INSTALLATION INSTRUCTIONS FOR *MVM96 & *CVM96 MODULATING GAS FURNACE (Type FSP CATEGORY IV Direct or Non Direct Vent Air Furnace) Installer: Affix all manuals adjacent to the unit. These furnaces comply with requirements embodied in the American National Standard / National Standard of Canada ANSI Z21.47·CSA-2.3 Gas Fired Central Furnaces. RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
TABLE OF CONTENTS UPRIGHT INSTALLATIONS-TRAP ON LEFT SIDE ................................................. 25 HORIZONTAL INSTALLATIONS .................................... 26 Electrical Connections ............................................. 27 WIRING HARNESS ................................................. 28 115 VOLT LINE CONNECTIONS ................................. 28 JUNCTION BOX RELOCATION ................................... 28 24 VOLT THERMOSTAT WIRING ................................
TABLE OF CONTENTS DIP Switches ............................................................ NETWORK TROUBLESHOOTING .................................. SYSTEM TROUBLESHOOTING .................................... FAULT RECALL SEQUENCE ...................................... FAULT CLEAR SEQUENCE: ...................................... Normal Sequence of Operation ............................... POWER UP ......................................................... HEATING MODE .....................................
WARNING WARNING TO PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION , ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE, REFER TO THIS MANUAL . FOR ADDITIONAL ASSISTANCE OR INFORMATION , CONSULT A QUALIFIED INSTALLER , SERVICER AGENCY OR THE GAS SUPPLIER . GOODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES .
• • • • Original or certified copy of the Bill of Lading, or indemnity bond. Original paid freight bill or indemnity in lieu thereof. Original or certified copy of the invoice, showing trade and other discounts or reductions. Copy of the inspection report issued by carrier’s representative at the time damage is reported to carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim.
However, this reduces the benefits of the ComfortNet system as the enhancements will only apply to the furnace. IMPORTANT NOTE TO THE OWNER REGARDING PRODUCT WARRANTY The modulating furnace operation is based off of negative pressure created by the draft inducer. The furnace control board receives commands from the room thermostat. The furnace control board then controls the RPM of the (3 phase) inducer by varying the frequency and voltage to the inducer. This is known as variable frequency drive (VFD).
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 Gas Valve Gas Line Entrance (Alternate) Pressure Switch(es) Gas Manifold Combustion Air Intake Connection Hot Surface Igniter Rollout Limit Burners Flame Sensor Flue Pipe Connection Flue Pipe Primary Limit Gas Line Entrance Flue Pipe Connection (Alternate) Rubber Elbow Variable-Speed Induced Draft Blower Electrical Connection Inlets (Alternate) Coil Front Cover Pressure Tap Coil Front Cover Drain Port Drain Line Penet
B149.1 Installation Codes, local plumbing or waste water codes, and other applicable codes. • A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.
• • • • • • • If the furnace is used in connection with a cooling unit, install the furnace upstream or in parallel with the cooling coil. Premature heat exchanger failure will result if the cooling coil is placed upstream of the furnace. For vertical (upflow or downflow) applications, the minimum cooling coil width shall not be less than furnace width minus 1”.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. COMBUSTION & VENTILATION AIR REQUIREMENTS WARNING TO AVOID PROPERTY DAMAGE , PERSONAL INJURY OR DEATH, 4. Close fireplace dampers. SUFFICIENT FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF FLUE GASES MUST BE SUPPLIED . 5. Turn on clothes dryers and any appliance not connected to the venting system.
9.3.1.4 Where used, a draft hood or a barometric draft regulator shall be installed in the same room or enclosure as the appliance served so as to prevent any difference in pressure between the hood or regulator and the combustion air supply. 9.3.1.5 Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers, and fireplaces shall be considered in determining the adequacy of a space to provide combustion air requirements. 9.3.2 Indoor Combustion Air.
Figure A.9.3.3.1(2) All Combustion Air From Outdoors through Horizontal Ducts. Figure A.9.3.3.1(1)(a) All Combustion Air From Outdoors Inlet Air from Ventilated Crawl Space and Outlet Air to Ventilated Attic. 9.3.3.2* One Permanent Opening Method. One permanent openings, commencing within 12 in. (300 mm) of the top of the enclosure, shall be provided. The appliance shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front of the appliance.
(c) The minimum size of outdoor opening(s) shall be the full size of outdoor opening(s) calculated in accordance with 9.3.3, multiplied by the reduction factor. The minimum dimension of air openings shall not be less than 3 in. (80 mm). 9.3.8.5 Ducts shall not be screened where terminating in an attic space. 9.3.8.6 Horizontal upper combustion air ducts shall not slope downward toward the source of combustion air. 9.3.5 Engineered Installations.
LEVELING Leveling ensures proper condensate drainage from the heat exchanger and induced draft blower. For proper flue pipe drainage, the furnace must be level lengthwise from end to end. The furnace should also be level from back to front or have a slight tilt with the access doors downhill (approximately 3/4 inches) from the back panel. The slight tilt allows the heat exchanger condensate, generated in the recuperator coil, to flow forward to the recuperator coil front cover.
Furnace Mode l LP Kit A/GMVM960603BX LPKMOD060UF A/GMVM960805CX LPKMOD080UF A/GMVM961005DX LPKMOD100UF A/GMVM961155DX LPKMOD115UF A/GCVM960 604CX LPKMOD060CF A/GCVM960 805DX A/GCVM961 005DX LPKMOD080CF LPKMOD100CF It is the responsibility of the installer to follow the manufacturers’ recommendations and to verify that all vent/flue piping and connectors are compatible with furnace flue products.
V X v DIRECT VENT TERMINAL CLEARANCES 1 Canadian Installations U.S. Installations Canadian Installations 2 A= Clearance above grade, veranda, porch, deck or balcony. (See 1.24.6-i(9)b.) 12 in. (30 cm) 12 in. (30 cm) B= Clearance to window or door that may be opened. 6 in. (15 cm) for appliances 10,000 Btuh (3 kW), 12 in. (30 cm) for appliances > 10,000 Btuh (3 kW) and 100,000 Btuh (30 kW), 36 in. (91 cm) for appliances > 100,000 Btuh (30 kW). 6 in.
All 90° elbows must be medium radius (1/4 bend DWV) or long radius (Long sweep 1/4 bend DWV) types conforming to ASTM D3311. A medium radius (1/4 bend DWV) elbow measures 3 1/ 16” minimum from the plane of one opening to the centerline of the other opening for 2” diameter pipe, and 4 9/16” minimum for 3” pipe.
3 REMOVE PIPE 4 REMOVE AND RELOCATE CABINET GROMMET 2 DETACH RUBBER ELBOW FROM ID BLOWER AND VENT/FLUE PIPE 3 REMOVE PIPE 5 EXTERNALLY MOUNT RUBBER ELBOW AND SECURE FLANGE WITH 4 SCREWS REMOVED IN STEP 1 5 INSTALL CABINET GROMMET IN 2 LOCATIONS 7 EXTERNALLY MOUNT RUBBER ELBOW AND SECURE FLANGE WITH 4 SCREWS REMOVED IN STEP 1 2 REMOVE 3 SCREWS 4 DETATCH RUBBER ELBOW FROM ID BLOWER AND VENT/FLUE PIPE 6 SECURE TO ID BLOWER WITH RUBBER COUPLING AND HOSE CLAMPS COUNTERFLOW-HORIZONTAL MODEL ALTERNATE VENT
SPECIAL VENTING REQUIREMENTS FOR INSTALLATIONS IN CANADA densate drain lines, etc. If necessary, clearances may be increased by creating an offset using two 45 degree elbows. This joint can be rotated on the fitting to establish maximum clearance between refrigerant lines, metering devices, and condensate drain lines, etc. This joint is the equivalent of one 90 deg. elbow when considering elbow count. All installations in Canada must conform to the requirements of CAN/CSA B149.1 code.
ALTERNATE FURNACE CONNECTIONS FLANGE If the standard locations are undesirable for a specific installation, alternate side panel locations are available for both combustion air inlet and vent/flue pipe connections on counterflow-horizontal models. On upflow-horizontal models, only an alternate vent location is provided. 3.75" CUT HERE NOTE: Standard and alternate locations can be combined (i.e.
2. Remove the combustion air intake pipe from the furnace and cut the pipe at the basepan coupling. Save the basepan coupling and gasket from the blower deck coupling for use in the alternate location. Discard the remaining pipe. must be counted as an elbow when determining the number of elbows in the piping system.
terminations must be in the same atmospheric pressure zone. Example: Same side of structure, no major obstacles between pipes, etc. the last joist space to penetrate the header, two 45° elbows should be used to reach the header rather than two 90° elbows. NOTE: Terminate both pipes in the same pressure zone (same side of roof, no major obstacles between pipes, etc.).
10”- 24” 90° ELBOWS 6” MAX 4” MIN 3”-24” BETWEEN PIPES AIR INTAKE 90º OR 45° ELBOW SCREEN (OPTIONAL) SCREEN (OPTIONAL) 12" MIN. ABOVE HIGHEST ANTICIPATED SNOW LEVEL 12" MIN. TO GRADE OR HIGHEST ANTICIPATED SNOW LEVEL Combustion Air Intake may also be snorkeled to obtain 12” min ground clearance.
This is necessary to prohibit any interference with the function of the furnace’s drain trap. NOTE: In vertical installations, air conditioning coil condensate may drain into the furnace trap as long as there is a trap between the coil and the furnace trap and the drain pipe is not terminating below the water level of the furnace trap.
RUBBER ELBOW (EXTERNALLY MOUNTED) RIGHT SIDE PANEL RUBBER ELBOW RUBBER ELBOW DRAIN PORT FRONT COVER DRAIN PORT RUBBER ELBOW DRAIN PORT HOSE B SILVER HOSE CLAMP SILVER HOSE CLAMP TUBE 1 TUBE 1 HOSE B GREEN HOSE CLAMPS (3 PLACES) RED HOSE CLAMP HOSE A TUBE(S) 2 SIDE PANEL GROMMET HOLES TUBE(S) 2 RED HOSE FRONT CLAMP COVER DRAIN PORT DRAIN TRAP Upright “Alternate” Connections - Right Side (Upflow Shown, Counterflow Similar) HOSE A GREEN HOSE CLAMPS (3 PLACES) DRAIN TRAP Upright “Standard” Conn
GREEN HOSE CLAMP LEFT SIDE PANEL FRONT COVER DRAIN PORT RUBBER ELBOW RED HOSE CLAMP RUBBER ELBOW DRAIN PORT HOSE A HOSE B SILVER HOSE CLAMP SIDE PANEL DRAIN HOLES FRONT COVER PRESSURE TAP TUBE 1 TUBE(S) 2 GREEN HOSE CLAMP DRAIN TRAP GREEN HOSE CLAMP HOSE A GREEN HOSE CLAMP HOSE B LEFT SIDE PANEL Upright “Standard” Connections - Left Side (Upflow Shown, Counterflow Similar) TUBE(S) 2 FRONT COVER DRAIN PORT RED HOSE CLAMP Cabinet Width (inches) Models (kBTU_Tons) 17 1/2 60_3 60_4 80 5 80
2. Secure drain trap to side panel at the dimples or crosshairs located on either side of the grommet drain holes. 3. Confirm that tubes reach bottom of drain trap and that all hoses maintain a downward slope and are not kinked or binding. 4. Attach PVC drain line to drain trap outlet with either a 90° elbow or coupling.
WIRING HARNESS WARNING The wiring harness is an integral part of this furnace. Wires are color coded for identification purposes. Refer to the wiring diagram for wire routings. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C. Any replacement wiring must be a copper conductor.
THERMOSTAT IMPORTANT NOTE HEAT SET‐UP DIP SWITCH ‐ DIP SWITCH #13 MUST BE SET TO MATCH THERMOSTAT TYPE. TO USE THE CTK01 COMMUNICATING THERMOSTAT, DIP SWITCH #13 MUST BE SET TO ON POSITION . THIS ALSO THE CORRECT SETTING FOR A NON ‐COMMUNICATING 2‐STAGE THERMOSTAT. TO USE CTK02** OR CTK03** MODULATING THERMOSTAT, CHECK TO MAKE SURE DIP SWITCH #13 IS IN THE OFF POSITION (FACTORY POSITION ). THIS IS ALSO THE CORRECT POSITION WHEN USING A NON‐COMMUNICATING SINGLE‐STAGE THERMOSTAT.
LINE VOLTAGE ACCESSORIES (ELECTRONIC AIR CLEANER AND HUMIDIFIER) To use a single-stage thermostat, turn off power to the furnace, move the thermostat selection DIP switch to the OFF position. Turn power back on. Refer to the DIP switch chart in this manual.
call for humidity. The integrated control module electronic air cleaner terminals (EAC) are energized with 115 volts whenever the circulator blower is energized. GAS VALVE This unit is equipped with a 24 volt gas valve which modulates by pneumatic linkage to the combustion air blower. Taps for measuring the gas supply pressure and manifold pressure are provided on the valve. This is a non-convertible, non-adjustable gas valve equipped for natural gas.
external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage. • Gas piping must be supported external to the furnace • • cabinet so that the weight of the gas line does not distort the burner rack, manifold or gas valve. Use black iron or steel pipe and fittings for building piping. Where possible, use new pipe that is properly chamfered, reamed, and free of burrs and chips.
DIRECT/STANDARD INLET PIPING MAN UAL SHUT-OFF VALVE (UPSTREAM FROM GROUND JOINT PIPE UNION ) ALTER NATE UNION LOCATION GROUND JOINT PIPE UNION WARNING DRIP LEG EDGES OF SHEET METAL HOLES MAY BE SHARP. USE GLOVES AS A PRECAUTION WHEN REMOVING HOLE PLUGS . GROMMET IN STAND ARD GAS LINE HOLE GAS VALVE BURNERS When gas piping enters directly to the gas valve through the standard inlet hole, the installer must supply straight pipe with a ground joint union to reach the exterior of the furnace.
PROPANE GAS TANKS AND PIPING Sizing Between First and Second Stage Regulator* Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting. Capacities in 1,000 BTU/hour. WARNING Pipe or Tubing Length Feet IF THE GAS FURNACE IS INSTALLED IN A BASEMENT , AN EXCAVATED AREA OR CONFINED SPACE , IT IS STRONGLY RECOMMENDED TO 10 20 30 40 50 60 80 100 125 150 175 200 CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING WARNING DEVICE IN CASE OF A GAS LEAK.
used for supply and return connections to reduce noise transmission. To prevent the blower from interfering with combustion air or draft when a central return is used, a connecting duct must be installed between the unit and the utility room wall. Never use a room, closet, or alcove as a return air chamber. CHECKING DUCT STATIC Refer to your furnace rating plate for the maximum ESP (external duct static) rating. Total external static refers to everything external to the furnace cabinet.
With a parallel flow arrangement, the dampers or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool position. Input Airflow UPFLOW COOLING AIRFLOW REQUIREMENT (CFM) When the furnace is installed without a cooling coil, it is recommended that a removable access panel be provided in the supply air plenum.
• FILTER ACCESS DOOR R E LT FI FI LT E R • RETURN DUCT After 20 total minutes, the furnace control board increases to 100% at a rate of 1% per second for the remainder of the call for heat. The circulator fan is adjusted to the appropriate CFM, corresponding to the current firing rate. CENTRAL RETURN GRILLE FILTER SUPPORT BRACKET IGNITION (Field Supplied) (80%) 70% 10 MINS. 60% 8 MINS. 50% 2 MINS. MIN.
Call for 2nd-Stage Heat - Thermostat contacts close R to W1 and W2. • After a successful Light Off Sequence and expiration of the Ignition Stabilization Period: • The furnace control board adjusts to the low firing rate of 35%. • After 2 minutes, the furnace control board increases the firing rate to 80%. • Thereafter, the IFC will increase the firing rate by 10%, at a rate of 1% per second, every 10 minutes for the remainder of the call for heat.
4. Remove the burner compartment door. PRESSURE SWITCH CONNECTION NOTE: This furnace is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. ATMOSPHERE PORT FLOW 5. Move the furnace gas valve manual control to the OFF position. 6. Wait five minutes then smell for gas. Be sure to check near the floor as propane is heavier than air. 7. If you smell gas after five minutes, immediately follow the Safety Considerations on page 4 of this manual.
If supply pressure differs from table, make the necessary adjustments to pressure regulator, gas piping size, etc., and/or consult with local gas utility. 5. Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer. Reinstall threaded plug before turning on gas to furnace. 6. Turn OFF any unnecessary gas appliances stated in step 3. routine on the next call for heat The inducer will ramp up and down during the calibration routine.
number of seconds per cubic foot. The measured input must not be greater than the input indicated on the unit rating plate. EXAMPLE: Heating value of natural gas supplied, typically 1,000 BTUH CU FT: (exact heating value may be obtained from your gas provider) 1,000 BTU/ft3 (Obtained from gas supplier) Installation’s seconds per cubic foot: 34 sec/ ft3 Conversion Factor (hours to seconds): 3600 sec/hr Input = (Htg.
may require specific quantity of air, consult installation instructions of those devices for requirements. 3. Knowing the furnace model, locate the high stage cooling air flow table. Look up the cooling air flow determined in step 2 and find the required cooling speed and adjustment setting. Example: A *MVM960603BX furnace installed with a 2.5 ton air conditioning system. The air flow needed is 1000 CFM. Looking at the cooling speed chart for *MVM960603BX, find the air flow closest to 1000 CFM.
In general lower heating speeds will: reduce electrical consumption, lower operating sound levels of the blower, and increase the outlet air temperature delivered to the home. The speeds available allow the blower performance to be optimized for the particular needs of the installation. AIRFLOW CONSIDERATIONS Airflow demands are managed differently in a communicating system than they are in a non-communicating wired system.
FOSSIL FUEL APPLICATIONS NOTE: Use of the accessory transformer is recommended if installing a dual fuel/fossil fuel system. Failure to use the transformer in the outdoor unit could result in over loading of the furnace transformer. This furnace can be used in conjunction with a ComfortNet™ compatible heat pump in a fossil fuel application.
Not applicable Pull Down Pull Up Bias Dehum Compressor T-Stat Heat Heat Off Delay Adjust Taps Cooling Ramping Continuous Fan Speed Tap Heating Speed Tap Cooling Speed Tap Purpose A B C D A B C D A B C D A B C D 0 Trim Adjust Plus 10% Minus 10% 0 Trim Adjust 90 Seconds 120 Seconds 150 Seconds 180 Seconds 1 Stage Stat* 2 Stage Stat** 1-Stage Compressor 2-Stage Compressor Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Function ----------------- ----------------- -----
NON-COMM (APPLIES ONLY TO A COMMUNICATING COMPATIBLE FURNACE MATCHED WITH A NON-COMMUNICATING COMPATIBLE SINGLE STAGE AIR CONDITIONER) Submenu Item Cool Airflow (CL CFM) User Modifiable Options 18, 24, 30, 36, 42, 48, or 60, default is 18 Cool Airflow Trim (CL TRM) -15% to +15% in 3% increments, default is 0%.
LED LED Status Indication Possible Causes Red Communications LED Off • Normal condition • None • None • None 2 Flashes • Out-of-box reset • Control power up • None • None • None • None On Solid • Data 1/ Data 2 miss-wire Green Receive LED • Control is “talking” on network as expected • Data 1 and data 2 wires reversed • Check communications at furnace, thermostat or wiring (data 1/ data 2 communicating compatible wires).
• Circulator blower and electronic air cleaner terminal is de• OPERATIONAL CHECKS energized. Circulator blower ramps down to OFF during the 30 seconds following the heat off delay period. The burner flames should be inspected with the burner compartment door installed. Flames should be stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow). Flames should extend directly outward from the burners without curling, floating, or lifting off.
PRESSURESWITCHES DIAGNOSTIC CHART The pressure switches are normally-open (closed during operation) negative air pressure-activated switches. They monitor the airflow (combustion air and flue products) through the heat exchanger via pressure taps located on the induced draft blower and the coil front cover. These switches guard against insufficient airflow (combustion air and flue products) through the heat exchanger and/or blocked condensate drain conditions.
ANNUALINSPECTION HORIZONTAL UNIT FILTER REMOVAL The furnace should be inspected by a qualified installer, or service agency at least once per year. This check should be performed at the beginning of the heating season. This will ensure that all furnace components are in proper working order and that the heating system functions appropriately. Pay particular attention to the following items. Repair or service as necessary.
Functional Parts ListGas Valve Gas Manifold Natural Gas Orifice Propane Gas Orifice Igniter Flame Sensor Rollout Limit Switch Primary Limit Switch Auxiliary Limit Switch Pressure Switch Induced Draft Blower Door Switch BEFORE LEAVING AN INSTALLATION • Cycle the furnace with the thermostat at least three times. Verify cooling and fan only operation. • Review the Owner’s Manual with the homeowner and • discuss proper furnace operation and maintenance. Leave literature packet near furnace.
x Furnace fails to operate. x Integrated control module LED display provides E1 error code. x ComfortNet thermostat “Call for Service” icon illuminated. x ComfortNet thermostat scrolls “Check Furnace” message. x Induced draft blower runs continuously with no further furnace operation. x Integrated control module LED display provides E2 error code. x ComfortNet thermostat “Call for Service” icon illuminated. x ComfortNet thermostat scrolls “Check Furnace” message.
x Open auxiliary input. x Open Fuse x Flame sense micro amp signal is low E5 E6 x No furnace operation. x Integrated control module LED display provides E5 error code. x ComfortNet thermostat displays “Battery Power”. x Normal furnace operation. x Integrated control module LED display provides E6 error code. x Manual reset rollout switch is open x Inducer motor overcurrent fault. x Flame sensed when it should not be present. x Primary limit.
EA d0 REVERSED PLTY NO NET DATA x Polarity of 115 volt AC is reversed x Data not yet on network. EA d0 E9 x Furnace fails to operate. x Integrated control module LED display provides EA error code. x ComfortNet thermostat “Call for Service” icon illuminated. x ComfortNet thermostat scrolls “Check Furnace” message. x Furnace fails to operate. x Integrated control module LED display provides d0 error code. x ComfortNet thermostat “Call for Service” icon illuminated.
b0 b1 b2 b3 x Furnace fails to operate. x Integrated control module LED display provides b1 error code. x ComfortNet thermostat “Call for Service” icon illuminated. x ComfortNet thermostat scrolls “Check Furnace” message. x Furnace fails to operate. x Integrated control module LED display provides b2 error code. x ComfortNet thermostat “Call for Service” icon illuminated. x ComfortNet thermostat scrolls “Check Furnace” message. x Furnace operates at reduced performance.
x Furnace fails to operate. x Integrated control module LED display provides b7 error code. x ComfortNet thermostat “Call for Service” icon illuminated. x ComfortNet thermostat scrolls “Check Furnace” message. x Furnace operates at reduced performance. x Integrated control module LED display provides b9 error code. x Furnace fails to operate. x Integrated control module LED display provides b5 error code. x ComfortNet thermostat “Call for Service” icon illuminated.
STATUS CODES NO POWER On A b0 b1 b2 b3 b4 b5 b6 b7 b9 C C1 C2 d d0 d1 d2 d4 dF E0 E1 E2 E3 E4 E5 E6 E7 E8 E9 EA EC Ed EF F Ft H HI IF P P1 P2 50 12 NORMAL OPERATION INDICATES AIRFLOW, FOLLOWED BY CFM BLOWER MOTOR NOT RUNNING BLOWER COMMUNICATION ERROR BLOWER HP MIS-MATCH BLOWER MOTOR OPERATING IN POWER, TEMPERATURE, OR SPEED LIMIT BLOWER MOTOR CURRENT TRIP OR LOST ROTOR BLOWER MOTOR LOCKED ROTOR BLOWER OVER/UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP INCOMPLETE PARAMETERS SENT TO MOTOR LOW INDOOR AIRFLOW
HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
SPECIAL INSTRUCTIONS FOR PRODUCTS INSTALLED IN THE STATE OF MASSACHUSETTS VENT/FLUE TEE DISTANCE BETWEEN VENT AND GRADE COMBUSTION AIR INTAKE. DISTANCE BETWEEN COMBUSTION AIR INTAKE AND GRADE 3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment.
THIS PAGE LEFT INTENTIONALLY BLANK NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE. Goodman Manufacturing Company, L.P. 5151 San Felipe Suite 500 Houston, TX 77056 www.goodmanmfg.com • www.amana-hac.com © 2011 - 2013 Goodman Manufacturing Company, L.P.