DSZC16 Installation Manual
13
AIR C ONDITIONER/HEAT P UMP A DVANCED F EATURES M ENU ( CONT’D)
Submenu Item Indication (for Display Only; not User Modifiable)
Mode (MODE) Displays the current air conditioner operating mode
CFM (CFM) Displays the airflow for the current operating mode
STATUS
Submenu Item User Modifiable Options Comments
Heat Airflow Trim
(HT TRM)
-10% to +10% in 2% increments,
default is 0%
Selects the airflow trim amount; applies to
heat pump only.
Heat ON Delay
(HT ON)
5, 10, or 15 seconds, default is 5
seconds
Selects the indoor blower heat ON delay;
applies to heat pump only.
Heat OFF Delay
(HT OFF)
30, 50, 70, or 90 seconds, default
is 30 seconds
Selects the indoor blower heat OFF delay;
applies to heat pump only.
Defrost Interval
(DEFROST)
30, 60, 90, or 120 minutes,
default is 30 minutes.
Selects the time interval between defrosts;
applies to heat pump only.
Compressor Delay
(CMP DLY)
0, 5, 15, or 30 seconds, default is
30 seconds
Selects the compressor off time after a
reversing valve shift; applies to heat pump
only.
HEAT SET-UP
THERMOSTAT M ENU
If this heat pump is installed with a CT compatible furnace, the system is recognized as a dual fuel system. The balance point
temperature should be set via the thermostat. See thermostat instruction manual for details on how to set the balance point.
NETWORK TROUBLESHOOTING
Verify that the bus TERM dipswitches are in the ON position.
The ComfortNet™ system is a fully communicating system which operates over a communicating
network. Occasionally the need to troubleshoot the network may arise. The integrated control
module has some on-board tools that may be used to troubleshoot the network. These tools are: red
communications LED, green receive (Rx) LED, and learn button.
• Red communications LED - Indicates the status of the network. The table below indicates the
LED status and the corresponding potential problem.
• Green receive LED - Indicates network traffic. The table below indicates the LED status and the corresponding
potential problem.
• LEARN button - Used to reset the network. Depress the button for approximately 2 seconds to reset the network.
SYSTEM TROUBLESHOOTING
NOTE: Refer to the instructions accompanying the CT compatible indoor air handler/furnace/modular blower unit for troubleshooting
information regarding indoor unit diagnostics..
Refer to the Troubleshooting Chart at the end of this manual for a listing of possible air conditioner and heat pump error codes,
possible causes and corrective actions.
1
2
OFF ON
TERM
TERM