GPGM5 Spec Sheet

36 www.goodmanmfg.com SS-GPGM5
SS-GPGM5 www.goodmanmfg.com 37
A
B
C
D
CG
SUPPLY
RETURN
EVAPORATOR COIL
CONDENSER
COIL
COMPRESSOR
Y
X
Compressor
Return
Evaporator Coil
Supply
Condenser
Coil
Model X (In) Y (In)
Shipping
Weight
(Lbs)
Operating
Weight
(Lbs)
Corner Weights (Lbs.)
A B C D
GPGM560***41** 46.4 28.1 655 629 186 204 65 174



Maintain an adequate clearance around the unit for safety,
service, maintenance, and proper unit operaon. Leave a total
clearance of 75” on the main control panel side of the unit
for possible removal of fan sha, coil, electric heat, and gas
furnace. Leave a clearance of 48” on all other sides of the
unit for possible compressor removal or service access,
and to ensure proper venlaon and condenser
airow. Do not install the unit beneath any
obstrucon. Install the unit away
from all building exhausts to
inhibit ingeson of exhaust air
into the units fresh-air intake.