GPCH3 Spec Sheet

4 www.goodmanmfg.com SS-GPCH3
SS-GPCH3 www.goodmanmfg.com 5
Expanded Cooling Data — GPCH32441
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71
70
700
MBh 23.0 23.4 24.1 - 22.8 23.2 23.9 - 22.2 22.6 23.3 - 21.2 21.5 22.2 - 19.9 20.2 20.9 - 18.8 19.1 19.8 -
S/T 0.60 0.51 0.37 - 0.60 0.52 0.38 - 0.63 0.55 0.40 - 0.65 0.57 0.42 - 1.00 0.59 0.45 - 1.00 0.65 0.50 -
∆T 18.39 16.75 13.69 - 18.35 16.71 13.65 - 18.58 16.94 13.88 - 18.33 16.69 13.63 - 18.11 16.47 13.41 - 19.14 17.50 14.44 -
kW 1.52 1.52 1.51 - 1.71 1.71 1.70 - 1.92 1.92 1.92 - 2.16 2.16 2.15 - 2.42 2.41 2.41 - 2.72 2.72 2.72 -
Amps 6.03 6.02 6.01 - 6.91 6.90 6.89 - 7.89 7.88 7.87 - 8.96 8.95 8.93 - 10.14 10.14 10.12 - 11.54 11.53 11.52 -
Hi PR 262 263 265 - 303 304 306 - 347 348 350 - 393 395 396 - 444 445 447 - 498 499 501 -
Lo PR 123 124 128 - 130 132 135 - 137 139 142 - 143 144 147 - 148 150 153 - 155 156 160 -
800
MBh 23.3 23.6 24.3 - 23.1 23.4 24.1 - 22.5 22.8 23.5 - 21.4 21.8 22.5 - 20.2 20.5 21.2 - 19.0 19.3 20.0 -
S/T 0.67 0.59 0.45 - 0.68 0.60 0.45 - 0.71 0.62 0.48 - 1.00 0.65 0.50 - 1.00 0.67 0.52 - 1.00 0.72 0.58 -
∆T 17.36 15.72 12.65 - 17.31 15.67 12.61 - 17.54 15.90 12.84 - 17.29 15.65 12.59 - 17.08 15.44 12.37 - 18.10 16.46 13.40 -
kW 1.53 1.53 1.52 - 1.72 1.72 1.72 - 1.93 1.93 1.93 - 2.17 2.17 2.16 - 2.43 2.43 2.42 - 2.73 2.73 2.73 -
Amps 6.08 6.07 6.05 - 6.96 6.95 6.93 - 7.94 7.93 7.92 - 9.00 9.00 8.98 - 10.19 10.18 10.17 - 11.59 11.58 11.56 -
Hi PR 264 265 267 - 305 306 308 - 349 350 352 - 396 397 399 - 446 447 449 - 500 501 503 -
Lo PR 124 126 129 - 132 134 137 - 139 140 143 - 144 146 149 - 150 151 154 - 157 158 161 -
887
MBh 23.5 23.8 24.5 - 23.3 23.6 24.3 - 22.7 23.0 23.7 - 21.6 22.0 22.7 - 20.4 20.7 21.4 - 19.2 19.5 20.2 -
S/T 0.71 0.63 0.48 - 0.72 0.64 0.49 - 0.74 0.66 0.52 - 1.00 0.68 0.54 - 1.00 0.71 0.56 - 1.00 0.76 0.62 -
∆T 16.74 15.10 12.04 - 16.70 15.06 11.99 - 16.93 15.29 12.23 - 16.68 15.04 11.98 - 16.46 14.82 11.76 - 17.49 15.85 12.79 -
kW 1.53 1.53 1.53 - 1.73 1.72 1.72 - 1.94 1.94 1.94 - 2.17 2.17 2.17 - 2.43 2.43 2.43 - 2.74 2.74 2.73 -
Amps 6.10 6.10 6.08 - 6.98 6.98 6.96 - 7.97 7.96 7.95 - 9.03 9.02 9.01 - 10.22 10.21 10.20 - 11.61 11.61 11.59 -
Hi PR 265 266 268 - 307 308 310 - 350 351 353 - 397 398 400 - 447 449 450 - 501 502 504 -
Lo PR 126 127 130 - 133 135 138 - 140 141 144 - 145 147 150 - 151 152 156 - 158 159 162 -
75
700
MBh 23.1 23.4 24.1 25.1 22.9 23.2 23.9 24.9 22.2 22.6 23.3 24.3 21.2 21.5 22.2 23.3 19.9 20.3 21.0 22.0 18.8 19.1 19.8 20.8
S/T 0.73 0.65 0.51 0.4 0.74 0.66 0.51 0.4 1.00 0.69 0.54 0.4 1.00 0.71 0.56 0.4 1.00 0.73 0.59 0.4 1.00 1.00 0.64 0.5
∆T 22.00 20.36 17.30 14.1 21.96 20.32 17.25 14.1 22.19 20.55 17.48 14.3 21.94 20.30 17.24 14.1 21.72 20.08 17.02 13.8 22.75 21.11 18.04 14.9
kW 1.52 1.51 1.51 1.5 1.71 1.71 1.70 1.7 1.92 1.92 1.92 1.9 2.16 2.15 2.15 2.2 2.42 2.41 2.41 2.4 2.72 2.72 2.71 2.7
Amps 6.02 6.02 6.00 6.1 6.90 6.90 6.88 6.9 7.89 7.88 7.86 7.9 8.95 8.94 8.93 9.0 10.14 10.13 10.12 10.2 11.53 11.52 11.51 11.6
Hi PR 262 263 265 269 303 305 306 311 347 348 350 354 394 395 397 401 444 445 447 452 498 499 501 506
Lo PR 123 124 128 133 130 132 135 140 137 139 142 147 143 144 147 153 148 150 153 158 155 156 160 165
800
MBh 23.3 23.6 24.3 25.4 23.1 23.4 24.1 25.2 22.5 22.8 23.5 24.6 21.5 21.8 22.5 23.5 20.2 20.5 21.2 22.3 19.0 19.3 20.0 21.1
S/T 0.81 0.73 0.58 0.4 0.82 0.74 0.59 0.4 1.00 0.76 0.62 0.5 1.00 0.78 0.64 0.5 1.00 0.81 0.66 0.5 1.00 1.00 0.72 0.6
∆T 20.96 19.32 16.26 13.1 20.92 19.28 16.22 13.0 21.15 19.51 16.45 13.3 20.90 19.26 16.20 13.0 20.68 19.04 15.98 12.8 21.71 20.07 17.01 13.8
kW 1.53 1.52 1.52 1.5 1.72 1.72 1.71 1.7 1.93 1.93 1.93 1.9 2.17 2.16 2.16 2.2 2.43 2.42 2.42 2.4 2.73 2.73 2.73 2.7
Amps 6.07 6.06 6.05 6.1 6.95 6.94 6.93 7.0 7.93 7.93 7.91 8.0 9.00 8.99 8.98 9.0 10.19 10.18 10.16 10.2 11.58 11.57 11.56 11.6
Hi PR 264 265 267 272 306 307 309 313 349 350 352 357 396 397 399 403 446 447 449 454 500 501 503 508
Lo PR 125 126 129 134 132 134 137 142 139 140 143 149 144 146 149 154 150 151 154 160 157 158 161 167
887
MBh 23.5 23.8 24.5 25.6 23.3 23.6 24.3 25.4 22.7 23.0 23.7 24.8 21.7 22.0 22.7 23.7 20.4 20.7 21.4 22.5 19.2 19.6 20.2 21.3
S/T 0.85 0.77 0.62 0.5 1.00 0.77 0.63 0.5 1.00 0.80 0.66 0.5 1.00 0.82 0.68 0.5 1.00 0.84 0.70 0.5 1.00 1.00 0.75 0.6
∆T 20.35 18.71 15.65 12.5 20.30 18.66 15.60 12.4 20.53 18.89 15.83 12.7 20.29 18.65 15.58 12.4 20.07 18.43 15.36 12.2 21.09 19.45 16.39 13.2
kW 1.53 1.53 1.53 1.5 1.72 1.72 1.72 1.7 1.94 1.94 1.93 1.9 2.17 2.17 2.17 2.2 2.43 2.43 2.43 2.4 2.74 2.73 2.73 2.7
Amps 6.10 6.09 6.08 6.1 6.98 6.97 6.96 7.0 7.96 7.96 7.94 8.0 9.03 9.02 9.00 9.1 10.21 10.21 10.19 10.3 11.61 11.60 11.59 11.7
Hi PR 265 267 268 273 307 308 310 315 350 352 353 358 397 398 400 405 448 449 451 455 502 503 505 509
Lo PR 126 127 130 136 133 135 138 143 140 141 145 150 145 147 150 155 151 152 156 161 158 159 162 168
IDB = Entering Indoor Dry Bulb Temperature Shaded area reects ACCA (TVA) condions. kW = total system power
High and low pressures are measured at the liquid and sucon access ngs. Amps: Unit amps (comp.+ evaporator + condenser fan motors)