GPC14M Submittal

Product Specifications Product Specifications
2 www.goodmanmfg.com SS-GPC14M
SS-GPC14M www.goodmanmfg.com 3
Specifications
GPC14
24M41A*
GPC14
30M41A*
GPC14
36M41A*
GPC14
42M41A*
GPC14
48M41A*
GPC14
60M41A*

Total BTU/h 23,000 28,500 35,000 40,000 46,500 56,000
Sensible BTU/h 17,500 21,500 27,600 29,500 36,200 40,700
SEER / EER 14 / 11.0 14 / 11.0 14 / 11.0 14 / 11.0 14 / 11.0 14 / 11.0
Decibels 78.0 78.0 80.1 78.0 81.7 80.2
AHRI Numbers
7513338 7513342 7513339 7513340 7513341 7513343

Type EEM EEM EEM EEM EEM EEM
Nominal Cooling CFM 800 1,000 1,200 1,325 1,600 1,700
Wheel (DxW) 10 x 9 10 x 9 10 x 9 10 x 9 10 x 9 10 x 9
No. of Speeds 5 5 5 5 5 5
Horsepower - RPM
½ ½ ½ ½ ¾ 1.0

Face Area (²) 4.50 4.50 4.50 4.50 6.17 6.17
Rows Deep/ Fin per Inch 4/ 14 4/ 14 4/ 14 4/ 14 4/ 14 4/ 14
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"
Refrigerant Charge (oz.)
86 80 77 95 108 177

Horsepower - RPM ⅙ - 815 ¼ - 830 ¼ - 1,075 ¼ - 1,075 ¼ - 1,075 ⅓ - 1120
Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 3 22 / 3 22 / 3 22 / 3
Face Area (²) 12.29 12.29 8.77 11.13 15.36 20.67
Rows Deep/ Fins per Inch
1 / 24 1 / 24 2 / 27 2 / 27 1 / 24 2 / 16

Quanty 1 1 1 1 1 1
Type Rotary Scroll Scroll Scroll Scroll Scroll
Stage
Single Single Single Single Single Single

Voltage-Phase 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Compressor RLA/LRA 7.7 / 37 14.1 / 73 16.7 / 79 17.9 / 112 19.9 / 109 25.0 / 134
Indoor Blower FLA 3.9 3.9 3.9 3.9 5.7 7.0
Outdoor Fan FLA / LRA 1.1 / 1.7 1.5 / 3.0 1.4 / 2.9 1.4 / 2.9 1.4 / 2.9 2.0 / 4.4
Total Unit Amps 12.7 19.5 22.0 23.2 27.0 34.0
Min. Circuit Ampacity¹ 14.6 23.0 26.2 27.7 32.0 40.3
Max. Overcurrent Protecon²
20 amps 35 amps 40 amps 45 amps 50 amps 60 amps
 319 342 365 388 435 458
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.