GPC14H Technical Manual

PACKAGE COOLING SPECIFICATIONS
35
*PC14[24-36]H41D*
IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers
in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.
(1)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
*
Calculated external filter size based on air velocity of 300 ft/min.
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.
GPC1424H41D* APC1424H41D* *PC1430H41D* *PC1436H41D*
COOLING
COOLING CAPACITY, BTUH 24,600 24,600 28,400
35,600
CAPACITY
SEER / EER 14.5 / 12.1 14.5 / 12.1 14.0 / 12.1
14.0 / 12.0
UNIT
VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 208-230/1/60
208-230/1/60
ELECTRICAL
AMPS (TOTAL) 12.6 18.4 17.7
22
SPECIFICATION
MINIMUM CIRCUIT AMPACITY 15 22 21
26
MAXIMUM OVERCURRENT PROTECTION
(1)
20 35 30
40
COMPRESSOR
TYPE ROTARY SCROLL SCROLL
SCROLL
RATED LOAD AMPS 7.7 13.5 12.8
16.7
LOCKED ROTOR AMPS 37 58.3 64
79
CONDENSER
HORSEPOWER 1/6 1/6 1/6
1/4
FAN MOTOR
RPM 815 815 815
830
FULL LOAD AMPS 1.1 1.1 1.1
1.5
LOCKED ROTOR AMPS 1.7 1.7 1.7
3.0
CONDENSER FA
N
BLADE DIAMETER (INCHES) / # OF BLADES 22 / 2 22 / 2 22 / 2
22 / 3
CONDENSER
FACE AREA - SQ. FT. 12.3 12.3 12.3
12.3
COIL
NUMBER OF ROWS 1 1 1
1
FINS PER INCH 26 26 26
26
E VAP OR AT OR
HORSEPOWER - NO. OF SPEEDS 1/2 - 5 1/2 - 5 1/2 - 5
1/2 - 5
BLOWER
FULL LOAD AMPS 3.8 3.8 3.8
3.8
MOTOR
LOCKED ROTOR AMPS NA NA NA
NA
MOTOR SPEED TAP - COOLING T2 T2 T2
T2
RPM 1050 1050 1050
1050
E VAP OR AT OR
DIAMETER X WIDTH (INCHES) 10 X 8 10 X 8 10 X 8
10 X 8
BLOWER
HI EFFICIENCY COOLING CFM 850 850 1,050
1,200
FAN ONLY COOLING CFM 800 800 950
1,100
MAX EXTERNAL STATIC PRESS ("w.c.) 0.8 0.8 0.8
0.8
E VAP OR AT OR
FACE AREA - SQ. FT. 4.66 4.66 5.25 5.25
COIL
NUMBER OF ROWS 3 3 3
3
FINS PER INCH 16 16 16
14
GENERAL
FILTER SIZE - SQ. FT. * 20 x 20 x 1 20 x 20 x 1 20 x 25 x 1
25 x 25 x 1
INFORMATION
DRAIN SIZE (INCHES) 3/4" 3/4" 3/4"
3/4"
EXPANSION DEVICE ORIFICE (0.057) ORIFICE (0.057) ORIFICE (0.062)
ORIFICE (0.068)
REFRIGERANT CHARGE R-410A (Oz.) 60 60 61
65
POWER SUPPLY CONDUIT KNOCKOUT SIZE (IN.) 3/4, 1, 1-1/4 3/4, 1, 1-1/4 3/4, 1, 1-1/4
3/4, 1, 1-1/4
LOW VOLTAGE CONDUIT KNOCKOUT SIZE (IN.) 1/2 1/2 1/2
1/2
SHIPPING WEIGHT LBS. 310 310 315
330
OPERATING WEIGHT LBS. 305 305 310
315