Heat Kit Electrical Data (Blower Only, Heat Mode)


  


MCA¹ MOP² MCA¹ MOP² MCA¹ MOP²
GPC14240M41** 1.9 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 25 40 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 34 / 39 40 / 40 7.0 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 45 / 52 60 / 60 9.5 / 32,400
GPC1430M41** 1.9 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 25 40 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 34 / 39 40 / 40 7.0 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 45 / 52 60 / 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 66 / 76 70 / 80 14.25 / 48,600
GPC1436M41** 1.9 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 25 40 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 34 / 39 40 / 40 7.0 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 45 / 52 60 / 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 66 / 76 70 / 80 14.25 / 48,600
GPC1442M41** 1.9 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 25 40 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 34 / 39 40 / 40 7.0 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 45 / 52 60 / 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 66 / 76 70 / 80 14.25 / 48,600
GPC1448M41** 7.3 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 32 50 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 38 / 40 50 7.0 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 49 / 56 60 / 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 70 / 80 80 / 90 14.25 / 48,600
HKP-20C 43 / 49 45 / 50 43 / 49 45 / 50 92 / 105 100 / 110 19.0 / 64,800
GPC1460M41** 9.5 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 42 60 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 42 60 7.0 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 51 / 58 60 / 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 72 / 82 80 / 90 14.25 / 48,600
HKP-20C 43 / 49 45 / 50 43 / 49 45 / 50 93 / 107 100 / 110 19.0 / 64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protecon Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker opon
HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respecvely to meet new UL1995 requirements.