Installation Instructions

The Furnace Twinning Kit (FTK) provides the means for two gas furnaces
containing an Integrated Ignition control to operate at the same time from a
single thermostat. The two furnaces to be “twinned” must be
exactly the
same model with their circulating air blowers set to deliver the same air flow
at the same time. The furnaces may deliver different CFMs in the cooling
mode, if appropriate. THIS KIT CANNOT BE USED TO CONTROL MORE
THAN TWO (2) FURNACES. When properly installed, these furnaces will
achieve the operational and performance specifications described in the in-
stallation instructions. For items not covered in this manual, follow the instal-
lation instructions shipped with the furnaces.
This Twinning Kit Installation Instruction is divided into five sections. Section
I deals with furnace opening sizes, recommended filter sizes and maximum
CFM per furnace. Section II details the installation of the twinning kit. Sec-
tion III details the sequence of operation. Section IV provides checks and
possible repair procedures. Section V provides a point-to-point wiring dia-
gram.
SECTION 1 GENERAL INFORMATION
It is very important to properly size ductwork and to supply appropriate filters
for your furnaces. There are four possible ductwork configurations for twinning
your furnaces:
Bottom Return
Side Return - One Return per Furnace
Two Side Returns
Top Return
IMPORTANT NOTE: Back return duct installations to furnaces are NOT per-
mitted. Back return installations constrict airflow which leads to poor perfor-
mance and equipment damage. Back return installations are considered im-
proper installation and will void warranty coverage.
GENERAL NOTES
Maximum CFMs are limited by a maximum filter velocity of 600 feet per
minute, or by circulator high speed at 0.5 inches External Static Pres-
sure (ESP) (whichever CFM is lower). THIS REQUIRES A HIGH VE-
LOCITY FILTER. THROWAWAY FILTERS MUST NOT BE USED. If us-
ing anything other than a permanent high velocity filter, consult filter
manufacturer recommendations for maximum allowable velocity.
Actual CFM at the job should be established by carefully setting the
furnace input and measuring the temperature rise. The ESP/CFM Tables
in the furnace specification sheets and installation manuals are based
on side return(s) for a single furnace. For twinned installations - espe-
cially those with bottom return - the relationship between ESP and CFM
may be different. The most accurate way to estimate airflow on twinned
installations is to use temperature rise:
CFM =
BTUH Input
1.085 x (Supply Air Temperature - Return Air Temperature)
Cooling CFM should be 350 to 450 CFM per nominal ton of cooling
capacity. Heating CFM must produce a temperature rise within the
range(s) specified on the furnace nameplate.
Bottom Return
In most cases, bottom return air to both upflow furnaces will be more
practical. When bottom return air is used, the furnaces should be set as
close together (0 to 3 inches) as is practical. This separation distance is
variable, depending upon the needs of the particular job.
See furnace specification sheet for furnace opening sizes, recommended
filter sizes, and maximum CFM per furnace.
Side Return (One Return per Furnace)
This is applicable only for the upflow models with less than five tons of airflow.
PREFERRED M ETHOD
Place the furnaces close together and install a return air drop to the outside of
each furnace (Figure 1).
Figure 1 - [Preferred Method] Single-Side Return Per Furnace Side
Cutouts are 14" x 23" (All Furnaces)
ALTERNATE M ETHOD
The alternate method is used when the installer is forced to use one return for
two furnaces (Figure 2). The maximum required spacing between the fur-
naces is 30 inches apart (approximately 28 x 24 return trunk duct).
Figure 2 - [Alternate Method] Single-Side Return per Furnace
Side Cutouts are 14" x 23" Furnaces are 30" Apart
NOTE: NOT FOR USE WITH TWO-STAGE VARIABLE SPEED FURNACES OR WITH 2-STAGE CONDENSING UNITS.
NOT FOR USE WITH FURNACES UTILIZING IGNITION CONTROL 50A55-289 (PCBBF112(S).
IO-656B
September 2013
FURNACE TWINNING KIT
INSTALLATION INSTRUCTIONS
WARNING
EACH FURNACE MUST BE EQUIPPED WITH ITS OWN
GAS SHUTOFF VALVE A S REQUIRED BY THE NATIONAL
FUEL GAS CODE.

Summary of content (4 pages)