ACNF Air Handler Submittal
4 www.goodmanmfg.com SS-GACNF
SS-GACNF www.goodmanmfg.com 5
Product Specifications
ACNF24
1016
ACNF25
0016
ACNF25
0516
ACNF25
0616
ACNF25
0816
ACNF25
1016
ACNF30
0016
ACNF30
0516
Cooling (BTU/h) 24,000 24,000 24,000 24,000 24,000 24,000 30,000 30,000
Piston Size² 0.057 0.055 0.055 0.055 0.055 0.055 0.061 0.061
Diameter 6.31 6.31 6.31 6.31 6.31 6.31 6.75 6.75
Width 8.25 8.25 8.25 8.25 8.25 8.25 8.25 8.25
Coil Drain Connect FPT 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
FLA 1.29 2 2 2 2 2 1.29 1.29
HP 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Liquid ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾"
Voltage 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Min Circuit Ampacity @ 230V 55 2.5 28.6 35.1 42 56 1.6 28
Min Circuit Ampacity @ 208V 49.8 2.5 26 32 38.4 50.7 1.6 25.3
Max. Overcurrent Device @ 230V 60 15 30 40 45 60 15 30
Max. Overcurrent Device @ 208V 50 15 30 35 40 60 15 30
Minimum Voltage VAC 197 197 197 197 197 197 197 197
Maximum Voltage VAC 253 253 253 253 253 253 253 253
kW @ 230 Volts 9.8 0.0 4.8 6.0 7.3 9.8 0.0 4.8
BTU/h @ 230 Volts 33,500 0 16,400 20,500 24,900 33,500 0 16,400
69 69 69 69 69 69 79 79
¹ CFM @ .2 stac
Note: When the room thermostat calls for second stage heat, the rst stage (heat pump) operaon must be locked out. When matching the
“AC” unit that has electric heat with a heat pump, order “HEAT PUMP SHUT OFF KIT HPSK-01.” The ACXX-00 units do not require this kit.