GPC14H Installation Manual

12
5 8 10 15 20
*PC/*PH1324H41**
M
(F)
M
(F)
M
(F)
HNA
*PC/*PH1330H41**
L
(F)
L
(F)
L
(F)
MNA
*PC/*PH1336H41**
M
(F)
M
(F)
M
(F)
HNA
*PC/*PH1342H41**
L
(F)
L
(F)
MMH
*PC/*PH1348H41**
M
(F)
M
(F)
M
(F)
M
(F)
H
*PC1349H41**
M
(F)
M
(F)
M
(F)
M
(F)
H
*PC/*PH1360H41**
2
(F)
2
(F)
2
(F)
2
(F)
2
(F)
H / 3 - High; M / 2 - Medium; L / 1 - Low
Speed Taps Description: H/M/L - PSC: 3/2/1 - EEM
Electric Heat KW
*PC/*PH13(24-60) Models
Unit Model Number
5 8 10 15 20
T3 T3
*PC/*PH1460H41**
T3 T3 T3
T3 T3
*PC/*PH1442H41**
T3
*PC/*PH1448H41**
T3 T3 T3
T3 T3
T5 NA
T5 NA
T3 T5
*PC/*PH1436H41**
T3 T3 T3
*PC/*PH1430H41**
T3 T3 T3
*PC/*PH1424H41**
T3 T3 T3 T5 NA
*PC/*PH14(24-60) Models (0 - 0.5 E.S.P.)
Unit Model Number
Electric Heat KW
5 8 10 15 20
*PC/*PH1424H41** T5 T5 T5 T5 NA
*PC/*PH1430H41** T5 T5 T5 T5 NA
*PC/*PH1436H41** T5 T5 T5 T5 NA
*PC/*PH1442H41** T5 T5 T5 T5 NA
*PC/*PH1448H41** T5 T5 T5 T5 NA
*PC/*PH1460H41** T5 T5 T5 T5 NA
T4 - High Speed Cooling; T5 - High Speed Heating
*PC/*PH14(24-60) MODELS ( 0.5 - 0.8 E.S.P.)
UNIT
MODEL NUMBER
Electric Heat KW
T1 - Fan Only; T2 - Normal Speed Cooling
T3 - Normal Speed Heating
MAINTENANCE
WARNING
HIGH
VOLTAGE
!
D
ISCONNECT
ALL
POWER BEFORE SERVICING OR INSTALLING
THIS UNIT.
M
ULTIPLE POWER SOURCES MAY BE PRESENT. FAILU
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY O
DEATH.
RE
R
The Self Contained Package Air Conditioner and Heat Pump
should operate for many years without excessive service calls
if the unit is installed properly. However it is recommended
that the homeowner inspect the unit before a seasonal start
up. The coils should be free of debris so adequate airflow is
achieved. The return and supply registers should be free of
any obstructions. The filters should be cleaned or replaced.
These few steps will help to keep the product up time to a
maximum. The Troubleshooting Chart (on page 16) should
help in identifying problems if the unit does not operate
properly.
SERVICE
THE FOLLOWING INFORMATION IS FOR USE BY
QUALIFIED SERVICE AGENCY ONLY: OTHERS SHOULD
NOT ATTEMPT TO SERVICE THIS EQUIPMENT.
Common Causes of Unsatisfactory Operation of Heat Pump
on the Heating Cycle.
Inadequate Air Volume Through Indoor Coil
When a heat pump is in the heating cycle, the indoor coil is
functioning as a condenser. The return air filter must always
be clean, and sufficient air volume must pass through the
indoor coil to prevent excessive discharge pressure, and high
pressure cut out.
Outside Air Into Return Duct
Do not introduce cold outside air into the return duct of a
heat pump installation. Do not allow air entering the indoor
coil to drop below 65° F. Air below this temperature will
cause low discharge pressure, thus low suction pressure,
and excessive defrost cycling resulting in low heating output.
It may also cause false defrosting.
Undercharge
An undercharged heat pump on the heating cycle will
cause low discharge pressure resulting in low suction
pressure and frost accumulation on the outdoor coil.
Poor “Terminating” Sensor Contact
The unit’s defrost terminating sensor must make good
thermal contact with the outdoor coil tubing. Poor contact
may not terminate the unit’s defrost cycle quickly enough to
prevent the unit from cutting out on high discharge pressure.
Malfunctioning Reversing Valve
This may be due to:
1. Solenoid not energized - In order to determine if the solenoid
is energized, touch the nut that holds the solenoid cover in
place with a screwdriver. If the nut magnetically holds the
screwdriver, the solenoid is energized and the unit is in the
cooling cycle.
2. No voltage at unit’s solenoid - Check unit voltage. If no
voltage, check wiring circuit.
3. Valve will not shift:
a. Undercharged - check for leaks;
b. Valve Body Damaged - Replace valve;
c. Unit Properly Charged - If it is on the heating cycle,
raise the discharge pressure by restricting airflow through
the indoor coil. If the valve does not shift, tap it lightly
on both ends with a screwdriver handle. Do Not Tap
The Valve Body. If the unit is on the cooling cycle,
raise the discharge pressure by restricting airflow through
the outdoor coil. If the valve does not shift after the above
attempts, cut the unit off and wait until the discharge
and suction pressure equalize, and repeat above steps.
If the valve does not shift, replace it.