Specifications
8 www.goodmanmfg.com SS-GMVC96
SS-GMVC96 www.goodmanmfg.com 9
Airflow Data (cont.)
GMVC961205DNA
Cooling Speed
( @ .1" - .8" w.c. ESP)
GMVC961205DNA
Heating Speed
(@ .1" - .5" w.c. ESP; Rise Range: 35 - 65°F)
Tap Adjust
High-Stage
CFM
Low-Stage
CFM
Tap Adjust
High-Stage
CFM
Low-Stage
CFM
Rise
(°F)
A
Minus 10% 780 492
A
Minus 10% 1,702 1,196 63
Minus 5% 824 520 Minus 5% 1,796 1,263 59
Normal 867 547 Normal 1,891 1,329 56
Plus 5% 910 574 Plus 5% 1,986 1,395 54
Plus 10% 954 602 Plus 10% 2,080 1,462 51
B
Minus 10% 1,044 748
B
Minus 10% 1,746 1,226 61
Minus 5% 1,102 789 Minus 5% 1,843 1,294 58
Normal 1,160 831 Normal 1,940 1,362 55
Plus 5% 1,218 873 Plus 5% 2,037 1,430 52
Plus 10% 1,276 914 Plus 10% 2,134 1,498 50
C
Minus 10% 1,320 918
C
Minus 10% 1,771 1,251 60
Minus 5% 1,394 969 Minus 5% 1,870 1,321 57
Normal 1,467 1,020 Normal 1,968 1,390 54
Plus 5% 1,540 1,071 Plus 5% 2,066 1,460 52
Plus 10% 1,614 1,122 Plus 10% 2,165 1,529 49
D
Minus 10% 1,719 1,150
D
Minus 10% 1,825 1,296 58
Minus 5% 1,815 1,214 Minus 5% 1,927 1,368 55
Normal 1,910 1,278 Normal 2,028 1,440 53
Plus 5% 2,006 1,342 Plus 5% 2,129 1,512 50
Plus 10% 2,101 1,406 Plus 10% 2,231 1,584 48
Notes
• All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
• For most jobs, about 400 CFM per ton when cooling is desirable.
• INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.