Service Instructions APG/GPG 16 SEER 81% AFUE Gas Electric Package Units with R-410A Refrigerant & Accessories This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard / National Standard of Canada Shown Below. ANSI Z21.47•CSA-2.3 Central Furnaces This manual is to be used by qualified, professionally trained HVAC technicians only.
TABLE OF CONTENTS IMPORTANT INFORMATION .......................................... 2 - 3 TROUBLESHOOTING CHARTS ................................ 28 - 29 PRODUCTION IDENTIFICATION ........................................ 4 SERVICING TABLE OF CONTENTS ................................. 30 LIGHTING INSTRUCTIONS ................................................ 5 SERVICING ................................................................. 31 - 57 ACCESSORIES ..................................................
IMPORTANT INFORMATION SAFE REFRIGERANT HANDLING While these items will not cover every conceivable situation, they should serve as a useful guide. WARNING Refrigerants are heavier than air. They can "push out" the oxygen in your lungs or in any enclosed space.To avoid possible difficulty in breathing or death: • Never purge refrigerant into an enclosed room or space. By law, all refrigerants must be reclaimed. • If an indoor leak is suspected, thoroughly ventilate the area before beginning work.
PRODUCT IDENTIFICATION The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information.
LIGHTING INSTRUCTIONS *PG16 ROBINET A GAZ MANUEL, EN POS "ON/MARCHE" GAS INLET ARRIVEE DU GAZ MANUAL GAS LEVER SHOWN IN "ON" POS 5
ACCESSORIES ACCESSORIES Part Number Description LPM-08 Propane Conversion Kit (*PG16) for 2-s tage gas fired 81% AFUE units.
ACCESSORIES ROOF CURBS B S R A C 1 5/8 14 1/2 1 3/8 MODEL A B C PGC101/102/103 46 1/4 39 3/8 14 1/2 RETURN SUPPLY 12 1/2 x 23 15 x 22 1/2 DOWNFLOW FILTER RACK (PGFR101/102/103) 25 1 1/2 3 14 2 26 1/2 Filter Size: 14" x 25" x 2" Measurement in inches. NOTE: PGFR cannot be used with downflow economizers.
ACCESSORIES PGEDJ103 (DOWNFLOW ECONOMIZER) PGED103 A B 16 18 A 14 X 25 FILTER ATTACHMENT 25 B 16 X 20 x 2” FILTER + 16 X 20 MIST ELIMINATOR ECONOMIZER (HORIZONTAL APPLICATIONS) 16 1/8 18 Measurement in inches.
ACCESSORIES MOTORIZED/MANUAL FRESH AIR DAMPERS (HORIZONTAL APPLICATIONS) B 7 5/8 5 3/4 11 7/8 A B A MANUAL MODEL A B PGMDH101 26 1/2 29 3/4 PGMDH102 31 1/2 29 3/4 PGMDH103 30 29 3/4 MOTORIZED MODEL A B PGMDMH101 26 1/2 29 3/4 PGMDMH102 31 1/2 29 3/4 PGMDMH103 30 29 3/4 MOTORIZED/MANUAL FRESH AIR DAMPERS (DOWNFLOW APPLICATIONS) BOTTOM VIEW 12 1/8 6 5 3/4 10 A 11 7/8 1 PGMDD103 B BOTTOM VIEW 12 1/8 10 1 5 3/4 6 A 11 7/8 B PGMDD101/102 MANUAL MODEL A B PGMDD101/102 16 16 PGM
ACCESSORIES SQUARE TO ROUND CONVERTER (DOWNFLOW APPLICATIONS) 12 1/4 14 3/4 C D S 16 ø 22 3/4 16 ø 22 1/4 R A 12 1/4 14 3/4 B 22 3/4 22 1/4 18 ø 18 ø MODEL A B C D RETURN SUPPLY SQRPG101/102 22 3/4 12 1/4 22 1/4 14 3/4 16 16 SQRPG103 22 3/4 12 1/4 22 1/4 14 3/4 18 18 SQUARE TO ROUND CONVERTER (HORIZONTAL APPLICATIONS) B C A 10 MODEL A B C SQRPG101/102 16 16 1/2 16 1/2 SQRPG103 18 18 1/2 18 1/2 Measurements are in inches.
ACCESSORIES GPGHFR101-103 (EXTERNAL HORIZONTAL FILTER RACK) 16” x 25" x 2" FILTER 11
PRODUCT DESIGN Locations and Clearances NOTE: To ensure proper condensate drainage, unit must be installed in a level position. In installations where the unit is installed above ground level and not serviceable from the ground (Example: Roof Top installations) the installer must provide a service platform for the service person with rails or guards in accordance with local codes or ordinances or in their absence with the latest edition of the National Fuel Gas Code ANSI Z223.1.
PRODUCT DESIGN A 3/4" - 14 NPT drain connector is provided for removal of condensate water from the indoor coil. In order to provide proper condensate flow, do not reduce the drain line size. NOTE: Tighten drain to a maximum torque of 10 in-lbs. - These Scroll compressors use "POE" or polyolester oil which is NOT compatible with mineral oilbased lubricants like 3GS. "POE" oil must be used if additional oil is required.
PRODUCT DESIGN During compression, one scroll remains stationary (fixed scroll) while the other form (orbiting scroll) is allowed to orbit (but not rotate) around the first form. All line voltage connections must be made through weather proof fittings. All exterior power supply and ground wiring must be in approved weather proof conduit. Low voltage wiring from the unit control panel to the thermostat requires coded cable. See the following figures for ground level and rooftop wiring.
PRODUCT DESIGN GAS PIPING WARNING TO AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL INJUSRY OR FIRE, USE ONLY COPPER CONDUCTORS All line voltage connections must be made through weather proof fittings. All exterior power supply and ground wiring must be in approved weather proof conduit. Low voltage If it is necessary for the installer to supply additional line voltage wiring to the inside of the package unit, the wiring must comply with all local codes.
PRODUCT DESIGN 8. Connect the unit to the building piping by one of the following methods. a. Rigid metallic pipe and fittings. b. Semi-rigid metallic tubing and metallic fittings. Aluminum alloy tubing shall not be used in exterior locations. c. Listed gas appliance connectors used in accordance with the terms of their listing that are completely in the same room as the equipment.
PRODUCT DESIGN TYPICAL PROPANE PIPING PROPANE GAS PIPING CHARTS 5 to 15 PSIG (20 PSIG Max.) First Stage Regulator 200 PSIG Maximum Sizing Between First and Second Stage Regulator Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10 PSIG Setting. Capacities in 1,000 BTU/HR Continuous 11" W.C. PIPE OR TUBING LENGTH, FEET Second Stage Regulator WARNING NOMINAL PIPE SIZE, SCHEDULE 40 TUBING SIZE, O.D.
SYSTEM OPERATION COOLING HEATING The refrigerant used in the system is R-410A. It is a clear, colorless, non-toxic and non-irritating liquid. R-410A is a 50:50 blend of R-32 and R-125. The boiling point at atmospheric pressure is -62.9°F. The heating cycle is accomplished by using a unique tubular design heat exchanger which provides efficient gas heating on either natural gas or propane gas fuels.
SYSTEM OPERATION IGNITION CONTROL SEQUENCE OF OPERATION A. Heating Operation: Low stage heat B. Heating Operation: High stage heat 1. Thermostat type is set to two-stage. 2. Thermostat “W1” and “W2” inputs initiate high stage heating. 1. Thermostat type is set to two-stage. 2. Thermostat “W1” input initiates low stage heating. 3. 3. Induced draft blower is energized at high speed for the pre-purge period. Pre-purge timer begins after control recognizes pressure switch has closed.
A/GPG16 SYSTEM OPERATION IGNITION CONTROL SEQUENCE OF OPERATION (CONT.) 3. A. Cooling Operation: Low stage cool 1. Thermostat type is set to two-stage. 2. Thermostat “Y1” or thermostat “Y1” and “G” input initiates low stage cooling. 3. IDT/ODT/Pressure/Loss of Charge Switch circuits are checked for closed condition. Cooling operation can proceed only if these circuits are closed. 4. Low stage compressor output is energized. 5. Condenser fan motor is energized at low speed. 6.
SYSTEM OPERATION The following tables list the functions for the connectors and terminals, the timings, and the fault codes for the PCBAG127 control board. PCBAG127 CONTROL BOARD DESCRIPTION The ignition control is designed for use in gas heating/electric cooling package equipment (rooftop applications) and operates with a two stage heat and two stage cooling system. It is a direct spark ignition system that uses a 22,000 volt spark to ignite the burners. A flame sensor is used to monitor the flame.
SYSTEM OPERATION Pin Voltage 1 24VAC Indoor/Outdoor Thermostat (IDT/ODT) Output Function 2 24VAC High Stage Compressor Output 3 24VAC Pressure Switch/Loss of Charge Switch Input 4 24VAC Indoor/Outdoor Thermostat (IDT/ODT) Input 5 24VAC Pressure Switch/Loss of Charge Switch Output 6 24VAC Low Stage Compressor Output Circuit Definitions and Voltage Ratings for the 6-Circuit Connector Circuits Pin Voltage Function 1 24VAC Limit Switch Output 2 24VAC 24VAC Input to Control 3 24VA
SYSTEM OPERATION Period Timing Pre-Purge 15 Seconds Inter-Purge 30 Seconds Post Purge 30 Seconds Trial-for-Ignition (TFI) 7 Seconds Flame Stabilization Period 10 Seconds Flame Failure Response Time 2 Seconds within Flame Stabilization Period 2 Seconds or Per ANSI Z21.
SYSTEM OPERATION Typical Package Cooling or Package Gas Indoor Coil Outdoor Coil Thermostatic Expansion Valve Restrictor Orifice Assy Either a thermostatic expansion valve or restrictor orifice assembly may be used depending on model, refer to the parts catalog for the model being serviced. Restrictor Orifice Assembly in Cooling Operation In the cooling mode the orifice is pushed into its seat forcing refrigerant to flow through the metered hole in the center of the orifice.
SCHEDULED MAINTENANCE Package gas units require regularly scheduled maintenance to preserve high performance standards, prolong the service life of the equipment, and lessen the chances of costly failure. In many instances the owner may be able to perform some of the maintenance; however, the advantage of a service contract, which places all maintenance in the hands of a trained serviceman, should be pointed out to the owner. 10. Start the system and run a Heating Performance Test.
SCHEDULED MAINTENANCE 1 0 9 2 9 8 3 1 1 8 2 5 1 Million 6 6 5 4 8 5 6 10 Thousand 2 3 6 5 4 1 Thousand CUBIC FEET One Foot Foot 1 8 7 7 4 100 Thousand Quarter 9 9 2 3 3 7 7 4 0 GAS RATE -- CUBIC FEET PER HOUR 26 Seconds for One Revolution 1/4 cu/ft 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 90 82 75 69 64 60 56 53 50 47 45 43 41 39 37 36 34 33 32 31 30 -28 -26 -- Size of Test Dial 1/2 1 2 cu/ft cu/ft cu/ft 5 cu/ft Seconds for
SCHEDULED MAINTENANCE Example: It takes forty-five (45) seconds on the gas meter for the hand on the cubic foot dial to make one complete revolution, with all appliances off, except the unit. Using the gas rate chart, observe the forty-five (45) seconds, locate and read across to the one (1) cubic foot dial column. There you will find the number 80, which shows that eighty (80) cubic feet of gas will be consumed in one (1) hour.
SERVICING COOLING ANALYSIS CHART Pow er Failure Blow n Fuse Loose Connection Shorted or Broken Wires Open Overload Faulty Thermostat Faulty Transformer Shorted or Open Capacitor Shorted or Grounded Compressor Compressor Stuck Faulty Compressor Contactor 2nd Stage Compressor Not Energized Faulty Ignition Control Open Control Circuit Low Voltage Faulty Evap.
SERVICING GAS HEATING ANALYSIS CHART Pow er Failure Blow n Fus e Loos e Connection Shorted or Broken Wires No Low V oltage Faulty Thermostat Faulty Transf ormer Poor or High Resistance Ground Improper Heat A ntic ipator Setting Improper Thermostat Loc ation Faulty Limit or Roll Out Sw itc h Faulty Flame Sensor Faulty Ignition Control Gas V alve or Gas Supply Shut Of f Faulty Induced Draf t Blow er Dirty Flame Sensor, Low uA Flame Sensor not in Flame, Low uA Faulty Gas V alv e No High Stage Heat (2 Stage On
SERVICING Table of Contents S-1 CHECKING VOLTAGE .................................... 31 S-103 CHARGING ...................................................... 41 S-2 CHECKING WIRING ....................................... 32 S-104 CHECKING COMPRESSOR EFFICIENCY ... 41 S-3 CHECKING THERMOSTAT, WIRING, S-105B THERMOSTATIC EXPANSION VALVE ........... 41 AND ANTICIPATOR ......................................... 32 S-106 OVERFEEDING ..............................................
SERVICING S-1 CHECKING VOLTAGE HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Three phase units require a balanced 3 phase power supply to operate. If the percentage of voltage imbalance exceeds 3% the unit must not be operated until the voltage condition is corrected. % Voltage = Imbalance Max.
SERVICING If the imbalance had not changed then the problem would lie within the equipment. Check for current leakage, shorted motors, etc. S-2 CHECKING WIRING WARNING Line Voltage now present. 1. Set fan selector switch at thermostat to "ON" position. 2. With voltmeter, check for 24 volts at wires C and G. HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. 1.
SERVICING S-4 CHECKING TRANSFORMER AND CONTROL CIRCUIT NOTE: Most single phase contactors break only one side of the line (L1), leaving 115 volts to ground present at most internal components. 1. Remove the leads from the holding coil. HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
SERVICING THREE PHASE 4. Start the system and place a piece of cardboard in front of the condenser coil, raising the condensing pressure. Using a voltmeter, test across terminals. A. L1-L2, L1-L3, and L2-L3 - If voltage is present, proceed to B. If voltage is not present, check breaker or fuses on main power supply.. B. T1-T2, T1-T3, and T2-T3 - If voltage readings are not the same as in "A", replace contactor. T3 T2 T1 CC VOLT/OHM METER L3 L2 5.
SERVICING Your unit comes with a 180-second anti-short cycle to prevent the compressor from starting and running backwards. MODELS EQUIPPED WITH A HARD START DEVICE A start capacitor is wired in parallel with the run capacitor to increase the starting torque. The start capacitor is of the electrolytic type, rather than metallized polypropylene as used in the run capacitor.
SERVICING WARNING Discharge capacitor through a 20 to 30 OHM resistor before handling. Capacitance (MFD) = 2650 X Amperage Voltage 4. Using an ohmmeter, check the motor windings for continuity to ground (pins to motor shell). If the ohmmeter indicates continuity to ground, the motor is defective and must be replaced. 5. Using an ohmmeter, check the windings for continuity (pin to pin). If no continuity is indicated, the thermal limit (over load) device may be open. Allow motor to cool and retest.
SERVICING High Voltage Connections 3/16" C L G N Ignition cannot occur at the venting terminal without the presence of contaminant air, and cannot occur externally from the venting terminal without the presence of an external ignition source. Therefore, proper evacuation of a hermetic system is essential at the time of manufacture and during servicing.
SERVICING NOTE: If an open compressor is indicated, allow ample time for the internal overload to reset before replacing compressor. S-17B GROUND TEST If fuse, circuit breaker, ground fault protective device, etc., has tripped, this is a strong indication that an electrical problem exists and must be found and corrected. The circuit protective device rating must be checked, and its maximum rating should coincide with that marked on the equipment nameplate.
SERVICING 4. Next check the molded plug. A. B. C. Voltage check: Apply control voltage to the plug wires (18 to 28 volt ac). The measured dc voltage at the female connectors in the plug should be around 15 to 27 vdc. Resistance check: Measure the resistance from the end of one molded plug lead to either of the two female connectors in the plug. One of the connectors should read close to zero ohms while the other should read infinity. Repeat with other wire.
SERVICING S-101 LEAK TESTING (NITROGEN OR NITROGEN-TRACED) WARNING To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gases for leak testing of a refrigeration system. 1. Connect the vacuum pump, vacuum tight manifold set with high vacuum hoses, thermocouple vacuum gauge and charging cylinder as shown. 2. Start the vacuum pump and open the shut off valve to the high vacuum gauge manifold only.
SERVICING S-103 CHARGING WARNING REFRIGERANT UNDER PRESSURE! * Do not overcharge system with refrigerant. * Do not operate unit in a vacuum or at negative pressure. Failure to follow proper procedures may cause property damage, personal injury or death. NOTE: Even though the compressor section of a Scroll compressor is more tolerant of liquid refrigerant, continued floodback or flooded start conditions may wash oil from the bearing surfaces causing premature bearing failure.
SERVICING Pressure vs. Temperature Chart R-410A PSIG 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 °F -37.7 -34.7 -32.0 -29.4 -36.9 -24.5 -22.2 -20.0 -17.9 -15.8 -13.8 -11.9 -10.1 -8.3 -6.5 -4.5 -3.2 -1.6 0.0 1.5 3.0 4.5 5.9 7.3 8.6 10.0 11.3 12.6 13.8 15.1 16.3 17.5 18.7 19.8 21.0 22.1 23.2 24.3 25.4 26.4 27.4 28.5 29.5 30.5 31.2 32.2 33.2 34.1 35.1 35.5 36.9 PSIG 114.0 116.0 118.0 120.
SERVICING S-106 OVERFEEDING 3. Refer to the superheat table provided for proper system superheat. Add charge to lower superheat or recover charge to raise superheat. Overfeeding by the expansion valve results in high suction pressure, cold suction line, and possible liquid slugging of the compressor. Superheat Formula = Suct. Line Temp. - Sat. Suct. Temp. If these symptoms are observed: EXAMPLE: 1. Check for an overcharged unit by referring to the cooling performance charts in the servicing section.
SERVICING REQUIRED LIQUID LINE TEMPERATURE LIQUID PRESSURE AT SERVICE VALVE (PSIG) 189 195 202 208 215 222 229 236 243 251 259 266 274 283 291 299 308 317 326 335 345 354 364 374 384 395 406 416 427 439 450 462 474 486 499 511 44 8 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 REQUIRED SUBCOOLING TEMPERATURE (°F) 10 12 14 16 56 54 52 50 58 56 54 52 60 58 56 54 62 60 58 56 64 62 60 58 66 64 62 60 68 66 64 62 70 68 66 64 72 70 68
SERVICING COOLING OPERATION NOTE: Mechanical cooling cannot be reliably provided at ambient temperatures below 50° F. 1. Turn on the electrical power supply to the unit. 2. Place the room thermostat selector switch in the COOL position (or AUTO if available, and if automatic changeover from cooling to heating is desired). 3. Set the room thermostat to the desired temperature. The TXV should NOT be adjusted at light load conditions 55º to 60ºF, under such conditions only the subcooling can be evaluated.
SERVICING 1. Attach a gauge manifold to the suction and liquid line dill valves. 2. Start the system and allow the pressures to stabilize. 3. Stop the system and check the time it takes for the high and low pressure gauge readings to equalize. If it takes more than seven (7) minutes to equalize, the restrictor device is inoperative. Replace, install a liquid line drier, evacuate and recharge.
SERVICING NOTE: At least twelve (12) inches of the suction line immediately out of the compressor stub must be discarded due to burned residue and contaminates. 1. Remove compressor discharge line strainer. 2. Remove the liquid line drier and expansion valve. INCLINED MANOMETER SUPPLY 3 Purge all remaining components with dry nitrogen or carbon dioxide until clean. 4. Install new components including liquid line drier. 5. Braze all joints, leak test, evacuate, and recharge system. RETURN 6.
SERVICING If the temperature within the furnace should exceed this setting, the control will open, de-energizing the ignition control which in turn will open the electrical circuit to the gas valve. The control will automatically reset when the temperature within the combustion chamber is sufficiently lowered. SUPPLY RETURN TSUPPLY HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present.
SERVICING AUX. LIMIT S-302 CHECKING FLAME ROLLOUT SWITCH APG/GPG units are equipped with a temperature-activated manual reset control. This control is mounted to the manifold assembly and is wired in series with the auxiliary limit and gas valve. The control is designed to open should a flame roll out occur. An over firing condition or flame impingement on the heat shield can also cause the control to open.
SERVICING When the limit switch re-closes, the induced draft motor runs through its post purge and the indoor blower goes through the heat off delay. If a call for heat exists when the limit switch re-closes, the control goes through a pre-purge period and then makes an ignition attempt. The indoor blower remains on (for the delay off time) during the re-ignition attempt. 1. If no voltage is measured on either side of control it indicates ignition control or wiring to control problem. 2.
SERVICING Gas Valve On/Off Switch S-305 CHECKING MAIN BURNERS Inlet Pressure Tap Inlet Outlet The main burners are used to provide complete combustion of various fuels in a limited space, and transfer this heat of the burning process to the heat exchanger. Proper ignition, combustion, and extinction are primarily due to burner design, orifice sizing, gas pressure, primary and secondary air, vent and proper seating of burners.
SERVICING DENT OR BURR GAS STREAM B Low Pressure Adjust Gas Valve Inlet Pressure On/Off Tap Switch Open to Atmosphere Manometer Hose A dent or burr will cause severe deflection of gas stream. Open to Atmosphere Inlet Outlet High Pressure Adjust The length of Dimension "A" determines the angle of Gas Stream Defraction, "B".
SERVICING MEASURING INLET AND MANIFOLD GAS PRESSURE With Power ON: 3. Carry over (lighter tube or cross lighter) obstructed clean. WARNING 4. Main burner orifice(s) deformed, or out of alignment to burner - replace. Line Voltage now present. 3. Put furnace into heating cycle and turn on all other gas consuming appliances. For NATURAL GAS: a. Inlet pressure should be a nominal 7" w.c. b. (2 stage heat models only) Manifold pressure on low stage should be 2.0” w.c. ± .3"w.c. c.
SERVICING S-311 HIGH ALTITUDE APPLICATION HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. 1. Remove wires from the electrical terminals. 2. Using a VOM check from Common to NO (Normally Open) - should read open. If switch reads as noted proceed to Step 3, otherwise replace control. 3.
SERVICING High INPUT/BURNER 20,000 BTUH NAT/18,000 BTUH/L.P. ELEVATION ABOVE SEA-LEVEL (FEET) Altitude Kit U.S. BURNER O RIFICE CANADA BURNER ORIFICE HA-03 2000 3000 4000 46/1.25M M 46/1.25M M 47/56 -- -- 4500 5000 6000 7000 8000 -- 48/56 48/57 49/57 49/57 48/56 -- -- -- -- S-313 TESTING IGNITION CONTROL MODULE NOTE: Failure to earth ground the unit, or a high resistance connection in the ground may cause the control to lockout due to failure to flame sense.
SERVICING Cooling Mode Indoor thermostat calling for cool. 1. Check for 230 volts from L1 terminal of control module to L2. No voltage - check wire connections, continuity, etc. LED Flashes/Status System Condition No voltage - check 3 amp automotive type fuse on control board. A blown fuse could indicate a short in the 24 volt circuit.
SERVICING 7. The nominal microamp reading is 4 microamps. Flame Sensor 8. If the microamp current is less than 0.5 microamp the control will lockout and flash a code of 1 flash after attempting to reestablish flame sense. 9. If the microamp reading is less than the minimum specified, check for high resistance wiring connections, the distance (3/16") between the sensor and burner, flame sensor connections, dirty flame sensor or poor grounding. 10.
AIRFLOW DATA APG16 APG1624060M41** - Rise Range: 35° - 65° Tap Low Cool High Cool Low Heat APG1630080M41** - Rise Range: 35° - 65° High Heat CFM Rise CFM Rise Tap Low Cool High Cool Low Heat High Heat CFM Rise CFM Rise A- 505 675 540 63 720 63 A- 545 810 720 63 960 63 A 565 750 600 56 800 56 A 605 900 800 56 1065 56 A+ 620 825 660 51 880 51 A+ 665 990 880 51 1170 51 B- 540 720 610 55 810 56 B- 605 900 810 56 1075 56 B 600 800 675
AIRFLOW DATA GPG16 GPG1624060M41** - Rise Range: 35° - 65° T1 LOW STAGE HEATING T2 HIGH STAGE HEATING T3 LOW STAGE T4 HIGH STAGE SPEED SPEED COOLING SPEED COOLING SPEED E.S.P. T5 COOLING SPEED CFM WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS 0.1 625 53 54 855 107 53 625 51 850 104 1,090 197 0.2 585 61 58 815 114 55 590 60 810 116 1,055 201 0.3 550 70 61 785 125 57 555 68 775 122 1,020 207 0.
AIRFLOW DATA GPG16 GPG1642100M41** - Rise Range: 35° - 65° T1 LOW STAGE HEATING T2 HIGH STAGE HEATING T3 LOW STAGE T4 HIGH STAGE SPEED SPEED COOLING SPEED COOLING SPEED E.S.P. T5 COOLING SPEED CFM WATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS 0.1 1,100 172 51 1,420 325 53 1,075 162 1,335 274 1,620 484 0.2 1,040 181 54 1,360 331 55 1,015 172 1,290 288 1,575 489 0.3 985 185 57 1,310 342 57 960 185 1,230 297 1,530 497 0.
ACCESSORIES WIRING DIAGRAM ECONOMIZER HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Economizer wiring for PGEDJ and HZECNJPCGHM* Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
WIRING DIAGRAM APG16 HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
GPG16 WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.