Installation Instructions
12
For unit protection, use a fuse or HACR circuit breaker that is in
excess of the circuit ampacity, but less than or equal to the
maximum overcurrent protection device. DO NOT EXCEED THE
MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through weather-
proof fittings. All exterior power supply and ground wiring must
be in approved weatherproof conduit. Low voltage wiring from
the unit control panel to the thermostat requires coded cable. See below for ground level and rooftop wiring.
CIRCULATING AIR AND FILTERS
A
IRFLOW CONVERSION
Units can easily be converted from horizontal to down-discharge airflow delivery.
In down-discharge or high static installations, the installer should measure the
total external static and review the blower performance charts before perform-
ing the installation. In some installations it will be necessary to change the blower
speed to provide proper air flow.
HORIZONTAL AIR FLOW
Single phase models are shipped without horizontal duct covers. If needed, these
kits may be ordered through Goodman’s Service Parts department.
Down Discharge Applications
Cut insulation around bottom openings and remove panels from the bottom of
the unit, saving the screws holding the panels in place.
NOTE: Single phase models require installation of horizontal duct kit
#20464501PDGK (medium chassis) and #20464502PDGK (large chassis).
DUCTWORK
Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the unit. Ductwork
should be designed in accordance with the recommended methods of Air Conditioning Contractors of America Manual D (Residen-
tial) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation.
A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air
Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
Duct Cover Installation
Typical Electrical Wiring Unit Voltage
Note:Junction box location
shown is optional and is
for illustration purposes only.
JUNCTION BOX