Installation Guide

52
T
ROUBLESHOOTING
C
HART
Symptoms of Abnormal
Operation (Legacy
& ComfortNet
Thermostat)
Diagnostic/
Status LED
Codes
Fault Description
ComfortNet™
Thermostat Only
Possible Causes Corrective Actions Notes & Cautions
Message Code
b4
MOTOR
TRIPS
b4 Turn power OFF prior
to repair
Furnace fails to operate.
Integrated control
module LED display
provides b4 error code.
ComfortNet™ thermostat
“Call for Service” icon
illuminated.
ComfortNet™ thermostat
scrollsCheck Furnace
message.
MOTOR LCKD
ROTOR
b5 Turn power OFF prior
to repair.
Replace motor with
correct replacement
part.
Replace wheel with
correct replacement
part.
Furnace fails to operate.
Integrated control
module LED display
provides b6 error code.
ComfortNet™ thermostat
“Call for Service” icon
illuminated.
ComfortNet™ thermostat
scrollsCheck Furnace”
message.
b6 MOTOR
VOLTS
b6 Turn power OFF prior
to repair
Furnace fails to operate.
Integrated control
module LED display
provides b7 error code.
ComfortNet™ thermostat
“Call for Service” icon
illuminated.
ComfortNet™ thermostat
scrollsCheck Furnace”
message.
b7 MOTOR
PARAMS
b7
Furnace operates at
reduced performance or
Integrated control
module LED display
provides b9 error code.
b9 LOW ID
AIRFLOW
B9 Blocked filters.
Restrictive ductwork.
Undersized ductwork.
Check filters for
blockage. Clean filters
or remove obstruction.
Check ductwork for
blockage. Remove
obstruction. Verify all
registers are fully open.
Verify ductwork is
appropriately sized for
system. Resize/replace
ductwork if necessary.
Turn power OFF prior
to repair.
Circulator blower
motor senses
high current.
Circulator blower
motor fails to start
10 consecutive
times.
b5
Furnace fails to operate.
Integrated control
module LED display
provides b5 error code.
ComfortNet™ thermostat
“Call for Service” icon
illuminated.
ComfortNet™ thermostat
scrolls “Check Furnace”
message.
operates on low stage
when high stage is
expected.
Circulator blower
motor senses
a loss of rotor
control.
Circulator blower
motor shuts down
for over or under
voltage condition.
Circulator blower
motor shuts
down due to
over temperature
condition on
power module.
Circulator blower
motor does not
have enough
information to
operate properly.
Motor fails to start
40 consecutive
times.
Airflow is lower
than demanded.