LED LED Status Indication Possible Causes Corrective Action(s) Notes & Cautions
Off Normal condition • None None None
Depress once quickly for a
power-up reset
Depress and hold for 2
seconds for an out-of-box
reset
Control power up
Learn button depressed
No power No power to furnace Check fuses and circuit
breakers; replace/reset
Communications error Open fuse Replace blown fuse
Communications error • Check for shorts in low
voltage wiring in
heat pump/system
Reset network by
depressing learn button
Check data 1/ data 2
voltages
Broken/ disconnected data
wire(s)
• Check communications
wiring (data 1/ data 2
wires)
Turn power OFF prior to
repair
Heat pump is installed as a
legacy/ traditional system
Check wire connections at
terminal block
• Verify wires at terminal
blocks are securely twisted
together prior to inserting
into terminal block
Verify heat pump
installation type (legacy/
traditional or
communicating)
Check data 1/ data 2
voltages
Rapid Flashing Normal network traffic Control is “talking” on
network as expected
None None
Data 1 and data 2 wires reversed
at heat pump, thermostat, or
CT compatible indoor unit
• Check communications
wiring (data 1/ data 2
wires)
Turn power OFF prior to
repair
Short between data 1 and
data 2 wires
Check wire connections at
terminal block
• Verify wires at terminal
blocks are securely twisted
together prior to inserting
into terminal block
Short between data 1 or
data 2 wires and R
(24VAC) or C (24VAC
common)
Check data 1/ data 2
voltages
None
Green Receive LED
Off Turn power OFF prior to
repair
1 Steady Flash No network found
On Solid • Data 1/ Data 2 miss-wire
Red Communications
LED
Depress Learn Button
2 Flashes Out-of-box reset None
1 Flash Communications Failure Communications Failure