AMST Installation Manual
18
NOTE:
1.
2. The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on
rating plate.
3.
4.
applications.
Speed
Tap
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
T1 1165 1140
1085
1065 990 975 895 880 765
T2 1210 1185 1130 1110 1040 1025 950 935 830
T3 1215 1190 1135 1120 1055 1040 960 945 835
T4 1495 1470 1425 1415 1365 1355 1305 1295 1220
T5 1435 1410 1360 1345 1295 1285 1220 1210 1140
T6 1410 1385 1335 1325 1280 1270 1195 1185 1115
T7 1440 1415 1365 1355 1305 1295 1235 1225 1155
T8 1230 1205 1150 1135 1070 1060 990 975 850
T9 1495 1470 1425 1415 1365 1355 1305 1295 1220
T1 1420 1390 1330 1310 1235 1220 1135 1125 1050
T2 1580 1550 1490 1470 1400 1390 1315 1305 1230
T3 1635 1610 1560 1545 1480 1470 1400 1390 1315
T4 1735 1710 1660 1640 1560 1550 1485 1475 1410
T5 1820 1795 1750 1735 1680 1670 1605 1595 1525
T6 1465 1435 1375 1355 1280 1265 1165 1155 1065
T7 1725 1700 1650 1635 1570 1560 1495 1485 1420
T8 1755 1730 1680 1665 1595 1585 1515 1505 1425
T9 1325 1295 1230 1210 1130 1115 1025 1015 930
T1 1425 1395 1335 1320 1250 1240 1165 1155 1070
T2 1510 1480 1425 1410 1345 1335 1270 1260 1185
T3 1605 1580 1525 1510 1450 1440 1375 1365 1300
T4 1875 1855 1810 1795 1735 1725 1670 1665 1605
T5 1755 1730 1680 1665 1605 1595 1535 1525 1465
T6 1350 1320 1260 1245 1175 1160 1085 1075 980
T7 1140 1105 1040 1020 935 915 805 790 685
T8 1605 1580 1525 1510 1450 1440 1375 1365 1300
T9 1605 1580 1525 1510 1450 1440 1375 1365 1300
T1 1215 1175 1095 1070 975 950 790 780 700
T6 1815 1785 1725 1710 1650 1640 1570 1560 1490
T7 1360 1325 1250 1230 1145 1125 1010 990 850
T8 2070 2045 1995 1980 1930 1920 1855 1845 1785
T9 1970 1945 1895 1880 1815 1805 1740 1730 1660
AMST60DU1400AA
Model
CFM @ STATIC PRESSURE (IN W.C.)
AMST42CU1400AA
AMST48CU1400AA
AMST48DU1400AA