Installation Manual
6
CONDENSATE D RAIN
The condensate drain connection of the evaporator is a half cou-
pling of ¾” N.P.T. A trap must be provided to have Proper conden-
sate drainage.
2" Minimum
3" Minimum
A Positive Liquid Seal
Is Required
Flexible
Tubing-Hose
Or Pipe
Drain
Connection
Unit
Install condensate drain trap as shown. Use ¾ “ drain connection
size or larger. Do not operate without trap. Unit must be level or
slightly inclined toward drain.
WIRING
NOTE: All wiring should be made in accordance with the National
Electrical Code.
Consult your local Power Company to determine the availability of
sufficient power to operate the unit. Check the voltage, frequency,
and phase at the power supply to ensure it corresponds to the
unit’s RATED VOLTAGE REQUIREMENT.
In accordance with the N.E.C. or local codes, install a branch cir-
cuit fused disconnect near the unit. Determine wire sizes and
overcurrent protection from the unit nameplate ampacity and in
accordance with the Branch Circuit Ampacity table on the next page
or the N.E.C. The wiring should never be sized smaller than is
recommended by either of these two sources.
Fuses smaller than that recommended on the rating plate could
result in unnecessary fuse failure or service calls. The use of
protective devices of larger size than indicated could result in ex-
tensive damage to the equipment. The manufacturer bears no
responsibility for damage caused to equipment as result of the
use of larger than is recommended size protective devices.
All units have undergone a run test prior to packaging for ship-
ment. This equipment has been started at minimum rated voltage
and checked for satisfactory operation. Do not attempt to operate
this unit if the voltage is not within the minimum and maximum
voltages shown on nameplate.
All exterior wiring must be within approved weatherproof conduit.
The unit must be permanently grounded in accordance with local
codes, or in absence of local codes, with N.E.C ANSI/ NFPA NO.
70-1984 or latest edition by using ground lug in the control box.
Fuses or HACR type circuit breakers may be used where codes
permit.
CONTACTOR
R
W
G
G
RW
FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT
24 VOLT CONTROL WIRING
See
*NOTE
*NOTE:
LOW VOLTAGE CONNECTORS do not apply to heat pumps with
electric heat. LOW VOLTAGE CONNECTORS apply ONLY to *PC units
with electric heat.
tioning, Warm Air Heating and Ventilating Systems, Pamphlets No.
90A and 90B.
The supply duct from the unit through a wall may be installed
without clearance. However, minimum unit clearances as shown
in the appendix must be maintained. The supply duct should be
provided with an access panel large enough to inspect the air
chamber downstream of the heat exchanger. A cover should be
tightly attached to prevent air leaks.
For duct flange dimensions on the unit refer to the Unit Dimension
illustration in the appendix.
For down-discharge applications, the ductwork should be attached
to the roof curb prior to installing the unit. Duct work dimensions
are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be
made with flexible connections to reduce possible unit operating
sound transmission.
FILTERS
CAUTION
T
O PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF
EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT
BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR
FILTER INSTALLED IN THE RETURN AIR SYSTEM.
Filters are not provided with unit and must be supplied and exter-
nally installed in the return duct system by the installer. An optional
factory approved internal filter rack may also be used. A field-in-
stalled filter grille is recommended for easy and convenient ac-
cess to the filters for periodic inspection and cleaning. When
installing filters, ensure the air flow arrows on the filter are pointing
toward the circulator blower.
Refer to the unit filter size chart below for filter size information.
NOMINAL SIZE (INCHES) NOMINAL AREA (SQ. FT.)
10x20 1.4
14x20 1.9
14x25 2.4
15x20 2.1
16x20 2.2
16x25 2.8
20x20 2.8
20x25 3.5
25x25 4.3
MINIMUM FILTER SIZE
NOTE: Filters must have adequate face area for the rated quantity
of the unit. See the air delivery table below for recommended filter
size. Size the filters in accordance with their manufacturer recom-
mendations. Throwaway filters must be sized for a maximum face
velocity of 300 feet per minute.
500 1000 1500 2000 2500 3000 3500
7
6
5
4
3
2
D
I
S
P
O
S
A
B
L
E
F
I
L
T
E
R
P
E
R
M
A
N
E
N
T
F
I
L
T
E
R
Airflow - SCFM
N
o
m
i
n
a
l
F
i
l
t
e
r
A
r
e
a
S
q
u
a
r
e
F
e
e
t
PIPING