GPC14H Technical Manual

PRODUCT DESIGN
7
HKR ELECTRICAL DATA
All wires and overcurrent protection devices are sized for use with electric heaters only and without refrigera-
tion. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE
COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent protection during
refrigeration cycle.
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.
WARNINGWARNING
*PC14[24-60]H41**
Maximum Maximum
Overcurrent Overcurrent
Protection (amps) Protection (amps)
at 208 / 240V at 208 / 240V
*PC1424H41*
-- -- -- --
HKR05*,C* 24 / 27 30 / 30 -- -- 4.75 / 16,200
HKR08*,C* 33 / 38 40 / 40 -- -- 7.0 / 23,800
HKR10*,C* 45 / 51 60 / 60 -- -- 9.5 / 32,400
*PC1430H41*
-- -- -- --
HKR05*,C* 24 / 27 30 / 30 -- -- 4.75 / 16,200
HKR08*,C* 34 / 39 40 / 40 -- -- 7.0 / 23,800
HKR10*,C* 45 / 52 60 / 60 -- -- 9.5 / 32,400
HKR/P15*,C* 45 / 52 60 / 60 22 / 25 30 / 30 14.25 / 48,600
*PC1436H41*
-- -- -- --
HKR05*,C* 24 / 27 30 / 30 -- -- 4.75 / 16,200
HKR08*,C* 34 / 39 40 / 40 -- -- 7.0 / 23,800
HKR10*,C* 45 / 52 60 / 60 -- -- 9.5 / 32,400
HKR/P15*,C* 45 / 52 60 / 60 22 / 25 30 / 30 14.25 / 48,600
*PC1442H41*
-- -- -- --
HKR05*,C* 25 / 27 30 / 30 -- -- 4.75 / 16,200
HKR08*,C* 34 / 39 40 / 40 -- -- 7.0 / 23,800
HKR10*,C* 46 / 52 60 / 60 -- -- 9.5 / 32,400
HKR/P15*,C* 46 / 52 60 / 60 22 / 25 30 / 30 14.25 / 48,600
HKR/P20*,C* 46 / 52 60 / 60 43 / 49 60 / 60 19.5 / 66,500
*PC1448H41*
-- -- -- --
HKR05*,C* 25 / 28 30 / 30 -- -- 4.75 / 16,200
HKR08*,C* 34 / 40 40 / 40 -- -- 7.0 / 23,800
HKR10*,C* 46 / 53 60 / 60 -- -- 9.5 / 32,400
HKR/P15*,C* 46 / 52 60 / 60 22 / 25 30 / 30 14.25 / 48,600
HKR/P20*,C* 46 / 52 60 / 60 43 / 49 60 / 60 19.5 / 66,500
*PC1460H41*
-- -- -- --
HKR05*,C* 26 / 30 30 / 30 -- -- 4.75 / 16,200
HKR08*,C* 36 / 40 40 / 40 -- -- 7.0 / 23,800
HKR10*,C* 48 / 54 60 / 60 -- -- 9.5 / 32,400
HKR/P15*,C* 48 / 54 60 / 60 22 / 25 30 / 30 14.25 / 48,600
HKR/P20*,C* 48 / 54 60 / 60 43 / 49 60 / 60 19.5 / 66,500
Model and
Heat Kit Usage
Circuit #1 Circuit #2
Actual
kW & BTU
at 240V
Minimum Circuit
Ampacity
at 208 / 240V
Minimum Circuit
Ampacity
at 208 / 240V