5 Ton Models: GPGM560***41A
Down Flow Horizontal Flow
Speed
Tap
Torque
%
Torque
oz-ft
External
Static
Pressure
(ESP), in
w.c.
SCFM RPM BHP
Speed
Tap
Torque
%
Torque
oz-ft
External
Static
Pressure
(ESP), in
w.c.
SCFM RPM BHP
T1 25 20
0.2 983 570 0.14
T1 25 20
0.2 1003 606 0.14
0.4 833 659 0.16 0.4 850 701 0.17
0.6 703 739 0.18 0.6 718 785 0.19
0.8 574 808 0.19 0.8 586 858 0.20
T2 32 25.9
0.2 1175 640 0.20
T2 32 25.9
0.2 1229 617 0.19
0.4 1057 714 0.22 0.4 1105 699 0.22
0.6 902 801 0.25 0.6 945 795 0.24
0.8 790 874 0.27 0.8 844 861 0.27
T3 78 62.4
0.2 1963 883 0.66
T3 78 62.4
0.2 2032 853 0.63
0.4 1858 939 0.70 0.4 1941 908 0.67
0.6 1760 990 0.74 0.6 1850 966 0.72
0.8 1668 1038 0.77 0.8 1757 1018 0.76
T4 78 62.4
0.2 1963 883 0.66
T4 78 62.4
0.2 2032 853 0.63
0.4 1858 939 0.70 0.4 1941 908 0.67
0.6 1760 990 0.74 0.6 1850 966 0.72
0.8 1668 1038 0.77 0.8 1757 1018 0.76
T5 100 80
0.2 2369 2196 2.09
T5 100 80
0.2 2323 929 0.88
0.4 2248 987 0.94 0.4 2245 978 0.93
0.6 2144 1024 0.97 0.6 2161 1028 0.98
0.8 2054 1070 1.02 0.8 2080 1079 1.03
*Shaded area indicats air ow below 1500 SCFM (300 SCFM/ton) that is not
recommended for High Stage cooling or heang.