Specifications

6 www.goodmanmfg.com SS-GAVPTC
SS-GAVPTC www.goodmanmfg.com 7
Electric Heat Airflow & Dipswitch Settings
HTR kW 9 10 11
AVPTC
49C14
AVPTC
49D14 ƚƚ
AVPTC
59C14
AVPT
C59D14
AVPTC
61D14 ƚƚƚ
3 ON ON ON
--- --- --- --- ---
5 ON ON OFF 1170 1250 1170 1240 1250
6 ON OFF ON 1170 1300 1170 1240 1300
8 ON OFF OFF 1170 1500 1170 1240 1500
10 OFF ON ON 1170 1550 1170 1240 1550
15 OFF ON OFF 1345 1720 1345 1520 1780
19* OFF OFF ON 1345 --- 1345 --- ---
20 --- --- --- 1520 1850
21 or 25* OFF OFF OFF --- --- --- --- 1850
Note:Airowdatashownappliestotheelectricheatonlyinei-
therlegacymodeorcommunicangmodeoperaon
--- indicates Not Rated
* Withinthermostatusermenu,CTK0*communicangthermostatwilldisplay20kWforOFF-OFF-ON
dipswitchselecon,
21kWforOFF-OFF-OFFdipswitchselecon.
† Formatchupwitha2tonoutdoorunit:Heaterkitapplicaonshallnotexceed10kW.
Airowfor5kWupto10kWheaterkitsshallbesetto850cfmspeedtapofON-
ON-ON.
†† Formatchupwitha3tonoutdoorunit:Heaterkitapplicaonshallnotexceed15kW.
Airowfor5kWupto15kWheaterkitsshallbesetto1300cfmspeed
tapofON-OFF-ON.
†††Formatchupwitha3.5tonoutdoorunit:Heaterkitapplicaonshallnotexceed20kW.
Airowfor5kWupto20kWheaterkitsshallbesetto1500cfmspeed
tapofON-OFF-OFF
** 3kWheaterkitisnotapplicableforthisindoorapplicaon.
HTR kW 9 10 11
AVPTC
25B14
AVPTC
29B14
AVPTC
31C14
AVPTC
33C14
AVPTC
35B14
AVPTC
37B14
AVPTC
37C14
AVPTC
37D14
AVPTC
39C14
3 ON ON ON 550 550 600 600 550 550 --- --- ---
5 ON ON OFF 650 650 850 700 660 650 850 1240 850
6 ON OFF ON 700 700 900 750 700 700 900 1240 900
8 ON OFF OFF 800 800 1000 875 800 800 1000 1240 1000
10 OFF ON ON 850 875 1170 950 875 875 1170 1240 1170
15 OFF ON OFF 875 875 1345 950 875 1050 1345 1520 1345
19* OFF OFF ON --- --- 1345 --- --- --- 1345 --- 1345
20 --- --- --- --- --- --- --- 1520 ---
21 or 25* OFF OFF OFF --- --- --- --- --- --- --- --- ---
Note:Airowdatashownappliestotheelectricheatonlyineitherlegacymodeorcommunicangmodeoperaon
--- indicates Not Rated
* Withinthermostatusermenu,CTK0*communicangthermostatwilldisplay20kWforOFF-OFF-ONdipswitchselec-
on,
21kWforOFF-OFF-OFFdipswitchselecon.
† Formatchupwitha2tonoutdoorunit:Heaterkitapplicaonshallnotexceed10kW.
Airowfor5kWupto10kWheaterkitsshallbesetto850cfmspeedtapofON-
ON-ON.
†† Formatchupwitha3tonoutdoorunit:Heaterkitapplicaonshallnotexceed15kW.
Airowfor5kWupto15kWheaterkitsshallbesetto1300cfmspeed
tapofON-OFF-ON.
†††Formatchupwitha3.5tonoutdoorunit:Heaterkitapplicaonshallnotexceed20kW.
Airowfor5kWupto20kWheaterkitsshallbesetto1500cfmspeed
tapofON-OFF-OFF
** 3kWheaterkitisnotapplicableforthisindoorapplicaon.