Installation Guide

16 www.goodmanmfg.com SS-GPC14M
SS-GPC14M www.goodmanmfg.com 17
Airflow Data
  

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
GPC1424M41*
T1 230
CFM 580 505 445 390 320 --- --- ---
WATTS 36 46 54 60 65 --- --- ---
 230
CFM 900 850 800 740 655 605 555 490 420
WATTS 92 101 110 119 126 135 140 145 153
 230
CFM 1230 1190 1140 1095 1040 990 920 850 785
WATTS 202 212 220 233 235 243 249 262 265
GPC1430M41*
T1 230
CFM --- 550 475 415 340 270 --- --- ---
WATTS --- 50 59 66 74 77 --- --- ---
 230
CFM 1070 1030 985 935 875 770 705 660 ---
WATTS 144 153 160 169 178 184 188 200 ---
 230
CFM 1345 1305 1260 1220 1180 1125 1080 975 900
WATTS 258 273 272 283 292 298 306 310 320
GPC1436M41*
T1 230
CFM 1070 1030 980 935 870 775 720 665 ---
WATTS 145 161 165 173 181 190 198 202 ---
 230
CFM 1285 1245 1205 1165 1110 1060 1005 910 860
WATTS 238 246 258 264 263 282 288 296 296
 230
CFM 1505 1465 1420 1385 1335 1300 1250 1205 1150
WATTS 359 371 384 383 393 398 406 416 422
GPC1442M41*
T1 230
CFM 1035 995 945 895 845 790 695 630 580
WATTS 132 144 152 157 168 176 183 189 196
 230
CFM 1410 1365 1330 1290 1250 1205 1155 1110 1065
WATTS 301 312 316 322 331 339 347 356 365
 230
CFM 1545 1500 1465 1425 1385 1345 1310 1270 1225
WATTS 390 396 413 417 421 431 435 443 453
GPC1448M41*
T1 230
CFM 1355 1300 1250 1210 1155 1110 1045 965 905
WATTS 212 228 230 246 248 261 273 282 289
 230
CFM 1655 1610 1575 1530 1485 1440 1395 1340 1285
WATTS 365 370 383 396 410 417 416 423 434
 230
CFM 1895 1855 1805 1770 1730 1685 1640 1600 1565
WATTS 558 558 578 584 590 594 602 612 615
GPC1460M41*
T1 230
CFM 1360 1300 1260 1215 1175 1125 1085 1030 960
WATTS 213 221 233 244 255 264 273 293 304
 230
CFM 1665 1630 1595 1555 1505 1475 1425 1380 1360
WATTS 385 405 410 409 429 441 448 454 471
 230
CFM 2000 1960 1925 1875 1835 1800 1760 1725 1680
WATTS 642 651 660 651 672 683 691 699 695
Notes
Data shown is dry coil. Wet coil pressure drop is approximately 0.1” H₂O, for two-row indoor coil; 0.2” H₂O, for three-row indoor coil; and 0.3” H₂O, for four-
row indoor coil.
Data shown does not include lter pressure drop, approx. 0.08” H₂O.
ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON. USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER ASM. See Repair Parts list.
Reduce airow by 2% for 208-volt operaon.