Manual

8
Connecting the Gas Line
Consult local building codes before gas line installation.
This gas fireplace is designed to accept a 3/8" male flare
fitting attached to a 1/2" supply line. Have the gas line
installed by a qualified service person in accordance
with all building codes. Install gas line to fireplace on the
right side attaching gas line to the gas flex line inside the
control box accessed by opening the control box door.
Finishing the Wall
Finish the wall with the material of your choice. Do
not install a combustible mantle or other combustible
projection above the fireplace opening unless it is a
minimum of 12 inches above top of fireplace opening.
*Non-combustible material used between top of opening
and mantle must not exceed 3" in depth. (Figure 8.1)
CAUTION: All joints between the finished wall and the fireplace surround (Top and Sides) can
only be sealed with non-combustible material. Only non-combustible material can be applied as
facing to the fireplace surround. (Figure 8.1)
Hearth Extension
A Hearth Extension may be installed. But it is not required for decorative gas appliances.
Gas Log Installation
1. Fill burner pan with vermiculite supplied with log set. Note! On L.P. models be careful not
to pour vermiculite over brass air mixer attached to burner pan. Air mixer holes must not be
obstructed!
2. Spread the ember material over the vermiculite.
3. At this time, we suggest you test fire the burner. Refer to start up instructions on page 12.
Important! The fireplace damper must be in full open position.
4. Place the grate over the burner and install the logs as illustrated on page 9.
5. The last step is to cover floor of fireplace with volcanic rock around the sides and in front
of burner pan to enhance overall appearance. Note: On L.P. models be careful not to
pour black cinders over brass air mixer attached to burner pan. Air mixer holes must not
be obstructed!
STUD
2X4
HEADER
FINISHED
WALL
NON-COMBUSTIBLE
SEAL JOINT
MANTLE
12" MIN
TOP OF
OPENING
Figure 8.1
CONTROL
KNOB
DUCT
TERMINATION
RAIN CAP
CAULKING
WALL
OUTER
CASING
DUCT
COLLAR
Figure 7.2
Installing Outside Air Kit
Model SF3624-TV is supplied with the component parts for outside combustion with the
exception of the 4" flex duct. It is recommended that the outside air system be used whenever
possible. Connect 4" Class-1 Flex duct or Metal Vent to duct collar on side of firebox, run duct
to fresh air source and terminate using duct termination cap. The Outside air can be opened
by pushing control knob toward back of fireplace and closed by pulling towards front (Refer to
figure 7.2).