AVPT Spec Sheet
2 www.goodmanmfg.com SS-GAVPTC
SS-GAVPTC www.goodmanmfg.com 3
Product Specifications
AVPTC
25B14A*
AVPTC
29B14A*
AVPTC
31C14A*
AVPTC
33C14*
AVPTC
35B14A*
AVPTC
37B14A*
AVPTC
37C14A*
AVPTC
37D14A*
Nominal Ratings
Cooling (BTU/h) 24,000 30,000 30,000 24,000 28,000 36,000 36,000 36,000
CFM (High range) 1085/650 1085/610 1315/870 1090/685 1020/685 1085/610 1315/870 1375/865
Blower
Diameter 9½" 9½" 10⅝" 10⅝" 9½" 9½" 10⅝" 10⅝"
Width 6" 6" 8" 8" 6" 6" 8" 10⅝"
CoilDrainConneconFPT ¾" ¾" ¾" ¾" ¾" ¾" ¾" ¾"
Service Valve
Liquid ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon ¾" ⅞" ⅞" ⅞" ¾" ⅞" ⅞" ⅞"
Electrical Data
Voltage 208/240 208/240 208/240 208/240 208/240 208/240 208/240 208/240
Min Circuit Ampacity 4.9/4.9 6.5/6.5 6.5/6.5 4.9/4.9 4.9/4.9 6.5/6.5 6.5/6.5 6.5/6.5
Max.OvercurrentDevice(amps) 15/15 15/15 15/15 15/15 15/15 15/15 15/15 15/15
Minimum VAC 197 197 197 197 197 197 197 197
Maximum VAC 253 253 253 253 253 253 253 253
Blower Motor
FLA 3.9 5.2 5.2 3.9 3.9 5.2 5.2 5.2
HP ½ ¾ ¾ ½ ½ ¾ ¾ ¾
Ship Weight (lbs) 116 129 144 118 116 129 144 155
Note:MinimumCircuitAmpacity(MCA)andMaximumOvercurrentProtecon(MOP)forblowerwithoutsupplementalheatinstalled.
Refertounitnameplateand/orHeatKitDataforspecicaonwithapprovedaccessoryheatersinstalled
AVPTC
39C14*
AVPTC
49C14*
AVPTC
49D14A*
AVPTC
59C14A*
AVPTC
59D14A*
AVPTC
61D14A*
Nominal Ratings
Cooling (BTU/h) 36,000 48,000 42,000 48,000 48,000 60,000
CFM (High range) 1315/965
1420/1040 1530/1195 1595/875 1990/1445 2025/1630
Blower
Diameter 10⅝" 10⅝" 10⅝" 10⅝" 11¹⁵⁄₁₆" 11¹⁵⁄₁₆"
Width 8" 8" 10⅝" 8" 10⅝" 10⅝"
CoilDrainConneconFPT ¾"
¾" ¾" ¾" ¾" ¾"
Service Valve
Liquid ⅜" ⅜" ⅜" ⅜" ⅜" ⅜"
Sucon ⅞"
⅞" ⅞" ⅞" ⅞" ⅞"
Electrical Data
Voltage 208/240 208/240 208/240 208/240 208/240 208/240
Min Circuit Ampacity 6.5/6.5 6.5/6.5 6.5/6.5 8.6/8.6 8.6/8.6 8.6/8.6
Max.OvercurrentDevice(amps) 15/15 15/15 15/15 15/15 15/15 15/15
Minimum VAC 197 197 197 197 197 197
Maximum VAC 253
253 253 253 253 253
Blower Motor
FLA 5.2 5.2 5.2 6.9 6.9 6.9
HP ¾
¾ ¾ 1 1 1
Ship Weight (lbs) 118 125 167 144 155 167
Note:MinimumCircuitAmpacity(MCA)andMaximumOvercurrentProtec-
on(MOP)forblowerwithoutsupplementalheatinstalled.
Refertounitnameplateand/orHeatKitDataforspecicaonwithapprovedaccessoryheatersinstalled