Product Overview

2 www.goodmanmfg.com SS-GMVC96
SS-GMVC96 www.goodmanmfg.com 3
GMVC96
0403BNA
GMVC96
0603BNA
GMVC96
0803BNA
GMVC96
0804CNA
GMVC96
1005CNA
GMVC96
1005DNA
GMVC96
1205DNA
Heating Data
High Fire Input¹ 40,000 60,000 80,000 80,000 100,000 100,000 120,000
High Fire Output¹ 38,400 57,600 76,800 76,800 96,000 96,000 115,200
Low-Fire Steady-State Input¹ 28,000 42,000 56,000 56,000 70,000 70,000 84,000
Low-Fire Steady-State Output¹ 26,880 40,320 53,760 53,760 67,200 67,200 80,640
AFUE² 96 96 96 96 96 96 96
Temperature Rise Range (°F) 35 - 65 20 - 50 35 - 65 25 - 55 35 - 65 35 - 65 35 - 65
Vent Diameter³ 2" - 3" 2" - 3" 2" - 3" 2" - 3" 2" - 3" 2" - 3" 2" - 3"
No. of Burners 2 3 4 4 5 5 6
Circulator Blower
Available AC @ 0.5" ESP 1.5 - 3 1.5 - 3 1.5 - 3 1.5 - 4 2 - 5 2 - 5 2 - 5
Size (D x W) 10" x 8" 11" x 8" 11" x 8" 11" x 10" 11" x 10" 11" x 11" 11" x 11"
Horsepower @ 1075 RPM ½ ½ ½ ¾ 1 1 1
Speed VS ECM VS ECM VS ECM VS ECM VS ECM VS ECM VS ECM
Electrical Data
Min. Circuit Ampacity⁴ 7.8 7.8 7.8 10.6 14.4 14.4 14.4
Max. Overcurrent Device (amps)⁵ 15 15 15 15 20 20 20
Shipping Weight (lbs) 114 117 120 141 143 153 156
¹ Natural Gas BTU/h
² DOE AFUE based upon Isolated Combuson System (ICS)
³ Installer must supply one or two PVC pipes: one for combuson air (oponal) and one for the ue outlet (required).
Vent pipe must be either 2" or 3" in diameter, depending upon furnace input, number of elbows, length of run
and installaon (1 or 2 pipes). The oponal Combuson Air Pipe is dependent on installaon/code requirements
and must be 2" or 3" diameter PVC.
Minimum Circuit Ampacity = (1.25 x Circulator Blower Amps) + ID Blower amps. Wire size should be determined
in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
Maximum Overcurrent Protecon Device refers to maximum recommended fuse or circuit breaker size.
May use fuses or HACR-type circuit breakers of the same size as noted.
Notes
All furnaces are manufactured for use on 115 VAC, 60 Hz, single-phase electrical supply.
Gas Service Connecon ½" FPT
Important: Size fuses and wires properly and make electrical connecons in accordance with the
Naonal Electrical Code and/or all exisng local codes.
For boom return: Failure to unfold anges may reduce airow by up to 18%. This could result in performance
and noise issues.
For servicing or cleaning, a 24" front clearance is required. Unit connecons (electrical, ue and drain)
may necessitate greater clearances than the minimum clearances listed above. In all cases, accessibility
clearance must take precedence over clearances from the enclosure where accessibility clearances are greater.