Installation Instructions for *M9S96/*C9S96 & *M9S92 Single-Stage Gas Furnace (Type FSP CATEGORY IV Direct or Non Direct Vent Air Furnace) (Type FSP CATÉGORIE IV Direct ou four á air soufflé non direct) *NOTE: Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual. These furnaces comply with requirements embodied in the American National Standard / National Standard of Canada ANSI Z21.47·CSA-2.3 Gas Fired Central Furnaces.
TABLE OF CONTENTS Safety Considerations.................................................4 Shipping Inspection......................................................6 Electrostatic Discharge (ESD) Precautions..............6 To The Installer...........................................................6 Product Application......................................................7 Location Requirements & Considerations................8 Clearances and Accessibility...................................
TABLE OF CONTENTS Safety Circuit Description........................................39 Integrated Control Module.....................................39 Primary Limit...............................................................39 Auxiliary Limit.............................................................39 Rollout Limit..............................................................39 Pressure Switches.....................................................39 Flame Sensor.......................................
SAFETY CONSIDERATIONS CAUTION Adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or operating the furnace. To ensure proper installation and operation, thoroughly read this manual for specifics pertaining to the installation and application of this product. FROZEN AND BURST WATER PIPE HAZARD FAILURE TO PROTECT AGAINST THE RISK OF FREEZING MAY RESULT IN PROPERTY DAMAGE.
Drain trap must be primed at time of installation. Trap is internally partitioned; add water to both inlet ports until water appears at both sides of the outlet opening. Failure to prime trap at time of installation may have a negative effect on combustion quality and pressure switch action. WARNING FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame.
AVERTISSEMENT ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS RISQUE D'INCENDIE OU D'EXPLOSION Si les consignes de sécurité ne sont pas suivies à la lettre, cela peut entraîner la mort, de graves blessures ou des dommages matériels. WARNING SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY. Ne jamais vérifier la présence de fuites de gaz au moyen d'une flamme nue.
PRODUCT APPLICATION • A return air temperature range between 60ºF (16ºC) and 80ºF (27ºC) is maintained. • MERV 11 pleated minimum 4.0” thick (Example P/N • AMP-11-2025-45) air filter(s) are installed in the system and inspected daily and replaced as needed during construction and upon completion of construction. • The input rate and temperature rise are set per the furnace rating plate. • The furnace must be installed as a two pipe system, using 100% outside air for combustion during construction.
A copy of the CAN/CSA B149.1-15 Installation Codes can also be obtained from: CSA International 178 Rexdale Boulevard Etobicoke, Ontario, Canada M9W 1R3 • • LOCATION REQUIREMENTS & CONSIDERATIONS Follow the instructions listed below and the guidelines provided in the Combustion and Ventilation Air Requirements section when selecting a furnace location.
• • • • CLEARANCES AND ACCESSIBILITY Do not connect this furnace to a chimney flue that serves a separate appliance designed to burn solid fuel. On Counterflow Installations, the air conditioning coil must be downstream on the supply (positive) side of the furnace heat exchanger. Counterflow Installation over a noncombustible floor. Before setting the furnace over the plenum opening, ensure the surface around the opening is smooth and level.
WARNING AVERTISSEMENT CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. RISQUE D'INTOXICATION AU MONOXYDE DE CARBONE Si les étapes décrites ci-dessous ne sont pas suivies pour chacun des appareils raccordés au système de ventilation au moment de sa mise en marche, cela peut entraîner une intoxication au monoxyde de carbone ou la mort.
INSTALLATION POSITIONS Thermostat Location This furnace may be installed in an upright position or horizontal on either the left or right side panel. Do not install this furnace on its back. For upright upflow furnaces, return air ductwork may be attached to the side panel(s) and/or basepan. For horizontal upflow furnaces, return air ductwork must be attached to the basepan.
3. Locate 24” x 1/4” tube in bag assembly. 4. Install one end on front cover pressure switch. 5. Route tube to lower port on collector box cover and cut off excess tubing. Drain Trap and Lines In horizontal applications the condensate drain trap is secured to the furnace side panel, suspending it below the furnace. A minimum clearance of 5.5” below the furnace must be provided for the drain trap.
VENT PIPE & COMBUSTION AIR PIPE MATERIALS – INSTALLATIONS IN CANADA All installations in Canada must conform to the requirements of CAN/CSA B149.1-15 code. All vent components, including primer and cement, must be listed to ULC S636. The certified pipe and fittings should be clearly marked with the ULC standard “S636”. The primer and cement used must be of the same manufacturer as the vent system. For Royal Pipe System 636; use GVS65 Primer (Purple) and GVS-65 PVC Solvent Cement.
PIPE INSTALLATION ACCEPTABLE This furnace is manufactured with 2” CPVC vent & intake couplings. Use transition cement to connect PVC or ABS pipe to these fittings. For furnaces requiring installation of 3” pipe, the transition from 2” to 3” should be done as close to the furnace as possible, and only when the piping is sloped enough to prevent condensation from collecting. TRANSITION NO LESS THAN 45 DEGREES TO HORIZONTAL PLANE TO AVOID CREATING A WATER TRAP IN VENT PIPING.
MODEL *M9S960403AN *M9S960603BN *M9S960803BN *M9S960804CN *M9S960805CN *M9S961005CN *M9S961205DN *C9S960403BN *C9S960603BN *C9S960804CN *C9S961005CN *C9S961205DN PIPE SIZE 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 3. Tee used in the vent/flue termination must be included when determining the number of elbows in the piping system. 4. 2 ½” or 3” diameter pipe can be used in place of 2” diameter pipe. 5. Increased Clearance Configuration using (2) 45 deg.
Combustion Air Intake Options Exhaust The RF000142 coupling (Figure 9) can be secured directly to the furnace intake coupling if condensation/ rain water is a concern. If the RF000142 is used on the combustion air inlet, it must be installed with the arrow pointing up. It should be noted, the combustion air will actually be moving in a direction opposite of the arrow on the RF000142 coupling. It must have a field supplied, trapped drain tube free-draining to a proper condensate disposal location.
WARNING THE RUBBER ELBOW IS NOT DESIGNED TO SUPPORT A LOAD. WHEN THE RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE CABINET, EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT FIELDSUPPLIED VENT/FLUE PIPING, AS DAMAGE CAN RESULT IN LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES, INCLUDING CARBON MONOXIDE CAUTION Figure 11 BE SURE NOT TO DAMAGE INTERNAL WIRING OR OTHER COMPONENTS WHEN REINSTALLING COUPLING AND SCREWS. 1.
The vent termination of a direct vent application must terminate at least 12” from any opening through which flue gases may enter a building (door, window, or gravity air inlet).
Vent & Combustion Air Intake Measurements for Standard Horizontal Terminations (Dual Pipe) 10”- 24” Center to center = 10” min / 24” max. Vertical separation: 0” - 24” Vent termination from wall = 8” min / 12” max. Combustion air intake from wall = 6” max. Vent and intake clearance to ground or anticipated snow level = 12” min. 6” MAX 4” MIN 90º OR 45° ELBOW 3”MIN 24”MAX 12” MIN SEPARATION 12" MIN.
Side Wall Vent Kit This kit is to be used with 2” or 3” direct vent systems. The vent kit must terminate outside the structure and may be installed with the intake and exhaust pipes located sideby-side or with one pipe above the other. These kits are NOT intended for use with single pipe (non-direct vent) installations. Refer to the directions furnished with the Side Wall Vent Kit (p/n 0170K00000S or 0170K00001S) for installation specifications.
Field Supplied Drain 4. Install smaller end of hose #3 on 45º elbow and secure with 1” clamp. 5. Refer to Field Supplied Drain section for instructions on field supplied / installed drain on outlet of furnace trap. Drain the furnace and air conditioning coil if applicable, in compliance with code requirements. In horizontal or counterflow installations, a field installed rubber coupling will allow the drain trap to be removed for cleaning. The drain trap must be primed before initial furnace start up.
6. For models *MSS920403AN and *MSS960403AN; locate the hose #2 (factory installed) and cut 1.5 length from the end of the hose. Insert hose #2 from outside the cabinet through the cabinet’s drain hole nearest to the top. Secure it to the barbed fitting in the elbow with a red clamp. 7. (Draining the Collector Box) Install the non-grommet end of hose #11 from outside the cabinet in the bottom drain hole. Install on collector box and secure with a silver clamp. 8.
10. Use two silver clamps and secure the hoses to drain trap. The trap outlet faces the front of the furnace. Secure the trap to the cabinet using two screws removed in step 2 by inserting the two screws through the large set of holes in the top mounting tabs of the trap. Insert flange. Cut 2 ½” long. RF000142 Hose #4 x 3 Hose #5 Figure 28 Drain Exiting Right Side (See Figure 29) Figure 27 1. Removing the gas manifold assembly will provide better access when re-locating the trap.
3. (Draining the Collector Box) From outside the cabinet, insert the non-grommet end hose #7 into the back drain hole and secure to collector box drain port using a silver clamp. 4. (Draining the Vent Elbow) Insert the straight barbed coupling into the vent - drain elbow drip leg and secure with a red clamp. Figure 30 Figure 29 5. From outside the cabinet, insert the non-grommet end of hose #8 into the front cabinet drain hole and secure on the vent - drain elbow barb fitting using a red clamp. 6.
8. The unused vent-drain elbow drip leg port must be plugged to prevent flue gases from escaping. Insert rubber plug removed in step 7 into the 100° elbow. (Inserting a blunt tool such as a 3/16’’ Allen wrench into the center of the rubber plug will stretch the plug and allow complete insertion) 115 Volt Line Connections Before proceeding with electrical connections, ensure that the supply voltage, frequency, and phase correspond to that specified on the unit rating plate.
NOTE: Wire routing must not to interfere with circulator blower operation, filter removal, or routine maintenance. WARNING TO PREVENT PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, DISCONNECT ELECTRICAL POWER BEFORE INSTALLING OR SERVICING THIS UNIT. 115 VAC EAC 115 VAC HUM WARNING HIGH VOLTAGE ! TO AVOID THE RISK OF INJURY, ELECTRICAL SHOCK OR DEATH, THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE , WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC C ODE.
Junction Box Relocation Thermostat Wiring Diagrams Line voltage connections can be made through either the right or left side panel. The furnace is shipped configured for a left side electrical connection. To make electrical connections through the opposite side of the furnace, the junction box must be relocated to the left side prior to making electrical connections. To relocate the junction box, perform the following steps. 1. Remove the burner compartment door. 2.
Twinning Inlet gas supply pressures must be maintained within the ranges specified in the following table. The supply pressure must be constant and available with all other household gas fired appliances operating. The minimum gas supply pressure must be maintained to prevent unreliable ignition. The maximum must not be exceeded to prevent unit overfiring. Two furnaces of the same model may be twinned.
For furnaces being converted to LP gas, it is strongly recommended that a LPLP03 kit also be installed. The use of this kit will prevent the furnace from firing when the LP gas supply pressure is too low to support proper combustion. • • All conversions must be performed by a qualified installer, or service agency. Gas Valve • This unit is equipped with a 24 volt gas valve controlled during furnace operation by the integrated control module. As shipped, the valve is configured for natural gas.
The gas piping may enter the left or right side of the furnace cabinet. The installer must supply rigid pipe long enough to reach the outside of the cabinet to seal the grommet cabinet penetration. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes. 1/2” NPT pipe and fittings are required. For models with an “L” shaped manifold, a 4 1/2” long nipple is required. For models with a hook shaped manifold, a 2” long nipple is required.
Gas Piping Checks Before placing unit in operation, leak test the unit and gas connections. 5 to 15 PSIG (20 PSIG Max.) First Stage Regulator Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other approved testing methods. NOTE: Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause subsequent overfiring, resulting in heat exchanger failure.
NOTE: Both readings may be taken simultaneously and read directly on the manometer if so desired. If an air conditioner coil or Electronic Air Cleaner is used in conjunction with the furnace, the readings must also include theses components, as shown in the following drawing. Install the duct system in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
Filter Sizing Charts CUT USING TIN SNIPS Model PRESS OUT BY HAND *M9S960403AN CUT FOUR CORNERS AFTER REMOVING SHEET METAL SCRIBE LINES OUTLINING DUCT FLANGES Duct Flange Cut Outs Figure 43 When the furnace is used in connection with a cooling unit, the furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element.
Clean Comfort™ brand MERV 11 air cleaners have 5¼” media filters and are available in the following configurations. Consult your distributor for information on our complete line of IAQ Clean Comfort™ products. Depending on the installation and/or customer preference, differing filter arrangements can be applied. Filters can be installed in the central return register or a side panel external filter rack kit (upflows).
STARTUP PROCEDURE & ADJUSTMENT 8. Replace the burner compartment door. 9. Open the manual gas shutoff valve external to the furnace. 10. Turn on the electrical power to the furnace. 11. Adjust the thermostat to a setting above room temperature. 12. After the burners are lit, set the thermostat to desired temperature. Furnace must have a 115 VAC power supply properly connected and grounded. Proper polarity must be maintained for correct operation.
THERMOSTAT CALL 2nd Stage Cooling Mode Sequence: On a call for 2nd stage cooling, the Y2 or Y2 and G thermostat contacts close signaling the furnace control board with 24 VAC on Y2 or Y2 and G terminals. • The 7-Segment will display the cool mode: 2 A C • The compressor and condenser fan are energized. • The circulator fan is energized at cool speed after a cool on delay. The electronic air cleaner will also be energized.
Furnace Shutdown Gas Natural 1. Set the thermostat to the lowest setting. The integrated control will close the gas valve and extinguish flame. Following a 15 second delay, the induced draft blower will be de-energized. After the blower off delay time expires, the blower deenergizes. 2. Remove the burner compartment door and move the furnace gas valve manual control to the OFF position. 3. Close the manual gas shutoff valve external to the furnace. 4. Replace the burner compartment door.
8. Remove regulator cover screw from the outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure. Replace regulator cover screw. 9. Turn off all electrical power and gas supply to the system. 10. Remove the manometer hose from the hose barb fitting or outlet pressure tap. 11. Replace outlet pressure tap: White-Rodgers 36J22 valve: Turn outlet pressure test screw in to seal pressure port (clockwise, 7 in-lb minimum). 12.
OPERATIONAL CHECKS Pressure Switches The pressure switches are normally-open (closed during operation) negative air pressure-activated switches. They monitor the airflow (combustion air and flue products) through the heat exchanger via pressure taps located on the induced draft blower and the coil front cover. These switches guard against insufficient airflow (combustion air and flue products) through the heat exchanger and/or blocked condensate drain conditions.
Horizontal Unit Filter Removal Flame Sensor (Qualified Servicer Only) Filters in horizontal installations are located in the central return register or the ductwork near the furnace. Under some conditions, the fuel or air supply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator causing a drop in the flame sense signal. If the flame sense signal drops too low the furnace will not sense flame and will lock out.
1 Stage Status Codes Menu Description Active Alaram menu Last 6 Faults LED Display Main Menu Option Menu xx xx Code Release Number CR Number Reset to Factory Default yes, no Blower Speed for Continous Fan Mode xx Blower Speed for 1st Stage Compressor Mode xx Blower Speed for 2nd Stage Compressor Mode xx Cool On Delay Blower Speed for Gas Heat Mode xx Automatic Heat Staging - For Two Stage Control ( xx: Blower Speed Number F01, F02..
1 Stage Status Codes Status Menu Main Menu Mode Idle Continous Fan Compressor Cooling, Low Stage Compressor Cooling, High Stage Gas heat - Single Stage Control OEM test Mode 42
1 Stage Troubleshooting Codes TROUBLESHOOTING CHART Symptom Normal operation LED Status Fault Description Corrective Actions Normal operation None Locate and correct gas interruption Replace or realign igniter Furnace fails to operate Furnace lockout due to an excessive number of ignition “retries” (3 total) Failure to establish flame Loss of flame after establishment Check flame sense signal, clean sensor if coated or oxidized Check flue piping for blockage, proper length, elbows, and te
1 Stage Troubleshooting Codes TROUBLESHOOTING CHART Symptom LED Status Fault Description Corrective Actions Flame sense micro amp signal is minimal Flame sensor is coated/oxidized Normal furnace operation Flame sensor incorrectly positioned in burner fame Lazy burner flame due to improper gas pressure or combustion air Problem with igniter circuit Furnace fails to operate Furnace fails to operate Furnace fails to operate Furnace fails to operate Furnace fails to operate.
Airflow Tables - GC9S96 LOW STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *C9S960403B* Y/Y1 *C9S960603B* Y/Y1 *C9S960804C* Y/Y1 *C9S961005C* Y/Y1 *C9S961205D* Y/Y1 EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) 0.3 0.4 0.5 0.6 TAP # 0.1 0.
Airflow Tables - GC9S96 HIGH STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *C9S960403B* Y2 *C9S960603B* Y2 *C9S960804C* Y2 *C9S961005C* Y2 *C9S961205D* Y2 TAP # F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 0.
Airflow Tables - GC9S96 CIRCULATION AIFLOW MODEL THERMOSTAT CALL *C9S960403B* G *C9S960603B* G *C9S960804C* G *C9S961005C* G *C9S961205D* G TAP # F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 0.
Airflow Tables - GC9S96 HEATING AIFLOW MODEL THERMOSTAT CALL *C9S960403B* W/W1 *C9S960603B* W/W1 *C9S960804C* W/W1 *C9S961005C* W/W1 *C9S961205D* W/W1 TAP # F01^^ F02^ F03 F04 F01^^ F02^ F03 F04 F01^^ F02^ F03 F04 F01^^ F02^ F03^^ F04 F01^^ F02^ F03 F04 CFM 632 727 878 948 771 1197 1309 1138 873 1442 1643 1600 1176 1773 1709 1651 1187 1973 1918 1835 0.
Airflow Tables - GM9S92 LOW STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *M9S920403A* Y/Y1 *M9S920603B* Y/Y1 *M9S920803B* Y/Y1 *M9S920804C* Y/Y1 *M9S920805C* Y/Y1 TAP # F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 0.
Airflow Tables - GM9S92 LOW STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *M9S921004C* Y/Y1 *M9S921005C* Y/Y1 *M9S921205D* Y/Y1 TAP # F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 0.1 CFM 809 1754 1648 1558 1303 1406 1445 1778 1824 906 1871 1831 1653 1496 1640 1955 2086 2222 1056 2096 2023 1946 1231 1503 1704 1831 2222 EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) 0.2 0.3 0.4 0.5 0.6 0.
Airflow Tables - GM9S92 HIGH STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *M9S920403A* Y2 *M9S920603B* Y2 *M9S920803B* Y2 *M9S920804C* Y2 *M9S920805C* Y2 TAP # F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 0.
Airflow Tables - GM9S92 HIGH STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *M9S921004C* Y2 *M9S921005C* Y2 *M9S921205D* Y2 TAP # 0.1 CFM 809 1754 1648 1558 1303 1406 1445 1778 1824 906 1871 1831 1653 1496 1640 1955 2086 2222 1056 2096 2023 1946 1231 1503 1704 1831 2222 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) 0.2 0.3 0.4 0.5 0.6 0.
Airflow Tables - GM9S92 CIRCULATION AIRFLOW MODEL THERMOSTAT CALL *M9S920403A* G *M9S920603B* G *M9S920803B* G *M9S920804C* G *M9S920805C* G TAP # F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 0.
Airflow Tables - GM9S92 CIRCULATION AIRFLOW MODEL THERMOSTAT CALL *M9S921004C* G *M9S921005C* G *M9S921205D* G TAP # F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 0.1 CFM 809 1754 1648 1558 1303 1406 1445 1778 1824 906 1871 1831 1653 1496 1640 1955 2086 2222 1056 2096 2023 1946 1231 1503 1704 1831 2222 EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) 0.2 0.3 0.4 0.5 0.6 0.
Airflow Tables - GM9S92 HEATING AIFLOW MODEL THERMOSTAT CALL *M9S920403A* W/W1 *M9S920603B* W/W1 *M9S920803B* W/W1 *M9S920804C* W/W1 *M9S920805C* W/W1 *M9S921004C* W/W1 *M9S921005C* W/W1 *M9S921205D* W/W1 0.
Airflow Tables - GM9S96 LOW STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *M9S960403A* Y/Y1 *M9S960603B* Y/Y1 *M9S960803B* Y/Y1 *M9S960804C* Y/Y1 TAP # F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 0.
Airflow Tables - GM9S96 LOW STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *M9S960805C* Y/Y1 *M9S961005C* Y/Y1 *M9S961205D* Y/Y1 TAP # F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 F01 F02 F03 F04^ F05 F06 F07 F08 F09 0.1 CFM 1029 1814 1893 1738 1193 1421 1582 1962 2068 1008 2026 1921 1804 1475 1626 1693 1775 2161 1118 2143 2025 1906 1220 1684 1766 1863 2454 EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) 0.6 0.7 0.5 0.2 0.3 0.
Airflow Tables - GM9S96 HIGH STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *M9S960403A* Y2 *M9S960603B* Y2 *M9S960803B* Y2 *M9S960804C* Y2 TAP # F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 0.
Airflow Tables - GM9S96 HIGH STAGE COOLING AIFLOW MODEL THERMOSTAT CALL *M9S960805C* Y2 *M9S961005C* Y2 *M9S961205D* Y2 TAP # 0.1 CFM 1029 1814 1893 1738 1193 1421 1582 1962 2068 1008 2026 1921 1804 1475 1626 1693 1775 2161 1118 2143 2025 1906 1220 1684 1766 1863 2454 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 F01 F02 F03 F04 F05^ F06 F07 F08 F09 EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) 0.6 0.7 0.5 0.2 0.3 0.
Airflow Tables - GM9S96 CIRCULATION AIRFLOW MODEL THERMOSTAT CALL *M9S960403A* G *M9S960603B* G *M9S960803B* G *M9S960804C* G TAP # F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 0.
Airflow Tables - GM9S96 CIRCULATION AIRFLOW MODEL THERMOSTAT CALL *M9S960805C* G *M9S961005C* G *M9S961205D* G TAP # F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 F01 F02 F03 F04 F05 F06 F07 F08 F09 0.1 CFM 1029 1814 1893 1738 1193 1421 1582 1962 2068 1008 2026 1921 1804 1475 1626 1693 1775 2161 1118 2143 2025 1906 1220 1684 1766 1863 2454 EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN) 0.2 0.3 0.4 0.5 0.6 0.
Airflow Tables - GM9S96 HEATING AIFLOW MODEL THERMOSTAT CALL *M9S960403A* W/W1 *M9S960603B* W/W1 *M9S960803B* W/W1 *M9S960804C* W/W1 *M9S960805C* W/W1 *M9S961005C* W/W1 *M9S961205D* W/W1 TAP # F01^^ F02^ F03 F04 F01^^ F02^ F03 F04 F01^^ F02^ F03 F04 F01^^ F02^ F03 F04 F01^^ F02^ F03 F04 F01^^ F02^ F03 F04 F01^^ F02^ F03 F04^^ 0.1 CFM 705 1079 915 887 758 1218 1164 1121 715 1415 1388 1290 1019 1791 1625 1537 1029 1814 1893 1738 1008 2026 1921 1804 1118 2143 2025 1906 0.
Wiring Diagram *M9S92/*M9S96/*C9S96 GN GRD YL GY JUNCTION BOX ID BLOWER PRESSURE SWITCH HOT SURFACE IGNITER L YL DISCONNECT 2 CIRCUIT CONNECTOR RD TO 115VAC/ 1Ø /60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE C GY WH NO FLAME SENSOR SOME UNITS MAY HAVE 1 ROLL OUT SWITCH PU PU PK DISCONNECT JUNCTION BOX RD WH BK YL PK HUM-OUT BK WH IND FS EAC-H LINE-H CIRC-H NEUT2 NEUT1 HUM-N CIRC-N EAC-N XFMR-N LINE-N XFMR-H FLAME SENSOR 115 VAC LINE 24 VAC 2 1 RD YL
SPECIAL INSTRUCTIONS FOR PRODUCTS INSTALLED IN THE STATE OF MASSACHUSETTS For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above VENT/FLUE finished grade in the area of the venting, including but not TEE limited to decks and porches, the following requirements shall be
Start-Up Checklist Furnace Model Number Serial Number ELECTRICAL Line Voltage (Measure L1 to N and N to Ground Voltage) L-N N-G R-C Secondary Voltage (Measure Transformer Output Voltage) Blower Amps BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure Supply Air Static Pressure Total External Static Pressure (Ignoring +/- from the reading above, add total here) TEMPERATURES Return Air Temperature (Dry bulb / Wet bulb) Cooling Supply Air Temperature (Dry bulb / Wet bulb) Heating Supply Air Temperat
THIS PAGE LEFT INTENTIONALLY BLANK.
THIS PAGE LEFT INTENTIONALLY BLANK.
CUSTOMER FEEDBACK We are very interested in all product comments. Please fill out the feedback form on one of the following links: Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us). Amana® Brand Products: (http://www.amana-hac.com/about-us/contact-us). You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page. PRODUCT REGISTRATION Thank you for your recent purchase.