delay from setpoint that stage 2 hea ng stops.
Stage 2 turns off at setpoint + Delta Stage 2.
0 to 6
degrees
0
Aux Heat On
Threshold
Sets the delta from setpoint that stage 3 hea ng starts 3 to 8
degrees
3
Aux Heat Off
Threshold
Sets the delta from setpoint that stage 3 hea ng stops.
Stage 3 turns off at setpoint + Delta Stage 3
0 to 7
degrees
0
Cooling
Stage 1 On
Threshold
Sets the delta from setpoint that stage 1 cooling starts. 1 to 7
degrees
1
Cooling
Stage 1 Off
Threshold
Sets the delta from setpoint that stage 1 cooling stops.
Stage 1 turns off at setpoint - Delta Stage 1
0 to 6
degrees
0
Cooling
Stage 2 On
Threshold
Sets the delta from setpoint that stage 2 cooling starts. 2 to 8
degrees
2
Cooling
Stage 2 Off
Threshold
Sets the delta from setpoint that stage 2 cooling stops.
Stage 2 turns off at setpoint - Delta Stage 2.
0 to 7
degrees
0
Restore
Defaults
Restores all se ngs to factory defaults.
Press Yes to restore defaults
Press No to exit and not restore defaults
Y or N N