GPC14H Spec Sheet
Table Of Contents
18 www.goodmanmfg.com SS-GPC14H
SS-GPC14H www.goodmanmfg.com 19
Heat Kit Electrical Data (Blower Only, Heat Mode)
MCA¹ MOP² MCA¹ MOP² MCA¹ MOP²
GPC1424H41E* 1.9 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 29 30 4.75 / 16,200
HKR-08C* 32 / 36 35 / 40 --- --- 41 45 7 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 54 60 9.5 / 32,400
GPC1430H41E* 2.3 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 29 30 4.75 / 16,200
HKR-08C* 32 / 36 35 / 40 --- --- 41 45 7 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 54 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 79 80 14.25 / 48,600
GPC1430H41G* 2.3 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 29 30 4.75 / 16,200
HKR-08C* 32 / 36 35 / 40 --- --- 41 45 7 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 54 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 79 80 14.25 / 48,600
GPC1436H41D* 2.3 --- --- --- -- -- ---
HKR-05*, HKR-05C* 21 / 25 25 / 25 --- --- 29 40 4.75 / 16,200
HKR-08*, HKR-08C* 32 / 36 35 / 40 --- --- 41 45 7 / 23,800
HKR-10*, HKR-10C* 43 / 49 45 / 50 --- --- 54 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 79 80 14.25 / 48,600
GPC1442H41E* 3.6 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 29 45 4.75 / 16,200
HKR-08C* 32 / 36 35 / 40 --- --- 41 45 7 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 54 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 79 80 14.25 / 48,600
HKP-20C 43 / 49 45 / 50 43 / 49 45 / 50 104 110 19.0 / 64,800
GPC1448H41E* 3.6 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 32 50 4.75 / 16,200
HKR-08C* 32 / 36 35 / 40 --- --- 43 50 7 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 56 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 81 90 14.25 / 48,600
HKP-20C 43 / 49 45 / 50 43 / 49 45 / 50 106 110 19.0 / 64,800
GPC1460H41E* 7.5 --- --- --- -- -- ---
HKP-05C* 21 / 25 25 / 25 --- --- 40 60 4.75 / 16,200
HKR-08C* 32 / 36 35 / 40 --- --- 43 60 7 / 23,800
HKP-10C* 43 / 49 45 / 50 --- --- 56 60 9.5 / 32,400
HKP-15C* 43 / 49 45 / 50 21 / 25 25 / 25 81 90 14.25 / 48,600
HKP-20C 43 / 49 45 / 50 43 / 49 45 / 50 106 110 19.0 / 64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protecon Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker opon
^ Heat Kit requires three-phase power supply
Note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respecvely to meet new UL1995 requirements.