Installation Guide

43
PCBBF139
STATIC 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
T STAT CALL CFM CFM CFM CFM CFM CFM CFM CFM
Ylo 1265 1204 1146 1091 1034 973 918 870
Y 1598 1547 1509 1464 1417 1387 1340 1295
Ylo 789 719 637 545 458 378 324 273
Y 1265 1204 1146 1091 1034 973 918 870
Ylo 789 719 637 545 458 378 324 273
Y 1598 1547 1509 1464 1417 1387 1340 1295
Ylo 1265 1204 1146 1091 1034 973 918 870
Y 1424 1378 1330 1274 1226 1172 1119 1071
Ylo 1265 1204 1146 1091 1034 973 918 870
Y 1810 1764 1718 1682 1633 1596 1549 1510
Ylo 789 719 637 545 458 378 324 273
Y 1424 1378 1330 1274 1226 1172 1119 1071
Ylo 1810 1764 1718 1682 1633 1596 1549 1510
Y 1598 1547 1509 1464 1417 1387 1340 1295
Ylo 1810 1764 1718 1682 1633 1596 1549 1510
Y 789 719 637 545 458 378 324 273
PCBBF139
STATIC 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
T STAT CALL CFM CFM CFM CFM CFM CFM CFM CFM
OFF OFF OFF G 1424 1378 1330 1274 1226 1172 1119 1071
ON OFF OFF G 1810 1764 1718 1682 1633 1596 1549 1510
ON ON OFF G 789 719 637 545 458 378 324 273
OFF ON OFF G 1265 1204 1146 1091 1034 973 918 870
OFF OFF ON G 1598 1547 1509 1464 1417 1387 1340 1295
OFF ON ON G 1424 1378 1330 1274 1226 1172 1119 1071
ON OFF ON G 1424 1378 1330 1274 1226 1172 1119 1071
ON ON ON G 1424 1378 1330 1274 1226 1172 1119 1071
PCBBF139
STATIC 0.6 0.7 0.8
T STAT CALL CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
W1 1424 36 1378 38 1330 39 1274 41 1226 42 1172 1119 1071
W2 1810 41 1764 42 1718 43 1682 44 1633 45 1596 1549 1510
W1 789 N/A 719 N/A 637 N/A 545 N/A 458 N/A 378 324 273
W2 1810 N/A 1764 N/A 1718 N/A 1682 N/A 1633 N/A 1596 1549 1510
W1 789 N/A 719 N/A 637 N/A 545 N/A 458 N/A 378 324 273
W2 1265 N/A 1204 N/A 1146 N/A 1091 N/A 1034 N/A 973 918 870
W1 1265 41 1204 43 1146 45 1091 48 1034 50 973 918 870
W2 1598 46 1547 48 1509 49 1464 51 1417 52 1387 1340 1295
*MEC801004C* - HEATING
DIP Switches
S2-2 S2-3 S2-4
*MEC801004C* - COOLING
DIP Switches
S1-1 S1-2 S1-3
OFF OFF OFF*
ON OFF OFF
ON ON OFF
OFF ON OFF
OFF OFF ON
OFF ON ON
ON OFF ON
ON ON ON
*MEC801004C* - CONTINOUS FAN
**NOT RECOMMENDED
DIP Switches
S1-4 S2-1
0.1
0.2
0.3
OFF ON
*DEFAULT
0.4
0.5
OFF OFF*
ON OFF**
ON ON**
AIRFLOW TABLES
GMEC801004CN