Service Manual

TROUBLESHOOTING
49
Symptoms of Abnormal
Operation (Legacy
& ComfortNet™
Thermostat)
Diagnostic/
Status LED
Codes
Fault Description
ComfortNet
Thermostat Only
Possible Causes Corrective Actions Notes & Cautions
Message Code
Furnace fails to operate.
Integrated control
module LED display
provides E7 error code.
•ComfortNet
thermostat “Call
for Service icon
illuminated.
•ComfortNet
thermostat scrolls
“Check Furnace”
message.
E7 Problem with
igniter circuit.
IGNITER
FA ULT
E7 Improperly connected
igniter.
Shorted igniter.
Poor unit ground.
Igniter relay fault on
integrated control
module.
Check and correct
wiring from integrated
control module to
igniter.
Replace shorted igniter.
Check and correct unit
ground wiring.
Check igniter output
from control. Replace if
necessary.
Turn power OFF
prior to repair.
Replace igniter with
correct replacement
part.
Replace control with
correct replacement
part.
Furnace fails to operate
on high stage; furnace
operates normally on low
stage.
Integrated control module
LED display provides E8
error code.
E8 High stage
pressure switch
circuit is closed
at start of heating
cycle.
Induced draft
blower is
operating.
Furnace is
operating on low
stage only
PS2 CLOSED E8 High stage pressure
switch contacts sticking.
Shorts in pressure
switch circuit wiring.
Replace high stage
pressure switch.
Repair short in wiring
Turn power OFF prior
to repair.
Replace pressure
switch with proper
replacement part.
Furnace fails to operate
on high stage; furnace
operates normally on low
stage.
Integrated control module
LED display provides E9
error code.
E9 High stage
pressure switch
circuit is not
closed.
Induced draft
blower is
operating.
Furnace is
operating on low
stage only
PS2 OPEN E9 Pressure switch hose
blocked pinched, or
connected improperly.
Blocked fue and/or inlet
air pipe, blocked drain
system or weak induced
draft blower.
Incorrect pressure
switch set point or
malfunctioning switch
contacts.
Loose or improperly
connected wiring.
Inspect pressure switch
hose. Repair/replace if
necessary.
Inspect fue and/or inlet
air piping for blockage,
proper length, elbows,
and termination. Check
drain system. Correct as
necessary.
Check induced draft
blower performance.
Correct as necessary.
Correct pressure switch
set point or contact
motion.
Tighten or correct wiring
connection.
Turn power OFF prior
to repair.
Replace pressure
switch with proper
replacement part.
Replace induced draft
blower with proper
replacement part.
Furnace fails to operate.
Integrated control module
LED display provides EA
error code.
ComfortNet™ thermostat
“Call for Service” icon
illuminated.
ComfortNet™ thermostat
scrolls “Check Furnace”
message.
EA Polarity of 115 volt
AC is reversed
REVERSED
PLTY
EA Polarity of 115 volt AC
power to furnace or
integrated module is
revered.
Poor unit ground
Review wiring diagram to
correct polarity.
Verify proper ground.
Correct if necessary.
Check and correct
wiring.
Turn power OFF prior
to repair.
Integrated control
module LED display EF
error code.
ComfortNet™ thermostat
“Call for Service” .
EF Aux switch open Aux Alarm
Fault
EF High water level in the
evaporation coil.
Check overfow pan and
service.
Turn power OFF prior
to service.
Furnace fails to operate.
Integrated control module
LED display provides d0
error code.
ComfortNet™ thermostat
“Call for Service” icon
illuminated.
ComfortNet™ thermostat
scrolls “Check Furnace”
message.
d0 Data not yet on
network.
NO NET
DATA
d0 Furnace does not
contain any shared data.
Populate shared data
set using memory card.
Turn power OFF prior
to repair
Use memory card for
the specifc model.
Insert memory card
BEFORE turning
power ON. Memory
card may be removed
after data is loaded
and power is turned
off.
Error code will be
cleared once data is