Installation Guide

44
PCBBF139
STATIC 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
T STAT CALL CFM CFM CFM CFM CFM CFM CFM CFM
Ylo 1627 1566 1520 1470 1420 1398 1391 1343
Y 2226 2165 2126 2083 2048 2011 1983 1945
Ylo 815 742 662 590 503 422 362 299
Y 1627 1566 1520 1470 1420 1398 1391 1343
Ylo 815 742 662 590 503 422 362 299
Y 2226 2165 2126 2083 2048 2011 1983 1945
Ylo 1627 1566 1520 1470 1420 1398 1391 1343
Y 1381 1324 1274 1220 1164 1137 1109 1049
Ylo 1627 1566 1520 1470 1420 1398 1391 1343
Y 1831 1770 1723 1677 1630 1590 1547 1506
Ylo 815 742 662 590 503 422 362 299
Y 1381 1324 1274 1220 1164 1137 1109 1049
Ylo 1831 1770 1723 1677 1630 1590 1547 1506
Y 2226 2165 2126 2083 2048 2011 1983 1945
Ylo 1831 1770 1723 1677 1630 1590 1547 1506
Y 815 742 662 590 503 422 362 299
PCBBF139
STATIC 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
T STAT CALL CFM CFM CFM CFM CFM CFM CFM CFM
OFF OFF OFF G 1381 1324 1274 1220 1164 1137 1109 1049
ON OFF OFF G 1831 1770 1723 1677 1630 1590 1547 1506
ON ON OFF G 815 742 662 590 503 422 362 299
OFF ON OFF G 1627 1566 1520 1470 1420 1398 1391 1343
OFF OFF ON G 2226 2165 2126 2083 2048 2011 1983 1945
OFF ON ON G 1381 1324 1274 1220 1164 1137 1109 1049
ON OFF ON G 1381 1324 1274 1220 1164 1137 1109 1049
ON ON ON G 1381 1324 1274 1220 1164 1137 1109 1049
PCBBF139
STATIC 0.6 0.7 0.8
T STAT CALL CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM
W1 1381 45 1324 47 1274 49 1220 51 1164 53 1137 1109 1049
W2 1831 49 1770 50 1723 52 1677 53 1630 55 1590 1547 1506
W1 815 N/A 742 N/A 662 N/A 590 N/A 503 N/A 422 362 299
W2 1831 N/A 1770 N/A 1723 N/A 1677 N/A 1630 N/A 1590 1547 1506
W1 815 N/A 742 N/A 662 N/A 590 N/A 503 N/A 422 362 299
W2 1627 N/A 1566 N/A 1520 N/A 1470 N/A 1420 N/A 1398 1391 1343
W1 1627 38 1566 40 1520 41 1470 42 1420 44 1398 1391 1343
W2 2226 40 2165 41 2126 42 2083 43 2048 43 2011 1983 1945
*MEC801205D* - HEATING
DIP Switches
S2-2 S2-3 S2-4
*MEC801205D* - COOLING
DIP Switches
S1-1 S1-2 S1-3
OFF OFF OFF*
ON OFF OFF
ON ON OFF
OFF ON OFF
OFF OFF ON
OFF ON ON
ON OFF ON
ON ON ON
*MEC801205D* - CONTINOUS FAN
**NOT RECOMMENDED
DIP Switches
S1-4 S2-1
0.1
0.2
0.3
OFF ON
*DEFAULT
0.4
0.5
OFF OFF*
ON OFF**
ON ON**
AIRFLOW TABLES
GMEC801205DN