GPCH3 Spec Sheet
Table Of Contents
2 www.goodmanmfg.com SS-GPCH3
SS-GPCH3 www.goodmanmfg.com 3
Models
GPCH3
2441**
GPCH3
3041**
GPCH3
3641**
GPCH3
4241**
GPCH3
4841**
GPCH3
6041**
Cooling Capacity
Total BTU/h 22,800 28,400 35,600 40,000 46,000 56,000
Sensible BTU/h 18,582 22,550 27,732 30,960 36,616 39,984
SEER2 / EER2 13.4 / 10.6 13.4 / 10.6 13.4 / 10.6 13.4 / 10.6 13.4 / 10.6 13.4 / 10.6
AHRI Numbers
208842384 208842385 208842378 208842379 208842380 208842381
Evaporator Motor
Type ECM ECM ECM ECM ECM ECM
Wheel (D x W) 10 x 8 10 x 8 10 x 8 10 x 8 10 x 8 11 x 8
Cooling CFM
3
875 1,050 1,200 1,300 1,600 1,600
Fan-Only CFM 800 950 1,100 1,200 1,400 1,400
No. of Speeds 5 5 5 5 5 Variable
Horsepower - RPM
½ - 1050 ½ - 1050 ½ - 1050 ½ - 1050 ¾ - 1050 ¾ - 1050
Evaporator Coil
Face Area (
2
) 5.26 5.25 5.25 6.2 6.2 7
Rows Deep 3 3 3 4 4 4
Fins per Inch 14 16 14 14 14 14
Metering Device Type Piston Piston Piston Piston Piston TXV
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"
Refrigerant Charge (oz.)
51 50 57 78 87 103
Condenser Fan
Horsepower - RPM 1/6 - 810 1/6 - 815 ¼ - 830 ¼ - 1075 ¼ - 1075 ¼ - 1075
Fan Diameter 22 22 22 22 22 22
# of Fan Blades
3 3 3 4 4 4
Condenser Coil
Face Area (
2
) 9.2855 12.3 12.3 16 19.5 17
Rows Deep 1 1 1 1 2 2
Fins per Inch
27 26 26 28 28 28
Compressor
Quanty / Type 1 / Rotary 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
Stage
Single Single Single Single Single Two
Electrical Data
Compressor RLA/LRA 8.4/38 13.5/72.5 16.7 / 79 17.9 / 112 19.9 / 109 26.4 / 134
Voltage/Phase (60 Hz) 208-230 / 1 208-230 / 1 208-230 / 1 208-230 / 1 208-230 / 1 208-230 / 1
Indoor Blower FLA 3.8 3.8 3.8 5.4 5.4 5.4
Outdoor Fan FLA 0.95 0.95 1.3 1.4 1.4 1.4
M.C.A.
1
14.4 21.6 24.4 29.2 31.7 35.4
M.O.P.
2
20 35 35 45 50 50
Operating Weight (lbs)
315 315 375 375 375 400
Ship Weight (lbs)
324 324 387 387 387 412
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
³ Factory
Note: Always check the S&R plate for electrical data on the unit being installed.
Product Specifications