Specifications

2 www.goodmanmfg.com SS-GPH14M
SS-GPH14M www.goodmanmfg.com 3
Specifications
GPH14
24M41A*
GPH14
30M41A*
GPH14
36M41A*
GPH14
42M41A*
GPH14
48M41A*
GPH14
60M41A*

Total BTU/h 24,000 28,600 34,400 41,000 48,000 58,000
Sensible BTU/h 18,700 21,800 26,200 29,600 36,400 42,500
SEER / EER 14/11 14/11 14/11 14/11 14/11 14/11
Decibels 76 76 81 80 79 80
AHRI #s
7470164 7470160 7470161 7470165 7470166 7470162

BTU/h (47°F) 23,000 28,000 33,200 40,500 45,500 57,000
C.O.P (47°F) 3.6 3.6 3.6 3.6 3.6 3.5
BTU/h (17°F) 12,600 15,000 19,000 22,600 26,600 31,400
C.O.P (17°F) 2.2 2.2 2.2 2.2 2.2 2.2
HSPF
8.0 8.0 8.0 8.0 8.0 8.0

Type ECM ECM ECM ECM ECM ECM
Wheel (D x W) 10 x 9 10 x 9 10 x 9 10 x 9 10 x 9 10 x 9
Nominal Cooling CFM 850 1,050 1,200 1,300 1,600 1,850
FLA / LRA 4.3 / -- 4.3 / -- 4.3 / -- 5.8 / -- 5.8 / -- 7.6 / --
No. of Speeds 5 5 5 5 5 5
Horsepower - RPM
½ - 1,050 ½ - 1,050 ½ - 1,050 ¾ - 1,050 ¾ - 1,050 1 - 1,050

Face Area (²) 4.55 4.55 4.55 4.55 6.20
6.20
Rows Deep/ Fin per Inch 4 / 14 4 / 14 4 / 14 4 / 14 4 / 14 4 / 14
Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"
R-410A Refrigerant Charge (oz.)
128 128 115 133 153 180

Horsepower - RPM ¼ - 830 ¼ - 830 ¼ - 830 ¼ - 1,075 ¼ - 1,075 ⅓ - 1,075
FLA/LRA 1.5 / 3.0 1.5 / 3.0 1.4 / 3.0 1.4 / 2.9 1.4 / 2.9 2.5 / 3.0
Fan Diameter / # Fan Blades 22 / 3 22 / 3 22 / 4 22 / 3 22 / 3 22 / 3
Face Area (²) 12.21 12.21 12.21 12.21 15.30 21.32
Rows Deep/ Fin per Inch
2 / 16 2 / 16 2 / 16 2 / 16 2 / 16 2 / 16

Quanty 1 1 1 1 1 1
Type Scroll Scroll Scroll Scroll Scroll Scroll
Stage
Single Single Single Single Single 2 Stage

Voltage/ Phase (60 Hz) 208-230/1 208-230/1 208-230/1 208-230/1 208-230/1 208-230/1
Compressor RLA/ LRA 12.8 / 58.3 14.1 / 73 16.7 / 79 17.9 / 112 21.8 / 117 27.1/ 152.9
Total Unit Amps 18.6 19.9 22.4 25.1 29 37.2
Min. Circuit Ampacity¹ 21.8 23.4 26.6 29.6 34.5 44.0
Max. Overcurrent Protecon² 30 amps 35 amps 40 amps 45 amps 50 amps 70 amps
 380 390 400 410 485 495
¹
Wire size should be determined in accordance with Naonal Electrical Codes. Extensive wire runs will require larger wire sizes.
²
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.