GPCH3 Spec Sheet

18 www.goodmanmfg.com SS-GPCH3
SS-GPCH3 www.goodmanmfg.com 19
Heat Kit Electrical Data (Blower Only, Heat Mode)
Model and
Heat Kit Usage
Circuit #1 Circuit #2 Single-Point Kit
Actual kW /
BTU@ 240V
MCA¹ MOP² MCA¹ MOP² MCA¹ MOP²
GPCH32441* 1.9 --- --- --- -- -- ---
HKP-05C*
24.7 25 --- --- 29.5 30 4.75 / 16,200
HKR-08C*
36.5 40 --- --- 41.2 45 7 / 23,800
HKP-10C*
49.5 50 --- --- 54.2 60 9.5 / 32,400
GPCH33041* 2.3 --- --- --- -- -- ---
HKP-05C*
24.7 25 --- --- 29.5 35 4.75 / 16,200
HKR-08C*
36.5 40 --- --- 41.2 45 7 / 23,800
HKP-10C*
49.5 50 --- --- 54.2 60 9.5 / 32,400
HKP-15C*
49.5 50 24.7 25 79 80 14.25 / 48,600
GPCH33641* 2.3 --- --- --- -- -- ---
HKP-05C*
24.7 25 --- --- 29.5 35 4.75 / 16,200
HKR-08C*
36.5 40 --- --- 41.2 45 7 / 23,800
HKP-10C*
49.5 50 --- --- 54.2 60 9.5 / 32,400
HKP-15C*
49.5 50 24.7 25 79 80 14.25 / 48,600
GPCH34241* 3.6 --- --- --- -- -- ---
HKP-05C*
24.7 25 --- --- 31.7 50 4.75 / 16,200
HKR-08C*
36.5 40 --- --- 43.2 50 7 / 23,800
HKP-10C*
49.5 50 --- --- 56.2 60 9.5 / 32,400
HKP-15C*
49.5 50 24.7 25 81 90 14.25 / 48,600
HKP-20C 49.5 50 49.5 50 105.7 110 19.0 / 64,800
GPCH34841*
3.6 --- --- --- -- -- ---
HKP-05C*
25 25 --- --- 32 50 4.75 / 16,200
HKR-08C*
36 40 --- --- 43 50 7 / 23,800
HKP-10C*
49 50 --- --- 56 60 9.5 / 32,400
HKP-15C*
49 50 25 25 81 90 14.25 / 48,600
HKP-20C 49 50 49 50 106 110 19.0 / 64,800
GPCH36041*
7.5 --- --- --- -- -- ---
HKP-05C*
24.7 25 --- --- 35.4 50 4.75 / 16,200
HKR-08C*
36.5 40 --- --- 43.2 50 7 / 23,800
HKP-10C*
49.5 50 --- --- 56.2 60 9.5 / 32,400
HKP-15C*
49.5 50 24.7 25 81 90 14.25 / 48,600
HKP-20C 49.5 50 49.5 50 105.7 110 19.0 / 64,800
HKP-05C*
21 / 25 25 / 25 --- --- 40 60 4.75 / 16,200
HKR-08C*
32 / 36 35 / 40 --- --- 43 60 7 / 23,800
HKP-10C*
43 / 49 45 / 50 --- --- 56 60 9.5 / 32,400
HKP-15C*
43 / 49 45 / 50 21 / 25 25 / 25 81 90 14.25 / 48,600
HKP-20C
43 / 49 45 / 50 43 / 49 45 / 50 106 110 19.0 / 64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protecon Device @ 208 / 240 V
* Revision level that may or may not be designated
C Circuit breaker opon
^ Heat Kit requires three-phase power supply
Note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respecvely to meet new UL1995 requirements.