Installation INstructions

14
NOTE: Airflow blink codes are approximations of actual airflow. Airflows provided
are at 0.3 static.
TAPS1S2S3S4S5S6S12S13
A OFF OFF OFF OFF OFF OFF OFF OFF
B ON OFF ON OFF ON OFF ON OFF
C OFF ON OFF ON OFF ON OFF ON
D ONONONONONONON ON
A
B
C
D
SPEED SELECTION DIP SWITCHES
COOL
SELECTION
SWITCHES
ADJUST
SELECTION
SWITCHES
PROFILE
SELECTION
SWITCHES
CONTINUOUS
FAN
SPEED
PROFILES PRE-RUN SHORT-RUN OFF DELAY
---- ---- 60 SEC. / 100%
---- 30 SEC. / 50% 60 SEC. / 100%
TO SET AIRFLOW
: (1) Select model and desired HIGH STAGE COOLING
AIRFLOW. Determine the corresponding TAP (A, B, C, D). Set DIP switches S1
and S2 to the appropriate ON / OFF positions.
(2) Select model and installed electric heater size. Set DIP switches S9, S10
and S11 to the appropriate ON / OFF positions.
(3) If airflow adjustment is required, set TRIM ENABLE SWITCH S8 to ON (OFF =
0% Trim) and set S3 and S4 to appropriate ON / OFF positions. TAP A is +5%,
TAP B is - 5%, TAP C is +10%. TAP D is -10%.
TO SET COMFORT MODE:
Select desired Comfort Mode Profile. (see
profiles above). Set DIP switches S5 and S6 to appropriate ON / OFF positions.
DEHUMIDIFICATION:
To enable, set DIP switch S7 to ON. Cooling airflow will
be reduced to 85% of nominal value during cool call when DEHUM command is
present. To disable, set S7 to OFF.
CONTINUOUS FAN SPEED
: Use DIP switches S12 and S13 to select one of
the 4 continuous fan speeds, TAP A is 25%, TAP B is 50%, TAP C is 75%, TAP
D is 100%.
NOTES:
1. Airflow data shown applies to legacy mode operation only. For a fully
communicating system, please see the outdoor unit's installation instructions for
cooling and heat pump airflow data. See ComfortNet System- Airflow
Consideration section for details.
2. Airflow blink codes are approximations of actual airflow.
---- 7.5 MIN. / 82% 60 SEC. / 100%
30 SEC. / 50% 7.5 MIN. / 82% 30 SEC. / 50%
Note: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation
* Within thermostat user menu CTK0* communicating thermostat will display 20KW for OFF- OFF- ON dip switch selection, 21kW
for OFF-OFF-OFF dip swith selection.
NR - Not rated
For match up with a 3 ton outdoor unit
Airflow for 5kW up to 15kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON
For match up with a 3.5 ton outdoor unit: Heater kit applicaƟon shall not exceed 20kW
Airflow for 5 kW up to 20kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF
MODEL
Tap Low Stage High Stage
A 410 610
B 565 840
C 650 970
D 685 1020
A 375 610
B 545 795
C 630 930
D 740 1085
A 450 675
B 520 780
C 660 985
D 750 1115
A 665 990
B 770 1150
C 815 1215
D 910 1360
A 710 875
B 745 1225
C 880 1410
D 975 1595
A 595 870
B 705 1050
C 835 1260
D 870 1315
A 610 875
B 810 1225
C 940 140
D 1070 1595
A 590 865
B 700 1055
C 770 1210
D 885 1375
A 1040 1445
B 1260 1790
C 16330 1890
D 1395 1990
A 820 1195
B 895 1320
C 995 1460
D 1056 1530
A 1080 1630
B 1210 1820
C 1280 1925
D 1350 2025
Cooling/Heat Pump Airflow Table
AVPTC33C14
AVPTC39C14
AVPTC49C14
AVPTC25B14
AVPTC35B14
AVPTC29B14
AVPTC37B14
AVPTC31C14
AVPTC37C14
AVPTC59C14
AVPTC37D14
AVPTC59D14
AVPTC49D14
AVPTC61D14
DIP SWITCH SETTING & AIRFLOW TABLE FOR ELECTRIC HEAT
HTR KW S9 S10 S11 AVPTC25B14 AVPTC29B14
AVPTC35B14
AVPTC37B14
AVPTC33C14 AVPTC39C14 AVPTC49C14 AVPTC37C14 AVPTC59C14 AVPTC37D14 AVPTC59D14 AVPTC49D14 II
AVPTC61D14 III AVPTC31C14
3ONONON
550 550 550
600
600
5ONONOFF
650 650 650
700 850 1170
850 1170 1240 1240 1250 1250 850
6ONOFFON
700 700 700
750 900 1170
900 1170 1240 1240 1300 1300 900
8ONOFFOFF
800 800 800
875 1000 1170
1000 1170 1240 1240 1500 1500 1000
10 OFF ON ON
850 875 875
950 1170 1170
1170 1170 1240 1240 1550 1550 1170
15 OFF ON OFF
875 875 1050
950 1345 1345
1345 1345 1520 1520 1720 1780 1345
19* OFF OFF ON 1345 1345
1345 1345 1345
20 OFF OFF ON
1520 1520 1850
21 OFF OFF OFF
25* OFF OFF OFF 1850