GPC14H Installation Manual

11
SUCTION
PRESSURE
SATURATED
SUCTION
TEMPERATURE
ºF
LIQUID
PRESSURE
SATURATED
LIQUID
TEMPERATURE
ºF
PSIG R-410A PSIG R-410A
50 1 200 70
52 3 210 73
54 4 220 76
56 6 225 78
58 7 235 80
60 8 245 83
62 10 255 85
64 11 265 88
66 13 275 90
68 14 285 92
70 15 295 95
72 16 305 97
74 17 325 101
76 19 355 108
78 20 375 112
80 21 405 118
85 24 415 119
90 26 425 121
95 29 435 123
100 31 445 125
110 36 475 130
120 41 500 134
130 45 525 138
140 49 550 142
150 53 575 145
160 56 600 149
170 60 625 152
SATURATED
SUCTION PRESSURE
TEMPERATURE CHART
SATURATED
LIQUID PRESSURE
TEMPERATURE CHART
TABLE 5
Suction Pressure Liquid Pressure
Temperature (R-410A) Temperature (R-410A)
SUBCOOLING = SAT. LINE TEMP - LIQUID LINE TEMP.
Models # Superheat ± 2°F
*PC1324H41 6
*PC1330H41 6
*PC1336H41 6
*PC1342H41 6
*PC1349H41 10
*PC1360H41 6
*PC1424H41 10
*PC1430H41 10
*PC1436H41 6
*PC1442H41 7
*PC1448H41 12
*PC1460H41 6
*PC
Design superheat @ 95 °F outdoor
Models # Superheat ± 2°F
*PH1324H41 5
*PH1330H41 5
*PH1336H41 9
*PH1342H41 9
*PH1348H41 14
*PH1360H41 8
*PH1424H41 5
*PH1430H41 5
*PH1436H41 6
*PH1442H41 7
*PH1448H41 7
*PH1460H41 8
Design superheat @ 95 °F outdoor
*PH
ELECTRIC HEAT INSTALLATION & ADJUSTMENT
This series of electric cooling and heat pump package
equipment is designed to accept a field installed electric heat
kit. The unit is equipped to easily install the HKR/HKP Series
Electric Heat Kit. Full Installation Instructions are included in this
kit. Please use this document for guidance in field equipping
the package unit with electric heat.
Choose the heat kit that fits the application for the specific
installation. Permanently mark the unit’s nameplate with the
model being installed. High and low voltage connections are
detailed in the heat kit instructions.
Indoor Blower motor speed tap selection may need to be
modified to accommodate normal continuous operation to
prevent a nuisance trip. See following table.