Installation Guide

41
PCBBF139
STATIC 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
T STAT CALL CFM CFM CFM CFM CFM CFM CFM CFM
Ylo 1698 1621 1553 1497 1437 1393 1328 1270
Y 2266 2202 2143 2090 2040 1995 1945 1896
Ylo 1088 999 899 772 667 561 490 418
Y 1698 1621 1553 1497 1437 1393 1328 1270
Ylo 1088 999 899 772 667 561 490 418
Y 2266 2202 2143 2090 2040 1995 1945 1896
Ylo 1698 1621 1553 1497 1437 1393 1328 1270
Y 1450 1382 1314 1243 1181 1115 1047 973
Ylo 1698 1621 1553 1497 1437 1393 1328 1270
Y 1886 1822 1758 1701 1646 1591 1535 1482
Ylo 1088 999 899 772 667 561 490 418
Y 1450 1382 1314 1243 1181 1115 1047 973
Ylo 1886 1822 1758 1701 1646 1591 1535 1482
Y 2266 2202 2143 2090 2040 1995 1945 1896
Ylo 1886 1822 1758 1701 1646 1591 1535 1482
Y 1088 999 899 772 667 561 490 418
PCBBF139
STATIC 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
T STAT CALL CFM CFM CFM CFM CFM CFM CFM CFM
OFF OFF OFF G 1450 1382 1314 1243 1181 1115 1047 973
ON OFF OFF G 1886 1822 1758 1701 1646 1591 1535 1482
ON ON OFF G 1088 999 899 772 667 561 490 418
OFF ON OFF G 1698 1621 1553 1497 1437 1393 1328 1270
OFF OFF ON G 2266 2202 2143 2090 2040 1995 1945 1896
OFF ON ON G 1450 1382 1314 1243 1181 1115 1047 973
ON OFF ON G 1450 1382 1314 1243 1181 1115 1047 973
ON ON ON G 1450 1382 1314 1243 1181 1115 1047 973
PCBBF139
STATIC 0.6 0.7 0.8
T STAT CALL CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
W1 1450 29 1382 30 1314 32 1243 33 1181 35 1115 1047 973
W2 1886 31 1822 33 1758 34 1701 35 1646 36 1591 1535 1482
W1 1088 38 999 42 899 46 772 N/A 667 N/A 561 490 418
W2 1886 31 1822 33 1758 34 1701 35 1646 36 1591 1535 1482
W1 1088 38 999 42 899 46 772 N/A 667 N/A 561 490 418
W2 1698 35 1621 37 1553 38 1497 40 1437 41 1393 1328 1270
W1 1698 24 1621 26 1553 27 1497 28 1437 29 1393 1328 1270
W2 2266 26 2202 27 2143 28 2090 28 2040 29 1995 1945 1896
*MEC800805D* - HEATING
DIP Switches
S2-2 S2-3 S2-4
*MEC800805D* - COOLING
DIP Switches
S1-1 S1-2 S1-3
OFF OFF OFF*
ON OFF OFF
ON ON OFF
OFF ON OFF
OFF OFF ON
OFF ON ON
ON OFF ON
ON ON ON
*MEC800805D* - CONTINOUS FAN
**NOT RECOMMENDED
DIP Switches
S1-4 S2-1
0.1
0.2
0.3
OFF ON
*DEFAULT
0.4
0.5
OFF OFF*
ON OFF
ON ON
AIRFLOW TABLES
GMEC800805DN