Service Manual

SYSTEM OPERATION
55
ComfortNet™ System
FURNACE ADVANCED FEATURES MENUS
Submenu Item Indication/User Modifiable Options Comments
Fault 1 (FAULT #1) Most recent furnace fault For display only
Fault 2 (FAULT #2) Next most recent furnace fault For display only
Fault 3 (FAULT #3) Next most recent furnace fault For display only
Fault 4 (FAULT #4) Next most recent furnace fault For display only
Fault 5 (FAULT #5) Next most recent furnace fault For display only
Fault 6 (FAULT #6) Least recent furnace fault For display only
Clear Fault History (CLEAR) NO or YES
Selecting “YES” clears the
fault history
NOTE:
Consecutively repeated faults are shown a maximum of 3 times.
DIAGNOSTICS
Submenu Item Indication (for Display Only; not User Modifiable)
Model Number (MOD NUM) Displays the furnace model number
Serial Number (SER NUM) Displays the furnace serial number (Optional)
Software (SOFTWARE) Displays the application software revision
IDENTIFICATION
Submenu Item User Modifiable Options Comments
Heat Airflow Trim (HT
TRM)
-10% to +10% in 2% increments,
default is 0%
Trims the heating airflow by the selected
amount.
Heat ON Delay (HT ON 5, 10, 15, 20, 25, or 30 seconds,
default is 30 seconds
Selects the indoor blower heat ON delay
Heat OFF Delay (HT OFF) 30, 60, 90, 120, 150, or 180
seconds, default is 150 seconds
Selects the indoor blower heat OFF delay
Heat Airflow (HT ADJ) 1, 2, 3, or 4 Selects the nominal heating airflow (see
Startup Procedure and Adjustment
Circulator Blower Speeds for additional
information)
SET-UP
THERMOSTAT M ENU
If this furnace is installed with a ComfortNet compatible heat pump, the system is recognized as a dual fuel system. The
balance point temperature should be set via the thermostat advanced menu.