Installation Manual

13
GPC/GPH14**H41 BLOWER PERFORMANCE
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM 934 759 755 638 581 489 - -
WATTS957776738390 - -
CFM 990 837 801 744 696 652 601 -
WATTS 107 94 105 110 119 133 142 -
CFM 1061 989 947 925 876 - - -
WATTS 126 134 146 158 169 - - -
CFM 1022 929 894 829 797 748 695 643
WATTS 116 114 126 134 144 156 168 173
CFM 1103 1063 1012 962 937 - - -
WATTS 142 154 165 173 185 - - -
CFM 1285124012021163112410761046 1003
WATTS 205 218 231 244 257 268 280 288
CFM 1234111110711024 933 922 - -
WATTS 144 140 152 164 179 183 - -
CFM 128712321186113310991053 - -
WATTS 162 175 187 201 213 221 - -
CFM 138113251277123311811144 - -
WATTS 195 203 217 233 247 258 - -
CFM 12721197114511061055 998 947 906
WATTS 160 168 183 191 211 220 230 243
CFM 1357129712441194114710991049 1008
WATTS 188 202 213 228 245 255 267 284
CFM 1537147814311386133612931253 1208
WATTS 244 258 274 288 303 317 329 341
CFM 1418138313491312127512281178 1141
WATTS 242 258 273 282 299 308 320 338
CFM 1175163516451515151014501430 1400
WATTS 395 420 435 445 455 465 470 475
CFM 1845179017151685159015801530 1500
WATTS 490 505 520 535 550 560 570 575
CFM 1775163516451515151014501430 1400
WATTS 395 420 435 445 455 465 470 475
CFM 2025190018401780172516501620 1580
WATTS 575 595 620 630 645 655 660 670
NOTES:
1. Data shown is dry coil. Wet coil pressure drop is approx.
2. 0.1" H
2
O, for 2 row indoor coil; 0.2” H
2
O, for 3 row indoor coil; and 0.3 H
2
O, for 4 row indoor coil.
3. Data shown does not include filter pressure drop, approx. 0.08 H
2
O.
4. Reduce airflow by 2% for 208V operation.
T4, T5
GPC1460H41**
GPH1460H41**
230
T1, T2, T3
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
Model Speed Volts
E.S.P (In. of H
2
O)
GPC1424H41**
GPH1424H41**
T1
T2,T3
T4, T5
GPC1430H41**
GPH1430H41**
T1
T2,T3
T4, T5
GPC1436H41**
GPH1436H41**
T1
T2,T3
T4, T5
GPC1442H41**
GPH1442H41**
T1
T2,T3
T4, T5
GPC1448H41**
GPH1448H41**
T1
T2,T3
T4, T5