ACNF Air Handler Submittal

4 www.goodmanmfg.com SS-GACNF
SS-GACNF www.goodmanmfg.com 5
Product Specifications
ACNF30
0616
ACNF30
0816
ACNF30
1016
ACNF31
0016
ACNF31
0516
ACNF31
0616
ACNF31
0816
ACNF31
1016

Cooling (BTU/h) 30,000 30,000 30,000 30,000 30,000 30,000 30,000 30,000
Piston Size² 0.061 0.061 0.061 0.059 0.059 0.059 0.059 0.059

Diameter 6.75 6.75 6.75 6.75 6.75 6.75 6.75 6.75
Width 8.25 8.25 8.25 8.25 8.25 8.25 8.25 8.25
Coil Drain Connect FPT 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"

FLA 1.29 1.29 1.29 2 2 2 2 2
HP 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4

Liquid ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾"

Voltage 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Min Circuit Ampacity @ 230V 34.2 41 55 2.5 28.6 35.1 42 56
Min Circuit Ampacity @ 208V 31 37.6 49.8 2.5 26 32 38.4 50.7
Max. Overcurrent Device @ 230V 35 45 60 15 30 40 45 60
Max. Overcurrent Device @ 208V 35 40 50 15 30 35 40 60
Minimum Voltage VAC 197 197 197 197 197 197 197 197
Maximum Voltage VAC 253 253 253 253 253 253 253 253

kW @ 230 Volts 6.0 7.3 9.8 0.0 4.8 6.0 7.3 9.8
BTU/h @ 230 Volts 20,500 24,900 33,500 0 16,400 20,500 24,900 33,500
 79 79 79 79 79 79 79 79
¹ CFM @ .2 stac
Note: When the room thermostat calls for second stage heat, the rst stage (heat pump) operaon must be locked out. When matching the
AC” unit that has electric heat with a heat pump, order “HEAT PUMP SHUT OFF KIT HPSK-01.” The ACXX-00 units do not require this kit.