CPC C ommercial 7½- to 12½-Ton Three-Phase Packaged Air Conditioners Cooling Capacity: 90,000 — 118,000 BTU/h up to 11.
Product Specifications Nomenclature Brand C C 1 P 2 C 3 150 4,5,6 045 7,8,9 3 10 B 11 Commercial X 13 X 14 X A B C F Configura;on P Packaged Unit Applica;on C Cooling G Gas Heat H Heat Pump Nominal Gross Cooling Capacity 036 3 Tons 102 048 4 Tons 120 060 5 Tons 150 072 6 Tons 180 090 7½ Tons 240 X 12 M X A B 8½ Tons 10 Tons 12½ tons 15 Tons 20 Tons C D Nominal Hea;ng Capacity CPG 045 45,000 BTU/h 090 90,
Product Specifications Product Specifications — 7½ Tons A Models B Models CPC090 XXX3BXXX CPC090 XXX4BXXX CPC090 XXX3BXXX CPC090 XXX4BXXX CPC090 XXX7BXXX Total BTU/h 90,000 90,000 90,000 90,000 90,000 Sensible BTU/h 65,700 65,700 64,000 64,000 64,000 11.5 / 11.5 11.5 / 11.5 11.5 / 11.5 11.5 / 11.5 11.5 / 11.5 Cooling Capacity EER / IEER Decibels AHRI Reference #s 82.0 82.0 82.0 82.0 82.
Product Specifications Product Specifications — 8½ Tons CPC102 XXX3BXXX CPC102 XXX4BXXX CPC102 XXX7BXXX 102,000 102,000 102,000 Cooling Capacity Total, BTU/h Sensible BTU/h EER / IEER Decibels 70,380 70,380 70,380 11.3 / 11.2 11.3 / 11.2 11.3 / 11.2 83 83 83 3620220 3620220 3620220 Belt Drive Belt Drive Belt Drive 3,400 3,400 3,400 7.8 3.9 2.3 Horsepower - RPM 1725 1725 1725 Piston Size (Cooling) 0.08 0.08 0.
Product Specifications Product Specifications — 10 Tons CPC120 XXX3BXXX CPC120 XXX4BXXX CPC120 XXX7BXXX 118,000 118,000 118,000 Cooling Capacity Total BTU/h Sensible BTU/h EER / IEER Decibels 87,300 87,300 87,300 11.5 / 11.2 11.5 / 11.2 11.5 / 11.2 83.0 83.0 83.0 3023833 3023833 3023833 Belt Drive Belt Drive Belt Drive 4,000 4,000 4,000 7.8 3.9 2.7 Horsepower - RPM 2.0/1725 2.0/1725 2.0/1725 Piston Size (Cooling) 0.086 0.086 0.
Product Specifications Product Specifications — 12½ Tons Cooling Capacity Total, BTU/h Sensible BTU/h EER / IPLV Decibels ARI Reference #s Evapoartor Motor / Coil Motor Type Indoor Nominal CFM Indoor Motor FLA (Cooling) Horsepower - RPM Piston Size (Cooling) Filter Size Drain Size (NPT) R-410A Refrigerant Charge Cir #1 & #2 Evaporator Coil Face Area (ft2) Rows Deep / Fins per Inch Condenser Fan / Coil Quantity of condenser Fan Motors Horsepower - RPM Fan Diameter / # Fan Blades Outdoor Nominal CFM Face Ar
Product Specifications Airflow Data — 7½ Tons Standard Belt Drive — Down Shot ESP (“ W.C.) Turns Open 0 CFM RPM 1 BHP CFM RPM 2 BHP CFM RPM 3 BHP 4 RPM BHP CFM 3617 704 1.07 3293 653 0.84 3541 749 1.15 3179 704 0.88 2757 656 0.66 2606 710 0.71 0.1 0.3 0.5 0.7 0.9 3303 890 1.41 1.1 2838 897 1.23 3447 798 1.23 3049 754 0.94 3400 848 1.33 2950 798 1.01 2474 754 0.75 2871 848 1.11 2408 804 0.
Product Specifications Airflow Data — 8½ Tons Standard Belt Drive — Down Shot ESP (“ W.C.) Turns Open 0 CFM RPM 1 BHP CFM RPM 2 BHP CFM RPM 3 BHP 4 RPM BHP CFM 3467 701 1.04 3143 650 0.81 3391 746 1.12 3029 701 0.85 2607 653 0.63 2899 751 0.91 2456 707 0.68 0.1 0.3 0.5 0.7 0.9 3153 887 1.38 1.1 2688 894 1.20 3250 845 1.30 2721 845 1.08 3297 795 1.20 2800 795 0.98 RPM 5 CFM BHP CFM RPM BHP High-Static Belt-Drive — Down Shot ESP (“ W.C.
Product Specifications Airflow Data — 10 Tons Standard Belt-Drive — Down Shot ESP (“ W.C.) Turns Open 0 CFM RPM 1 BHP 2 BHP CFM 4632 781 1.76 4203 742 1.41 4488 825 1.85 4183 783 1.54 3733 748 1.23 3717 786 1.31 0.6 4442 880 2.02 4066 830 1.63 0.8 4001 885 1.77 3622 835 1.41 1 3603 890 1.55 BHP CFM RPM 4 RPM 0.2 0.4 RPM 3 CFM BHP CFM 5 RPM BHP CFM RPM BHP 3927 691 1.17 3510 658 0.9 3512 693 1 1.
Product Specifications Airflow Data — 12½ Tons Standard Belt Drive --- Down Shot ESP (" W.C.) Turns Open 0 CFM 1 BHP CFM 2 BHP 0.2 3 4 5 CFM BHP CFM BHP CFM BHP CFM BHP 5378 2.35 4967 1.92 4710 1.59 4512 1.33 4319 1.40 4030 1.13 0.4 5514 2.92 5349 2.56 4750 1.97 4583 1.71 0.6 5204 2.69 4919 2.27 4488 1.81 4258 1.54 0.8 4830 2.42 4649 2.09 4019 1.55 1.0 4497 2.19 4264 1.86 High-Static Belt Drive --- Down Shot ESP (" W.C.
Product Specifications Heat Kit Electrical Data (Blower Only, Heat Mode) — 7½ Tons (A Modles) Model and Heat Kit Usage CPC090XXX3BXXX EHK3-16 EHK3-30 EHK3-45 Model and Heat Kit Usage MCA¹ at 208 / 240V MOP² (amps) at 208 / 240V Actual kW at 240V Recommended Airflow Range 40 48 / 55 87 / 100 121 / 139 50 50 / 60 90 / 100 125 / 150 15 30 43 3000 - 3375 CFM 3000 - 3375 CFM 3000 - 3375 CFM MCA¹ at 480V MOP² (amps) at 480V Actual kW at 480V Recommended Airflow Range 19 27 50 70 25 30 50 70 15 30
Product Specifications Heat Kit Electrical Data (Blower Only, Heat Mode) — 7½ Tons (B Modles) Model and Heat Kit Usage CPC090XXX3BXXX EHK3-16 EHK3-30 EHK3-45 Model and Heat Kit Usage MCA¹ at 240V MOP² (amps) at 240V Actual kW at 240V Recommended Airflow Range 37 51 97 136 50 60 100 150 15 30 43 3000 - 3375 CFM 3000 - 3375 CFM 3000 - 3375 CFM MCA¹ at 480V MOP² (amps) at 480V Actual kW at 480V Recommended Airflow Range 18 26 48 68 20 30 50 70 15 30 43 3000 - 3375 CFM 3000 - 3375 CFM 3000 - 33
Product Specifications Heat Kit Electrical Data (Blower Only, Heat Mode) — 8½ Tons Model and Heat Kit Usage MCA¹ at 208 / 240V MOP² (amps) at 208 / 240V 43 50 CPC102XXX3BXXX Actual kW at 240V Recommended Airflow Range (Downshot) Recommended Airflow Range (Horizontal) EHK3-16 55 60 15 3400 - 3825 CFM 3400 - 3825 CFM EHK3-30 100 100 30 3400 - 3825 CFM 3400 - 3825 CFM EHK3-45 139 150 43 3400 - 3825 CFM 3400 - 3825 CFM MCA¹ at 480V MOP² (amps) at 480V Actual kW at 480V Recommended
Product Specifications Heat Kit Electrical Data (Blower Only, Heat Mode) — 10 Tons Model and Heat Kit Usage MCA¹ at 208 / 240V MOP² (amps) at 208 / 240V Actual kW at 240V Recommended Airflow Range 49 48 / 55 87 / 100 121 / 139 60 50 / 60 90 / 100 125 / 150 15 30 43 3500 - 4500 CFM 3500 - 4500 CFM 4000 - 4500 CFM MCA¹ at 208 / 240V MOP² (amps) at 208 / 240V Actual kW at 240V Recommended Airflow Range 50 49 / 57 88 / 102 122 / 141 60 50 / 60 90 / 110 125 / 150 15 30 43 3500 - 4500 CFM 3500 -
Product Specifications Heat Kit Electrical Data (Blower Only, Heat Mode) — 12½ Tons Model and Heat Kit Usage CPC150***3B*** MCA1 at 208 / 240V MOP2 (amps) at 208 / 240V 65 80 Actual kW at 240V Recommended Airflow Range EHK3-16 65 80 15 4000 - 5600 EHK3-30 102 110 30 4300 - 5600 EHK3-45 141 150 43 4500 - 5600 MCA1 at 208 / 240V MOP2 (amps) at 208 / 240V Actual kW at 240V Recommended Airflow Range CPC150***4B*** 31 40 EHK4-16 31 40 15 4000 - 5600 EHK4-30 51 60 30 4300 -
www.goodmanmfg.com 89.7 0.83 20 6.24 20.5 236 109 87.1 0.79 21 6.19 20.4 234 108 80.4 0.77 24 6.06 20.0 227 105 MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR 2400 3000 3375 59 88.2 0.73 18 6.19 20.4 234 108 85.6 0.70 18 6.15 20.3 231 107 79.0 0.67 20 6.01 19.9 224 104 Airflow MBh S/T ∆T kW 3375 Amps Hi PR Lo PR MBh S/T ∆T kW 3000 Amps Hi PR Lo PR MBh S/T ∆T 2400 kW Amps Hi PR Lo PR 71 - 92.3 100.0 107.3 0.75 0.56 0.36 19 15 11 6.36 6.55 6.75 20.
SS-CPC90-150 www.goodmanmfg.com 92.9 0.96 24 6.33 20.8 241 112 90.2 0.91 25 6.29 20.7 238 110 83.2 0.88 28 6.15 20.3 231 107 MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR 2400 3000 3375 59 91.3 0.91 23 6.29 20.7 238 110 88.6 0.87 24 6.24 20.5 236 109 81.8 0.84 26 6.10 20.1 229 106 Airflow MBh S/T ∆T kW 3375 Amps Hi PR Lo PR MBh S/T ∆T kW 3000 Amps Hi PR Lo PR MBh S/T ∆T 2400 kW Amps Hi PR Lo PR 94.7 0.92 24 6.46 21.2 259 119 91.9 0.88 25 6.41 21.
www.goodmanmfg.com 87.7 0.82 20 6.31 21.2 236 104 85.1 0.78 20 6.27 21.1 234 103 78.6 0.76 23 6.14 20.7 227 100 MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR 2400 3000 3375 59 86.2 0.72 17 6.27 21.1 234 103 83.7 0.69 18 6.23 21.0 231 102 77.3 0.67 20 6.10 20.6 224 99 Airflow MBh S/T ∆T kW 3375 Amps Hi PR Lo PR MBh S/T ∆T kW 3000 Amps Hi PR Lo PR MBh S/T ∆T 2400 kW Amps Hi PR Lo PR 90.3 0.74 18 6.43 21.6 254 111 87.7 0.70 19 6.39 21.4 252 110 80.9 0.
SS-CPC90-150 www.goodmanmfg.com 90.8 0.95 23 6.40 21.5 241 107 88.2 0.90 24 6.36 21.4 238 106 81.4 0.87 27 6.22 21.0 231 102 MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR 2400 3000 3375 59 89.3 0.90 22 6.36 21.4 238 106 86.7 0.86 23 6.31 21.2 236 105 80.0 0.83 25 6.18 20.9 229 101 Airflow MBh S/T ∆T kW 3375 Amps Hi PR Lo PR MBh S/T ∆T kW 3000 Amps Hi PR Lo PR MBh S/T ∆T 2400 kW Amps Hi PR Lo PR 92.6 0.91 23 6.52 21.8 259 113 89.9 0.87 24 6.48 21.
www.goodmanmfg.com MBh 101.6 104.7 S/T 0.79 0.71 ∆T 20 19 kW 8.90 8.90 HI PR 247 266 LO PR 105 111 2800 3600 91.1 0.73 22 8.90 237 101 MBh S/T ∆T kW HI PR LO PR 3200 2800 87.5 0.66 19 8.90 264 105 94.8 0.69 19 8.90 272 108 90.7 0.55 16 8.90 284 112 99.3 0.38 12 8.90 299 122 98.2 107.6 0.57 0.40 16 12 8.90 8.90 292 309 115 126 59 63 67 97.6 101.2 110.9 0.72 0.60 0.42 18 16 12 8.90 8.90 8.90 274 295 312 109 116 127 89.0 0.75 22 8.90 266 106 118.0 96.4 0.33 0.78 11 22 8.90 8.
SS-CPC90-150 www.goodmanmfg.com MBh S/T ∆T kW HI PR LO PR 3200 2800 90.5 0.82 25 8.90 269 107 92.5 0.77 23 8.90 289 114 92.1 0.86 26 8.90 272 108 93.9 0.83 26 8.90 292 115 114.5 95.8 0.49 0.88 16 24 8.90 8.90 329 315 137 115 71 59 117.9 98.6 0.51 0.92 15 23 8.90 8.90 332 318 138 116 109.8 0.82 23 8.90 321 131 90.3 0.79 24 8.90 329 119 98.4 104.9 89.9 0.75 0.61 0.89 24 21 26 8.90 8.90 8.90 309 322 309 126 134 113 113.7 97.4 0.63 0.92 21 26 8.90 8.90 332 318 138 116 114.3 97.9 0.68 0.
www.goodmanmfg.com 3200 4000 4500 3200 4000 4500 67 15 105 103.6 107.4 117.7 0.68 MBh S/T 131 314 12 0.45 118 295 16 0.61 129 311 12 0.43 - 136 358 12 0.46 123 335 16 0.63 134 354 12 0.44 19 143 407 12 0.47 141 403 12 0.45 24 239 103 ∆T Hi Pr Lo Pr 110 257 22 0.69 120 272 18 0.53 128 284 12 0.34 109 268 24 0.81 116 289 22 0.72 120 127 305 18 0.55 131 135 318 12 0.35 139 328 11 113 305 24 0.
SS-CPC90-150 www.goodmanmfg.com 3200 4000 4500 3200 4000 4500 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 22 24 28 244 105 ∆T Hi Pr Lo Pr 112 263 28 0.86 122 277 26 0.78 130 289 23 0.63 111 274 28 0.93 118 295 28 0.89 122 129 311 26 0.81 133 138 325 23 0.65 142 335 21 116 311 28 0.95 119 321 26 123 335 28 0.92 127 346 25 134 354 26 0.83 138 365 24 121 355 29 0.98 125 366 25 1.
www.goodmanmfg.com 145.5 0.80 23 10.50 36.5 249 102 141.3 0.76 24 10.42 36.3 247 101 130.4 0.73 26 10.17 35.5 240 97 MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR 3360 4200 4725 59 143.1 0.70 20 10.42 36.3 247 100 138.9 0.67 20 10.33 36.0 244 99 128.2 0.65 23 10.09 35.3 237 97 Airflow MBh S/T ∆T kW 4725 Amps Hi PR Lo PR MBh S/T ∆T kW 4200 Amps Hi PR Lo PR MBh S/T ∆T 3360 kW Amps Hi PR Lo PR 149.8 0.71 21 10.72 37.2 268 108 145.4 0.68 22 10.64 36.
SS-CPC90-150 www.goodmanmfg.com 150.7 0.92 27 10.67 37.0 254 104 146.3 0.88 28 10.58 36.8 252 103 135.0 0.85 31 10.33 36.0 244 99 MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR MBh S/T ∆T kW Amps Hi PR Lo PR 3360 4200 4725 59 148.1 0.88 25 10.58 36.8 252 103 143.8 0.84 26 10.50 36.5 249 102 132.7 0.81 29 10.25 35.8 242 98 Airflow MBh S/T ∆T kW 4725 Amps Hi PR Lo PR MBh S/T ∆T kW 4200 Amps Hi PR Lo PR MBh S/T ∆T 3360 kW Amps Hi PR Lo PR 153.6 0.89 26 10.89 37.7 274 110 149.1 0.
Product Specifications APPENDIX C UNIT DIMENSIONS Dimensions 7.5 Y 8.5 10 12.
Product Specifications Unit Clearances Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit operation. Leave a total clearance of 75” on the main control panel side of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48” on all other sides of the unit for possible compressor removal or service access, and to ensure proper ventilation and condenser airflow. Do not install the unit beneath any obstruction.
Product Specifications Roof Curb Installation — Rigging Provisions for forks have been included in the unit base frame. No other fork locations are approved. • Unit must be lifted by the four lifting holes located at the base frame corners. • Lifting cables should be attached to the unit with shackles. • The distance between the crane hook and the top of the unit must not be less than 60”. • Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables.
Product Specifications Roof Curb Installation (cont.) 3-D View 92¼ 15⅜ x 31⅛ Supply Opening 14⅝ x 38⅜ Return Opening Curb installations must comply with local codes and should follow the established guidelines of the National Roofing Contractors Association. Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb.
Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring. ⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡ Product Specifications Wiring Diagram — CPC090-120 (for models with serial numbers 0907 and below) 30 www.goodmanmfg.
Product Specifications Wiring Diagram — CPC090-120 (cont.) (for models with serial numbers 0907 and below) Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring. SS-CPC90-150 ⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. www.goodmanmfg.
Product Specifications Wiring Diagram — CPC090-150 SMOKE/FIRE DETECTOR REPLACES JUMPER RD G BL BR RD GR SPEED UP NO K1 COM K1 NOTE #2 NC M1 M2 C S1 PK RD GR 2 3 RD BL YL 208 240 460 575 T3 RD L3 L2 T2 C 24V L1 T1 BL BL PU BK BL TR 1 BR S2 EBTDR R XFMR-R XFMR-C C TB1 OR BK OR CC2 BK YL BK RD SEE NOTE #2 OR RD PB P O W E R S U P P L Y BL BL BK BL BK OR BK L1 RD OR GR L3 L2 PU T1 T2 BK YL COMP2 CM2 L2 BK GND C L1 T1 BK CC1 BR BK T3 T2 T1
Product Specifications Wiring Diagram — CPC090-150 (cont.
Product Specifications Accessories Item # Description Fits Model Sizes 14CURB90150 Roof Curb 14" Tall 7½-12½ tons 25FD90150 25% Manual Fresh Air Damper 7½-12½ tons 25MFD90150 25% Motorized Fresh Air Damper 7½-12½ tons BRD3672 Horizontal Barometric Relief Damper (two required) 7½-12½ tons CDK120 Concentric Duct Kit 10 tons CDK150 Concentric Duct Kit 12½ tons CDK90102 Concentric Duct Kit 7½-8½ tons DNBBS90150 Burglar Bar Sleeves: Includes Supply & Return 7½-12½ tons DNECONGS90120
Product Specifications Notes SS-CPC90-150 www.goodmanmfg.
Product Specifications Notes Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2011 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA. 36 www.goodmanmfg.