INSTALLATION & OPERATING INSTRUCTIONS for A/GPG 13.4 SEER2 “M” SERIES WITH R-410A SINGLE PACKAGE GAS-ELECTRIC HEATING & COOLING UNIT Affix this manual and Users Information Manual adjacent to the unit. This Forced Air Central Unit Design Complies With Requirements Embodied In The American National Standard / National Standard of Canada Shown Below. ANSI Z21.47•CSA-2.3 Central Furnaces. RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
TABLE OF CONTENTS REPLACEMENT PARTS..................................................2 Ordering Parts...........................................................2 SAFETY INSTRUCTIONS...............................................2 To the Installer..........................................................2 GENERAL INFORMATION..............................................5 Transportation Damage............................................5 UNIT LOCATION...........................................................
WARNING WARNING Should overheating occur or the gas supply fail to shut off, turn off the manual gas shutoff valve external to the furnace before turning off the electrical supply. If the information in these instructions is not followed exactly, a fire or explosions may result causing property damage, personal injury or loss of life. -Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
AVERTISSEMENT WARNING RISQUE D’INTOXICATION AU MONOXYDE DE CARBONE FIRE OR EXPLOSION HAZARD Si les étapes décrites ci-dessous ne sont pas suivies pour chacun des appareils raccordés au système de ventilation au moment de sa mise en marche, cela peut entraîner une intoxication au monoxyde de carbone ou la mort. Failure to follow the safety warnings exactly could result in serious injury, death or property damage. Never test for gas leaks with an open flame.
RISQUE D'EMPOISONNEMENT AU MONOXYDE DE CARBONE Advertencia especial para la instalación de calentadores ó manejadoras de aire en áreas cerradas como estacionamientos ó cuartos de servicio. Las emisiones de monóxido de carbono pueden circular a través del aparato cuando se opera en cualquier modo. CO can cause serious illness including permanent brain damage or death.
UNIT LOCATION • • WARNING To prevent possible equipment damage, property damage, personal injury or death, the following bullets points must be observed when installing the unit. • All Installations: • For proper flame pattern within the heat exchanger and proper condensate drainage, the unit must be mounted level. • The flue outlet hood must be at least 12 inches from any opening through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet.
The unit may be installed directly on wood floors or on Class A, Class B, or Class C roof covering material. To avoid possible personal injury, a safe, flat surface for service personnel should be provided. Important: If using bottom discharge with roof curb, ductwork should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in roof curb installation instructions.
The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. Conversion to LP gas is permitted with the use of the factory authorized conversion kit LPM-07, for use with single stage models, or LPM08, for use with two-stage models. See table below. The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available.
WARNING To avoid property damage or personal injury, BE SURE THERE IS NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING. PROPANE GAS INSTALLATIONS WARNING To avoid property damage, personal injury or death due to fire or explosion caused by a propane gas leak, install a gas detecting warning device. Since rust can reduce the level or odorant in propane gas, a gas detecting warning device is the only reliable way to detect a propane gas leak.
ELECTRICAL WIRING See below for typical propane gas piping. 5 to 15 PSIG (20 PSIG Max.) First Stage Regulator Thermostat Location Mount the thermostat approximately five feet above the floor, in an area that has an inside, vibration-free wall and has good air circulation. Continuous 11" W.C. 200 PSIG Maximum Movement of air must not be obstructed by furniture, door, draperies, etc.
Y2 C Y1 W1 W2 ( Thermostat Two-Stage Heating with Two-Stage Cooling ( R G R C W1W2 G Y1 Y2 Furnace Integrated Control Module Two-Stage Heating with Two-Stage Cooling Thermostat Diagram Single Stage Thermostat - Two-Stage Models To use a single stage thermostat, move jumper located to the left of the terminal strip labeled “Stage Delay” from NONE to “5” or “10” minutes. This selection will cause the control to run on low stage for the selected time (5 or 10 minutes) then shift to HIGH STAGE.
NOTE: A dedicated ground wire must be run from the unit to the electrical panel. DO NOT use gas piping, or conduit as an electrical ground. Low voltage wiring from the unit control panel to the thermostat requires coded cable. See below for ground level and rooftop wiring. NOTE: The unit transformer is factory connected for 240V operation. If the unit is to operate on 208V, reconnect the transformer primary lead as shown on the unit wiring diagram.
Filters Installation - Combustion Air Intake Hood 1. Locate the second hood. 2. Using the three screws provided, attach the hood (with the opening facing down) to the heat exchanger access door. CAUTION To prevent property damage due to fire and loss equipment efficiency or equipment damage due to dust and lint build up on internal parts, never operate unit without an air filter installed in the return air system.
Two-Stage Models: The fan runs at low cool speed for the off delay period. This allows additional cooling from the indoor coil to be transferred to the conditioned space. Then, the indoor fan stops. 3. The spark igniter and gas valve energizes for 7 seconds. NOTE: The igniter produces a very intense electrical spark that ignites the gas. 4. Main burners light and control detects presence of flame. 5. The 30-second HEAT FAN ON delay time begins after the main burners light. 6.
9. Replace the heat exchanger door on the side of the unit. 10. Open the manual gas valve external to the unit. 11. Turn on the electrical power supply to the unit. 12. Set the thermostat to desired setting. Rollout Protection Gas Supply And Manifold Check Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate. NOTE: Use adapter kit #0151K00000S to measure gas pressure on White-Rodgers 36J22 and 36G54 gas valves.
The line pressure supplied to the gas valve must be within the range specified in the Inlet Gas Supply Pressure table. The supply pressure can be measured at the gas valve inlet pressure tap or at a hose fitting installed in the gas piping drip leg. The supply pressure must be measured with the unit OFF. To measure inlet pressure, use the following procedure. 8. Measure the gas supply pressure with burners firing. Adjust supply pressure using the Inlet Gas Supply Pressure table shown below.
WARNING HIGH VOLTAGE Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. . This valve is shipped from the factory with the regulator preset (see control label). Mode Consult the appliance rating plate to ensure burner manifold pressure is as specified. If another outlet pressure is required, follow these steps. 1.
NOTE: Air temperature rise is the temperature difference between supply and return air. 2. With the unit operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered to the unit. 3. INPUT=GAS HTG VALUE x 3600 / SEC.
Blower Speed Adjustments Refer to the wiring diagram in the appendix to verify speed tap settings. LOCOOL U6 HICOOL U7 LOHEAT U3 All models are equipped with EEM motors. EEM motors are constant torque motors with very low power consumption. This motor is energized by 24V. Adjust the CFM for the unit by changing the 24V low voltage leads to the speed terminal block on the motor.
Refrigerant Charge Check After completing airflow measurements and adjustments the unit’s refrigerant charge must be checked. The unit comes factory charged, but this charge is based on 325 CFM per ton and minimum ESP per AHRI test conditions (generally between .15 -.28 ESP). When air quantity or ESP is different than above, the refrigerant charge must be adjusted to the proper amount. All package units with fixed orifice devices are charged using the super heat method at the compressor suction line.
External Lockout An external lockout occurs if the integrated ignition control determines that a measurable combustion cannot be established within three (3) consecutive ignition attempts. If flame is not established within the seven (7) second trial for ignition, the gas valve is de-energized, 15 second inter-purge cycle is completed, and ignition is reattempted. The control will repeat this routine three times if a measurable combustion is not established.
Rollout Limit If the burner flames are not properly drawn into the heat exchanger, the flame rollout protection device will open. Possible causes are restricted or blocked flue passages, blocked or cracked heat exchanger, a failed induced draft blower, or insufficient combustion air. The rollout protection device is a manual reset limit located on the burner bracket. The cause of the flame rollout must be determined and corrected before resetting the limit.
MAINTENANCE Flame Sensor (Qualified Servicer Only) A drop in the flame current can be caused by a nearly invisible coating on the flame sensor. This coating, created by the fuel or combustion air supply, can be removed by carefully cleaning the flame sensor with steel wool. NOTE: After cleaning, the microamp signal should be stable and in the range of 4 - 6 microamps DC. WARNING HIGH VOLTAGE Disconnect all power before servicing or installing this unit. Multiple power sources may be present.
CAUTION Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Check the burner flames for: 1. Good adjustment 2. Stable, soft and blue 3. Not curling, floating, or lifting off. CAUTION Always verify proper operation after servicing. Burner Flame For further information on the yearly inspection, consult the User Manual. It is recommended that a qualified servicer inspect and service the unit at least once each year.
BLOWER PERFORMANCE DATA A/GPGM32404041 - Rise Range: 25° - 55° E.S.P. 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 T1 HEATING SPEED CFM 695 650 605 565 480 415 365 320 WATTS 62 71 77 89 99 106 110 119 RISE 44 47 51 54 X X X X T2 HEATING SPEED CFM 820 785 745 700 665 575 510 455 WATTS 93 100 108 117 127 138 146 155 RISE 37 39 41 44 46 53 X X T3 HEATING SPEED CFM 1,050 1,010 970 935 890 850 815 755 WATTS 167 180 186 192 203 208 216 222 RISE 29 30 32 33 35 36 38 41 A/GPGM32406041 - Rise Range: 30° - 60° E.S.P. 0.
BLOWER PERFORMANCE DATA A/GPGM33604041** - Rise Range: 25° - 55° E.S.P. 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.
BLOWER PERFORMANCE DATA A/GPGM34806041 - Rise Range: 30° - 60° E.S.P. 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.
BLOWER PERFORMANCE DATA E.S.P. 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 E.S.P. 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 E.S.P. 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.
IGNITION CONTROL DIAGNOSTIC INDICATOR CHART (SINGLE STAGE MODELS ONLY) Red Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual Off 1 Flash 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes Internal Control Failure External Lockout Pressure Switch Stuck Open Pressure Switch Stuck Closed Thermal Protection Device Open Flame Detected with Gas Valve Closed Short Cycle Compressor Delay (Cooling Only) HEATING TIMING CHART Circulator Blower 100 % OFF Gas Valve
IGNITION CONTROL DIAGNOSTIC INDICATOR CHART (TWO-STAGE MODELS ONLY) Red Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual Off 1 Flash 2 Flashes 3 Flashes 4 Flashes 5 Flashes 6 Flashes 7 Flashes 8 Flashes 9 Flashes Amber Light Signal Internal Control Failure External Lockout Pressure Switch Stuck Open Pressure Switch Stuck Closed Thermal Protection Device Open Flame Detected with Gas Valve Closed Short Cycle Compressor Delay (Cooling Only) Limit
APPENDIX UNIT DIMENSIONS Model 47 A/GPGM324***41** A/GPGM330***41** A/GPGM336***41** A/GPGM342***41** A/GPGM348***41** A/GPGM361***41** 51 W 47 47 47 47 47 47 Unit Dimensions (Inches) Height D A B 51 32 34 1/2 51 32 34 1/2 51 32 34 1/2 51 32 34 1/2 51 40 42 1/2 51 40 43 1/2 Chassis Size Medium Medium Medium Medium Large Large POWER WIRE ENTRANCE 1.375 A W 4.125 2.125 B 5.5 W 6.5 H 2.5 RETURN H 4.75 CONDENSATE DRAIN CONNECTION 3/4" NPT FEMALE SUPPLY 3 16.
A/GPGM3 [24/30/36] ***41 WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
A/GPGM3 [24/30/36] ***41 WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
A/GPGM3[42/48]***41 WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
A/GPGM3[42/48]***41 WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
A/GPGM361***41 WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
A/GPGM361***41 WIRING DIAGRAM HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PACKAGE UNITS - DUAL FUEL & GAS HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS We strongly recommend a bi-annual maintenance checkup be performed by a qualified service agency before the heating and cooling seasons begin. Condenser, Evaporator and Induced Draft Motors The bearings on the air circulating blower motor, condenser motor and the combustion fan motor are permanently lubricated and require no further lubrication. WARNING HIGH VOLTAGE Disconnect all power before servicing or installing this unit.
START-UP CHECKLIST Residential Package - (Indoor Section) Model Number Serial Number ELECTRICAL Line Voltage (Measure L1 and L2 Voltage) Secondary Voltage (Measure Transformer Output Voltage) Blower Amps Heat Strip 1 - Amps Heat Strip 2 - Amps BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure Supply Air Static Pressure Total External Static Pressure (Ignoring +/- from the reading above, add total here) TEMPERATURES Return Air Temperature (Dry bulb / Wet bulb) Cooling Supply Air Temperature (Dry b
CUSTOMER FEEDBACK We are very interested in all product comments. Please fill out the feedback form on one of the following links: Goodman® Brand Products: (http://www.goodmanmfg.com/about/contact-us). Amana® Brand Products: (http://www.amana-hac.com/about-us/contact-us). You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page. GOODMAN® BRAND AMANA® BRAND GOODMAN® BRAND AMANA® BRAND PRODUCT REGISTRATION Thank you for your recent purchase.