Installation Guide

36
Profile D ramps up to 50% of the demand for 1/2 minute,
then ramps to 85% of the full cooling demand airflow and
operates there for approximately 7 1/2 minutes. The
motor then steps up to the full demand airflow. Profile D
has a 1/2 minute at 50% airflow OFF delay.
OFF
OFF
Figure 50
Model Tap
Low
Stage
Cool
High
Stage
Cool
Low
Stage
Heat
High
Stage
Heat
A
403 596 422 494
B
527 796 471 553
C
675 974 521 601
D
803 1192 574 676
A
398 599 667 953
B
557 817 740 1059
C
696 1007 808 1158
D
810 1212 881 1260
A
403 629 855 1202
B
540 806 923 1316
C
705 1023 1033 1389
D
819 1230 1063 1396
A
513 789 867 1228
B
660 967 939 1337
C
791 1182 1016 1430
D
913 1375 1077 1516
A
564 820 1256 1818
B
784 1133 1292 1870
C
982 1464 1316 1910
D
1259 1736 1358 1957
A
547 867 1329 1891
B
831 1160 1362 1940
C
1020 1467 1390 1968
D
1278 1910 1440 2028
A
449 655 682 957
B
569 807 750 1059
C
716 998 820 1155
D
854 1207 888 1251
A
433 656 687 938
B
541 790 751 950
C
686 972 814 986
D
806 1195 874 992
A 405 624 758 1057
B 549 808 815 1146
C 678 994 882 1256
D 784 1177 946 1349
A
556 837 889 1234
B
714 1022 944 1325
C
838 1206 1019 1442
D
991 1475 1068 1528
A
524 784 1209 1759
B
744 1078 1249 1797
C
927 1388 1277 1840
D
1185 1766 1300 1881
A
540 854 1284 1744
B
870 1123 1310 1827
C
1000 1399 1350 1860
D
1235 1804 1388 1918
*CVC960403BN*
*CVC960603BN
*CVC960803BN
*CVC960804CN*
*CVC961005CN*
*CVC961205DN*
*MVC960403BN*
*MVC960603BN*
*MVC960803BN*
*MVC960804CN*
*MVC961005CN*
*MVC961205DN*
Airflow Table
7. Select the heating speed for your model from the heating
speed chart in the Specification Sheet. The adjust setting
(already established by the cooling speed selection)
determines which set of speeds are available. The selected
speed must provide a temperature rise within the rise
range listed with the particular model.
Example: If the *MVC960804CN** is set for 1210 CFM
on cooling, the “ADJUST” is set to “+” (plus).
The four heating speeds available are “A
Plus”, “B Plus”, “C Plus”, and “D Plus”. “A
Plus” has a rise of 46°F for both stages which
is within the 30-60°F rise range for the
*MVC960804CN**. This setting will keep
electrical consumption to a minimum. Set
the “Heat” speed DIP switches to “A”.
34
AOFFOFF
B* ON OFF
COFFON
DONON
Switch Bank: S4
Heating
Airflow
DIP Switch No.
(*Indicates factory setting)
8. Select the desired “heating” speed tap by positioning
switches S4- 3,4 appropriately. Refer to figure above.
Verify CFM by noting the number displayed on the dual 7-
segment LED display.
In general lower heating speeds will: reduce electrical consump-
tion, lower operating sound levels of the blower, and increase the
outlet air temperature delivered to the home. The speeds avail-
able allow the blower performance to be optimized for the par-
ticular homeowner’s needs.
BLOWER HEAT OFF DELAY TIMINGS
The integrated control module provides a selectable heat off de-
lay function. The heat off delay period may be set to 90, 120,
150, 180 seconds using the DIP switches or jumper provided on
the control module. The delay is factory shipped at 150 seconds
but may be changed to suit the installation requirements and/or
homeowner preference. Refer to the following figures for switch
positions and corresponding delay times.
12
90 seconds OFF OFF
120 seconds ON OFF
150 seconds* OFF ON
180 seconds ON ON
Heat OFF Delay
DIP Switch No.
Switch Bank: S1
(*Indicates factory setting)
Heat Off Delay Dip Switches