Installation Guide

18
NOTE: In vertical installations, air conditioning coil conden-
sate may drain into the furnace trap as long as there is a
trap between the coil and the furnace trap and the drain pipe
is not terminating below the water level of the furnace trap.
GENERAL DRAIN INFORMATION
All furnace models come with a factory installed drain trap.
For vertical installations, the trap will remain in the factory
position except for a counterflow when the installer desires
the drain to exit the right side. All furnace models installed
horizontally require the trap to be relocated. Many drain hoses
have a built–in grommet which will provide a cabinet seal
when installed. See instructions below for your model and
installation position. NOTE: Both sides of the drain trap
must be primed prior to initial furnace start up
FIELD SUPPLIED DRAIN
Drain the furnace and air conditioning coil if applicable, in
compliance with code requirements. In horizontal or
counterflow installations, a field installed rubber coupling
will allow the drain trap to be removed for cleaning. The
drain trap must be primed before initial furnace start up.
When an air conditioning coil drain is connected to the field
supplied furnace drain, it must be vented.
#
3
#1
#2
#4
#5
#
6
#7
#8
#9
#10
#11
100 Degree
Elbow
Coupling
Figure 20
NOTE: Hoses are model specific
and not all hoses will be shipped with all models.
UPFLOW MODEL INSTALLED VERTICALLY
The trap and factory installed hoses remain as shipped. The
furnace drain may exit either the right or left side of the
furnace cabinet.
Installer selects right or left side drain
and installs this hose accordingly.
Hose #1
Hose #2
45 degree
barb-pipe
adapter
45 degree
barb-pipe
adapter
Figure 21
DRAIN EXITING RIGHT SIDE
1. Locate and Install the 45º pipe / hose drain coupling
from the outside of the cabinet (barbed end goes in
the cabinet) through hole in the right side of the cabinet
and secure with two field supplied #8 self-tapping
screws (see Figure 21).
2. Locate the long drain hose #3 and cut at line “A” .
3. Install large end of hose #3 to trap outlet and secure
with 1.25" clamp.
4. Install smaller end of hose #3 on 45º elbow and secure
with 1" clamp.
5. Refer to Field Supplied Drain section for instructions
on field supplied / installed drain on outlet of furnace
trap.
DRAIN EXITING LEFT SIDE
1. Install the 45 degree pipe / hose drain coupling from
the outside of the cabinet (barbed end goes in the
cabinet) through the hole in the left side of the cabinet
and secure with two field supplied #8 self-tapping
screws (see Figure 21).
2. Locate the long drain hose #3 and cut at “B” line for a
17.5" cabinet; cut at line “C” for a 21" cabinet; do not
cut for a “D” width cabinet.
3. Install large end of hose #3 to trap outlet and secure
with 1.25" clamp.