GPC14M Submittal
Table Of Contents
Product Specifications Product Specifications
2 www.goodmanmfg.com SS-GPC14M
SS-GPC14M www.goodmanmfg.com 3
Specifications
GPC14
24M41A*
GPC14
30M41A*
GPC14
36M41A*
GPC14
42M41A*
GPC14
48M41A*
GPC14
60M41A*
Total BTU/h 23,000 28,500 35,000 40,000 46,500 56,000
Sensible BTU/h 17,500 21,500 27,600 29,500 36,200 40,700
SEER / EER 14 / 11.0 14 / 11.0 14 / 11.0 14 / 11.0 14 / 11.0 14 / 11.0
Decibels 78.0 78.0 80.1 78.0 81.7 80.2
AHRI Numbers
7513338 7513342 7513339 7513340 7513341 7513343
Type EEM EEM EEM EEM EEM EEM
Nominal Cooling CFM 800 1,000 1,200 1,325 1,600 1,700
Wheel (DxW) 10 x 9 10 x 9 10 x 9 10 x 9 10 x 9 10 x 9
No. of Speeds 5 5 5 5 5 5
Horsepower - RPM
½ ½ ½ ½ ¾ 1.0
Face Area (²) 4.50 4.50 4.50 4.50 6.17 6.17
Rows Deep/ Fin per Inch 4/ 14 4/ 14 4/ 14 4/ 14 4/ 14 4/ 14
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"
Refrigerant Charge (oz.)
86 80 77 95 108 177
Horsepower - RPM ⅙ - 815 ¼ - 830 ¼ - 1,075 ¼ - 1,075 ¼ - 1,075 ⅓ - 1120
Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 3 22 / 3 22 / 3 22 / 3
Face Area (²) 12.29 12.29 8.77 11.13 15.36 20.67
Rows Deep/ Fins per Inch
1 / 24 1 / 24 2 / 27 2 / 27 1 / 24 2 / 16
Quanty 1 1 1 1 1 1
Type Rotary Scroll Scroll Scroll Scroll Scroll
Stage
Single Single Single Single Single Single
Voltage-Phase 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Compressor RLA/LRA 7.7 / 37 14.1 / 73 16.7 / 79 17.9 / 112 19.9 / 109 25.0 / 134
Indoor Blower FLA 3.9 3.9 3.9 3.9 5.7 7.0
Outdoor Fan FLA / LRA 1.1 / 1.7 1.5 / 3.0 1.4 / 2.9 1.4 / 2.9 1.4 / 2.9 2.0 / 4.4
Total Unit Amps 12.7 19.5 22.0 23.2 27.0 34.0
Min. Circuit Ampacity¹ 14.6 23.0 26.2 27.7 32.0 40.3
Max. Overcurrent Protecon²
20 amps 35 amps 40 amps 45 amps 50 amps 60 amps
319 342 365 388 435 458
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.