GPGM3 Spec Sheet
4 www.goodmanmfg.com SS-GPGM3
SS-GPGM3 www.goodmanmfg.com 5
GPGM3
3608041
GPGM3
4206041
GPGM3
4208041
GPGM3
4806041
GPGM3
4808041
GPGM3
4810041
Total BTU/h 34,200 40,000 40,000 46,250 46,250 46,250
Sensible BTU/h 28,160 30,980 30,980 36,190 36,190 36,190
SEER2 / EER2 13.4 / 10.6 13.4 / 10.6 13.4 / 10.6 13.4 / 10.6 13.4 / 10.6 13.4 / 10.6
Decibels 78 78 78 80 80 80
AHRI Reference #s 209319532 209319538 209319538 209319544 209319544 209319544
Input BTU/h 80,000 60,000 80,000 60,000 80,000 100,000
Output BTU/h 64,800 48,600 64,800 48,600 64,800 81,000
AFUE 81 81 81 81 81 81
Temperature Rise Range 30 - 60 30 - 60 30 - 60 30 - 60 30 - 60 35 - 65
No. of Burners 4 3 4 3 4 5
Type ECM ECM ECM ECM ECM ECM
Wheel (D x W) 10” x 9” 11” x 10” 11” x 10” 11” x 10” 11” x 10” 11” x 10”
Indoor Nominal CFM 1,200 1,300 1,300 1,525 1,525 1,525
No. of Speeds 5 5 5 5 5 5
Horsepower 1/2 3/4 3/4 3/4 3/4 3/4
Face Area (²) 4.35 5.68 5.68 5.68 5.68 5.68
Rows Deep/Fins per Inch 4/14 4/14 4/14 4/14 4/14 4/14
Piston Size (Cooling) 0.068 0.072 0.072 0.076 0.076 0.076
Drain Size (NPT) ¾” ¾” ¾” ¾” ¾” ¾”
Refrigerant Charge (oz.) 92 103 103 107 107 107
Horsepower - RPM 1/4 - 1,075 1/4 - 1,075 1/4 - 1,075 1/3 - 1,120 1/3 - 1,120 1/3 - 1,120
Diameter / # of Blades 22” / 3 22” / 3 22” / 3 22” / 3 22” / 3 22” / 3
Outdoor Nominal CFM 2,250 2,850 2,850 3,300 3,300 3,300
Face Area (²) 11.13 15.36 15.36 8.81 8.81 8.81
Rows Deep/Fins per Inch 2/27 1/24 1/24 2/27 2/27 2/27
Quanty / Type 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll
Stage Single Single Single Single Single Single
Compressor RLA/LRA 14.1 / 77.0 17.9 / 112.0 17.9 / 112.0 19.9 / 109.0 19.9 / 109.0 19.9 / 109.0
Voltage-Phase (Frequency 60Hz) 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1 208/230-1
Indoor Blower FLA 3.8 5.4 5.4 5.4 5.4 5.4
Outdoor Fan FLA/LRA 1.4 / 3.2 1.4/ 3.2 1.4/ 3.2 1.4 / 3.2 1.4 / 3.2 1.4 / 3.2
Min. Circuit Ampacity 22.8 29.2 29.2 32.3 32.3 32.3
Max. Overcurrent Protecon 35 amps 45 amps 45 amps 50 amps 50 amps 50 amps
458 / 480 493 / 515 496 / 520 518 / 540 523 / 545 528 / 550
¹ Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
² Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
Always check the S&R plate for electrical data on the unit being installed.