PCBAG127 CONTROL BOARD
DESCRIPTION
The ignition control is designed for use in gas heating/electric
cooling package equipment (rooftop applications) and oper-
ates with a two stage heat and two stage cooling system. It
is a direct spark ignition system that uses a 22,000 volt spark
to ignite the burners. A flame sensor is used to monitor the
flame.
The board has the option of using a single or two stage ther-
mostat. The board also controls the indoor blower and has
an adjustable heat fan off delay.
There is also a fault recall button for recalling the last 5 fault
codes. To recall the fault codes, depress the fault recall but-
ton for at least 2 seconds but not more than 4 seconds. To
clear the fault code memory, depress the fault recall button
for at least 5 seconds.
The following tables list the functions for the connectors
and terminals, the timings, and the fault codes for the
PCBAG127 control board.